QC Notes Lecture_3 Tray Installation, NSL Noise Susceptibility Level

This article is about ARAMCO Notes Tray Installation, NSL Noise Susceptibility Level  and focusing to the engineers, technicians and supervisors. You will find lot of documents related to this article. Just navigate our website  www.paktechpoint.com  and find more articles. Please! Do not forget to subscribe our You tube channel also. Thanks in Advance.

PLEASE SUBSCRIBE OUR PAKTECHPOINT YOUTUBE CHANNEL

Tray Installation:

Cable Tray Installation:  The publication is intended as practical guide for the proper installation of cable system. Cable tray systems design and Installation shall comply with NEC Article – 392 & 318,
NEMA VE1, NEME VE2 and NEMA FG 1 and follow safe practices as described in NFPA 70E.

Tips for Cable Tray Installation:

Ø Cable tray specification shall be per NEMA VE1 the tray shall be per NEMA VE2.
Ø The distance between consecutive rungs shall not exceed 229 mm (9 Inch).
Ø Cable Ties for Vertical Application shall be provided every 18 inch (after one rung).
Ø Cable Tied for Horizontal application shall be provided every 27 inch (after two rungs).
Ø Unless otherwise noted, the support interval shall be not more than 2.4 meters as per NEMA VE1.
Ø For the Vertical Application cable ties must be 316SS with PVC coated.
Ø The open gap between tray/conduit to the instrument maximum 350 mm.
Ø The cable tray system shall be installation with manufactures standards fittings.
Ø Such as Clamps, Splicer Plates, Connector, Hangers, Reducer Plates, Grounding Brackets Blind, Nut Bolts,
Washers etc.
Ø  The channel cable tray material shall be copper free aluminum (Aluminum with max of 0.4% copper).
Ø Channel cable tray width shall be 3, 4, or 6 inches with a minimum loading depth of ¼ inch.
Ø Non metallic cable tray permitted in corrosive area. Non metallic cable trays shall be made of
flame retardant material.
Tips for Cable Tray Installation
Tips for Cable Tray Installation

 

Tips for Cable Tray Installation

NSL: Noise Susceptibility Level

Level 1: High to Medium susceptibility analog signals of less than 50V and discrete instrument signal of less than 30V.
Level 2:  Low susceptibility switching signal greater than 30V, analog signals grater then 50 V and 120 ~ 240 AC feeder less than 20 Amps.
Level 3:  Power AC and DC buses of 0 ~ 1000 V with currents of 20 ~ 800 Amps.
Tray to Tray Spacing in mm:
NSL      1          2          3
1          0          150       650
Tray to Conduit Spacing in mm:
NSL      1          2          3
1          0          100       450
Conduit to Conduit Spacing in mm:
NSL      1          2          3
1          0          75         300
Tray to Tray:
Level 1 to Level 2 gap should be             150 mm
Level 2 to Level 3 gap should be             500 mm
Level 1 to Level 3 gap should be             650 mm
Tray to Conduits: 
Level 1 to Level 2 gap should be             100 mm
Level 2 to Level 3 gap should be             350 mm
Level 1 to Level 3 gap should be             450 mm
Conduit to Conduit:
Level 1 to Level 2 gap should be             75 mm
Level 2 to Level 3 gap should be             225 mm
Level 1 to Level 3 gap should be             300 mm

 