Analog Temperature Transmitter  Calibration With HART Parameters

This article is about Analog Temperature Transmitter  Calibration With HART Parameters  and focusing to the engineers, technicians and supervisors. You will find lot of documents related to this article. Just navigate our website  www.paktechpoint.com  and find more articles. Please! Do not forget to subscribe our You tube channel also. Thanks in Advance.

PLEASE SUBSCRIBE OUR PAKTECHPOINT YOUTUBE CHANNEL

Analog Temperature Transmitter  Calibration With HART Parameters

Applications and Hands On Exercises

Calibrator Setup Screen

Start by selecting the desired SETUP functions
Select  temperature units and turn on 24V loop supply.
•Press the “NEXT PAGE” soft key TWICE
•Select Temperature units using the ARROW key
•Press the “ENTER” key and select Units  using the ARROW keys
•Press the “ENTER” key
•Push the “DONE” soft key
2.  Continue by selecting the desired MEASURE and SOURCE functions.
Use Type K thermocouple and milliamps
                                               

Transmitter Cal Measure Configuration

•Press the “MEAS/SOURCE”  key to get the  full MEASURE screen
•Press the “mA” key to select milliamps

Transmitter Cal Source Configuration

•Press the “MEAS/SOURCE” key to get the SOURCE screen
•Press the “TC” key once to select Thermocouple type
•Select ‘K’ and press the “ENTER” key
•Select “Linear T” transmitter type and press the “ENTER” key
•Use the “Numeric Keypad” to enter a temperature value and press the “ENTER” key

Transmitter Cal Measure & Source

•Press the “MEAS/SOURCE” key to get the Split screen
•The Measure portion of the screen should be in mA
•The Source portion of the screen should be in Temperature
Select Instrument to be Calibrated
•Press the “As-Found” soft key.
•4 types of instruments
•Instrument – linear
–Calibrates linear transmitters
·Ö Instrument
–Calibrates square law transmitters
•1 Point Switch test
•2 Point Switch test Highlight
“Instrument” to select linear responding transmitters
•Select “Instrument”

Transmitter Cal Parameters

•Define your procedure by defining end points, test tolerance, and strategy
•Press 4 using the “Numeric key pad” and press “ENTER”
•Repeat to select:
 –100% Value
 –Tolerance
•Press the “Down Arrow” key to highlight the Source 0% Value field
•Specify from transmitter’s  span:
–0% Value
–100% Value

Select Test Strategy

•Highlight the Test Strategy field using the “Arrow” keys
•Press the “ENTER” key
•Using the ARROW keys select the 3 point up/down strategy and press the “ENTER” key
•Press the “DONE” soft key
TC Transmitter As Found Test
•Verify Lead connections:
–Connect the TC connector to the 743’s TC jacks
–Connect the Loop Supply leads to the CENTER set of jacks on the 743
•Test can be run in either Automatic or Manual mode
•Press the “AUTO TEST” soft  key
As Found Results
Use the internal tests to verify and document the “As Found” – before adjustment – conditions
•Results displayed
•Display highlights Out-of -Tolerance measurements
•Press the “DONE” soft key

Document Transmitter & tech details

•Instrument specific information is saved with the Calibration Data
•The user enters:
–Tag information
–Serial number
–Identification field
•Tag information is required for documented data
•Press the “DONE” soft key

Transmitter adjustment 

•Press the “ADJUST” soft key
•Adjust the zero adjustment until the error is in forward video
•Select GoTo 100% and adjust the Span as necessary
–Repeat Zero and Span until the desired results (error forward video) are obtained
•Linearity can be checked by using “Goto 50%” soft key.
•Once all (3) tests, (0%, 50% and 100%) pass, go to the As-Left test

 

Transmitter calibration As-Left measurement

The As-Left test will repeat the initial tests to verify and document the “As Left”, post adjustment condition of the
transmitter
•Press “As Left”
•Push the “DONE” soft key to accept the procedure test conditions
•Press “Auto Test” and review  the results
•The As-Left test is successful if all Error% results are in forward video.
• If they fail, additional adjustment and additional As-Left test(s) are necessary.
Reviewing Results
•Press the “More Choices” soft key until the “Review Memory” soft key is visible
•Push the “Review Memory” soft key
•Use the ARROW keys to select the TAG number of the desired result
•Select the As Found entry and press the “ENTER” key

 

•Review your procedure template
•Press the “Next Page” soft key to Review your result table
•Press the “Tag” soft key to  review your ID data
•Press the “DONE” soft key Twice
•Now look at the As Left data
Please read also:  Linearity Check and Calibration Of Vibration Probe (Axial and Radial)  Proximitor
Please read also: TEMPERATURE TRANSMITTER CALIBRATION CHECKING OF TEMPERATURE SENSORS
Please read also: Differential Pressure DP Type Transmitter Calibration
Please read also: HART Pressure Calibration and Zero Calibration of Pressure Transmitter
Please read also: HART CALIBRATOR FUNCTIONS EXPLANATION FOR CALIBRATION
Please read also: Calibration of DP type level transmitters with zero suppression
Please read also:  DISPLACER TYPE LEVEL TRANSMITTER CALIBRATION INSTRUMENTATION