UNINTERRUPTIBLE POWER SUPPLY FIELD INSTALLATION CHECK LIST
VISUAL AND MECHANICAL INSPECTION
Yes
|
No
|
|
1. All components have been checked against one-line diagram and have been signed off by all agencies.
|
||
2. Safety equipment in place and serviceable per standards.
|
||
3. All power and control wiring tested, marked, color coded and properly phased (AC/DC circuits).
|
||
4. HVAC checked out, operational and on.
|
||
5. All cabinets, enclosures and rooms clean.
|
||
6. Replacement power and control fuses, control boards available for both inverter and rectifier.
|
||
7. Normal power is available for start-up and commissioning.
|
||
8. All vendor (manufacturer) manuals and factory test documents are available.
|
||
9. Batteries tested per Manufacturers instructions.
|
ELECTRICAL INSPECTION
Yes
|
No
|
|
1. UPS start-up procedure approved and available.
|
||
2. Verify inverter check-out by vendor Representative.
|
||
3. Witness and verify output wave forms are correct.
|
||
4. Witness and verify output voltage is set and correct.
|
||
5. Witness and verify all alarm functions.
|
||
6. Witness and verify static switch function.
|
||
7. Verify operation of manual bypass switch.
|
||
8. Verify all voltmeters/ammeters are calibrated and correct.
|
||
9. Insure Operations has sufficient operator training on UPS system.
|
Electrical Function Testing
Equipment Required
Digital Voltmeter (DVM)
Spectrum Analyzer to 10 Khz
Multi-amp tester
Dual trace Oscilloscope, (ungrounded plug)
1. UPS on line and unloaded.
Yes
|
No
|
|
a. Connect Oscilloscope and DVM to UPS output, compare reading to the installed output meter.
|
||
b. Take Polaroid photo or draw wave form and compare wave form of output to vendor illustration.
|
||
c. Make adjustments per vendor instruction manual if required.
|
2. UPS on line and loaded.
Yes
|
No
|
|
a. Repeat steps a, b, and c in (1) above.
|
||
b. Switch “off” Primary feed, monitor Oscilloscope for switching transients, voltage level, and wave from purity.
Make adjustments per static switch vendor instruction manual if required. |
||
c. Reinitialize UPS inverter per vendor manual, check synchronization indicator and time to synchronize
|
||
d. Perform vendor under voltage and over-current switching checks, using multi-amp test set. Monitor the UPS output with DVM and Oscilloscope. Adjust if necessary.
|
||
e. Connect Spectrum Analyzer to UPS output. Set to 7th harmonic and log vertical scale. Calculate the amplitude of each harmonic. If harmonic amplitudes exceed 4% corrections must be made.
|
||
f. Remove Primary and Alternate power supplies and monitor UPS output. Repower the system with Primary and Alternate power supplies when the output amplitude starts decreasing.
|