SF6 Switchgear Electrical Testing (Pad Mounted)

Electrical testing of SF6 switchgear is essential to ensure the safety, reliability, and performance of the equipment. SF6 (sulfur hexafluoride) switchgear is commonly used in high voltage applications for its excellent insulating and arc quenching properties.

SF6 Switchgear Electrical Testing (Pad Mounted)

Read Also: SF6 Circuit Breaker: Working Principle, Types, Applications, Technical Issues

Mechanical Inspection of SF6 Switchgear (Pad-Mounted).

Mechanical inspection of SF6 switchgear, particularly pad-mounted switchgear, is important to ensure the equipment’s structural integrity, proper functioning, and safety.

  1. Inspect for physical damage and compare nameplate data with plans and specifications.
  2. Perform mechanical operations tests in accordance with manufacturer’s instructions.
  3. Verify proper operation grounding switch.
  4. Check interlocks for correct operation.
  5. Check for positive gas pressure in SF-6 switches, verify no leaks.
  6. Verify use of proper cable termination’s (Elastimold 600 Amp with voltage test point) and phasing.
  7. Verify hardware is properly installed and torqued.
  8. Grounding installed.
  9. Switches have exterior coating in accordance with standards requirements for area location.
  10. Verify current rating and sizing of current transformers and that they are properly installed.
  11. Verify internal arc over pressure exhaust venting is properly installed.

By conducting a thorough mechanical inspection of SF6 switchgear, including pad-mounted switchgear, you can identify and address any mechanical issues or deficiencies promptly, ensuring the equipment’s reliable operation and longevity. Regular inspections should be performed according to manufacturer recommendations, industry standards, and regulatory requirements to maintain compliance and minimize the risk of equipment failure or accidents.

Electrical Testing of SF6 Switchgear (Pad-Mounted).

Electrical testing of SF6 switchgear, particularly pad-mounted switchgear, is essential to ensure the equipment’s electrical integrity, safety, and proper functioning. Here are some key electrical tests commonly conducted on SF6 pad-mounted switchgear:

  1. Perform insulation resistance test on each pole, phase to phase and phase to ground for one (1) minute.
  2. Perform A.C. or D.C. high potential test on each pole to ground and pole to pole with the switch in the closed position. High potential test voltages shall be applied in accordance with vendors recommended values.
  3. Perform contact resistance test across each interrupter. Contact resistance shall be determined in micro-ohms. Any value exceeding 150 micro-ohms or any values which deviate from adjacent poles or similar switches by more than 20 percent (20%) should be investigated.
  4. Verify continuity of ground connection between breaker and ground grid via current injection.
  5. Perform trip tests for circuit breakers.
  6. Verify settings and operation of protective relays.

Nameplate Data of SF6 Switchgear (Pad-Mounted)

Switch No.
Manufacturer
Model No.
Serial No.
Rated Voltage
Rated Current

High Potential Test of SF-6 Switchgear (Pad-Mounted)

Breaker ClosedCurrent AC or DCBreaker OpenCurrent AC or DC
Phase A to Gnd.Phase A line to load.
Phase B to Gnd.Phase B line to load.
Phase C to Gnd.Phase C line to load.
Phase A to B.
Phase A to C.
Phase B to C.

Test Data SF-6 Switchgear (Pad-Mounted)

Electrical
Mechanical tests
Manufacturer’s recommended test values.PHASE APHASE BPHASE C
Insulation Resistance.Breaker closed
Phase to ground Megohms_____
Breaker closed
Phase to ground Megohms______
Breaker closed
Phase to ground Megohms______
Contact Resistance.Breaker closed Micro-Ohms _______Breaker closed Micro-ohms _______Breaker closed Micro-ohms _________
Interrupter AC High Potential.PASS_____
FAIL _____
PASS _____
FAIL _____
PASS ______
FAIL ______

What is Insulation Resistance Test?

This test measures the resistance of the insulation material between conductive parts of the switchgear. It helps identify any deterioration or contamination of insulation that could lead to electrical breakdown.

What is Dielectric Strength Test?

Also known as the hi-pot test, this test applies a high voltage between conductive parts of the switchgear and ground to verify the insulation’s ability to withstand voltage stress without breakdown.

What is Partial Discharge Measurement?

Partial discharge (PD) testing detects small electrical discharges within the insulation of the switchgear. PD activity can indicate insulation degradation and potential failure points, so measuring and analyzing PD levels are critical for assessing the insulation condition.

What is Circuit Breaker Testing?

This includes various tests to evaluate the performance of SF6 circuit breakers, such as timing tests (open/close timings), contact resistance measurements, and insulation resistance tests on circuit breaker poles.

What is Contact Resistance Measurement?

This test measures the resistance between contacts in the switchgear, ensuring that the contacts are in good condition and can carry current effectively.

What is SF6 Gas Analysis?

SF6 gas is used as an insulating and arc-quenching medium in SF6 switchgear. Gas analysis tests measure the purity, moisture content, and other characteristics of SF6 gas to ensure it meets specified standards and remains effective as an insulating medium.

What is Temperature Rise Test?

This test assesses the temperature rise of switchgear components during normal operation and under specified load conditions to ensure they do not exceed allowable limits.

What is Protection Relay Testing?

SF6 switchgear often incorporates protection relays to detect faults and isolate electrical circuits. Testing protection relays involves functional tests, calibration, and verification of relay settings to ensure proper operation and coordination with other protection devices.