Overhead Transmission & Distribution Equipment Installation & Commissioning

This article is about Overhead Transmission & Distribution Equipment Installation & Commissioning for commercial buildings, plants and refinery projects as per international codes and standards.

Transmission & Distribution Equipment Installation

Load break switches shall be provided at sectionalizing points.
Surge arresters shall be installed at distribution transformer installations.
Surge arresters shall be installed at capacitor bank installations.
Surge arresters shall be installed at recloser installations.
Surge arresters shall be installed at metering installations.
Surge arresters shall be installed at aerial-to-underground cable termination points.

Surge arresters shall be of the distribution class, metal-oxide, gapless type rated per Table 5.

System Voltage (kV) Arrester Rating (kV)
4.16 6.0
13.8 12
34.5 27
The grounding electrode for surge arresters shall be minimum 16 mm (5/8 in) diameter by 3 m (10 ft) local copper or copper clad ground rod(s) driven along the center line of the circuit.
The ground rod(s) shall also be bonded to the plant or substation ground grid if located within 15 m of the rod.
The resistance to ground of the surge arrester ground shall not exceed 25 ohms.
The surge arrester grounding terminals shall be connected, with minimum bends, directly to the local ground rod.
Minimum arrester-to-arrester clearance shall be per Table 4.
Table 4
System Voltage (kV) Clearance mm
4.16 230
13.8 410
34.5 710
Fused cutouts shall be provided for transformers fed directly from overhead distribution lines.
and fused cutouts shall be provided for capacitor installations on overhead distribution lines.

International Codes & Standards

SAES-P-107 Overhead Distribution System