ELECTRICAL TEST LOW VOLTAGE MOTOR CONTROLGEAR
VISUAL INSPECTION
- Inspect primary and auxiliary equipment for physical damage, missing parts and proper assembly.
- Compare equipment nameplate data with one line diagram, design plans and/or starter schedule.
- Check nameplate voltage and current ratings for breaker, contactors and fuses.
- Compare overload heaters with motor full load current for proper size.
- Verify component sizing versus load.
- Check stab finger to bus tightness on draw-out cubicles.
- Protective grounding is correctly installed and connected to main ground.
- Remove shipping and blocking material from Motor Control Center/Switchboard.
- Check draw-out cubicles and wire ways for cleanliness.
MECHANICAL INSPECTION
- Torque all accessible bolted connections.
- Check insulators and the insulation system.
- Inspect main bus and bus taps to switches and voltage transformers.
- Manually operate breakers and contactors. Check for freedom of movement of all moving parts.
- Check for main contact pressure, alignment and full contact area on contactors.
- Check operation of door mechanical circuit breaker trip and reset linkage.
ELECTRICAL TEST IN CONTROLGEAR
- Check wiring point to point and megger.
- Check wire markers, and that terminal block connections are secure and properly identified.
- Megger test main bus phase to ground and phase to phase.
- Measure bus resistance and joint contact resistance.
- Inspect all protective relays and devices for correct operation and settings.
- Check to see that space heaters are connected and operable.
- Megger horizontal and vertical bus and outgoing feeder circuits.
- Check calibration of VT’s, CT’s, voltmeters and ammeters.
- Check rating of all fuses.
- Verify under voltage relay trip/alarm function.
- Verify ground fault protection for 30 horsepower motors and larger.
- Set motor circuit protectors.
- Check effectiveness of tripping devices.
- Megger and high potential test contactors and circuit breakers phase to phase and phase to ground.
- Measure the contact resistance of each power circuit breaker.
- Measure the contact resistance of each contactor.
- Check the Phase Rotation of the voltage on the main bus.
NAMEPLATE INFORMATION
TESTS ARE PERFORMED IN ACCORDANCE WITH VALUES RECOMMENDED BY THE MANUFACTURER.
MOTOR CONTROL CENTER RECORDED TEST DATA
| ITEMS TESTED | MEGGER TEST INSULATION RESISTANCE IN MEG-OHMS |
| Phase A to Ground | |
| Phase B to Ground | |
| Phase C to Ground | |
| Phase A to Phase B | |
| Phase B to Phase C | |
| Phase C to Phase A |
MOTOR CONTROL CENTER CONTACT RESISTANCE
MOTOR CONTROL CENTER DATA SHEET
Voltage Rating:______________



Like!! Thank you for publishing this awesome article.