HVAC Control System Fault Definitions

This article is about general HVAC Control System Fault Definitions used in Integrated Automation System or Building Automation System.

HVAC Control System Fault Definitions

Fault Rule Name

Fault Rule Short Description

AHU Cooling & Heating Cycling Finds periods when the heating and cooling are cycling between each other within a threshold. This indicates that the unit is fighting back and forth between its mechanical components.
AHU Cooling & Heating Simultaneously Finds periods when discharge fan is on, heating is on and cooling is on for over a duration.
AHU Cooling Failure Finds periods when discharge fan is on, cooling is on, and discharge temperature sensor is not under mixed air sensor minus a threshold for over a duration.
AHU Cooling Valve Leaking Generates a fault when discharge fan is on, cooling valve is closed, and discharge temperature sensor is under mixed air sensor by a threshold.
AHU Discharge Fan Failure Generates a fault when discharge fan is on and duct static pressure is below a threshold.
AHU Discharge Pressure Setpoint Unreachable Finds periods over a duration when discharge fan is on and discharge pressure is below or above the discharge pressure set point by a threshold.
AHU Discharge Pressure Unstable Generates a fault when the discharge fan is on and the discharge pressure bounces above and below the discharge pressure set point by a dead band
AHU Economizing & Cooling Simultaneously Finds periods when discharge fan is on, outdoor damper is open more than a threshold and cooling is on for over a duration.
AHU Economizing & Heating Simultaneously Finds periods when discharge fan is on, outdoor damper is open more than a threshold and heating is on for over a duration.
AHU Heating Failure Finds periods when discharge fan is on and discharge temperature sensor is not greater than mixed air sensor plus a threshold for over a duration.
AHU Heating Valve Leaking Generates a fault when discharge fan is on, heating valve is closed, and discharge temperature sensor is greater than the mixed air sensor by a threshold.
AHU Outside Damper Stuck Closed Generates a fault when discharge fan is on, outdoor damper is greater than a threshold and the calculated outdoor air percentage is lower by more than a percentage.
AHU Outside Damper Stuck Open Generates a fault when discharge fan is on, outdoor damper is less than a threshold and the calculated outdoor air percentage is higher by more than a percentage.
AHU Low Outside Airflow Generates a fault when the discharge fan is on and the outside airflow is below the outside airflow set point during occupancy.
AHU Unstable Outside Airflow Generates a fault when the discharge fan is on and the outside airflow bounces above and below the outside airflow set point by a dead band.
AHU Unit On Discharge Fan Off Generates a fault when discharge fan is off and anything is on; hot water valve is more than a threshold, any heating stage is on, chilled water valve is more than a threshold, or any cooling stage is on.
AHU Discharge Temperature Set point Unreachable Finds periods when discharge fan is on and any discharge temperature cannot get within a threshold of discharge temperature set point for over a duration.
AHU Discharge Temperature Unstable Finds periods when discharge fan is on and any discharge temperature bounces above and below the discharge temperature set point by a dead band.
AHU Low/High Pressure Finds periods when the AHU supply pressure is outside of the set point (+/- 0.25”) over a duration (~15 minutes).
AHU Low/High Temperature Finds periods when the AHU supply temperature is outside of the set point (+/- 2o F) over a duration (~15 minutes).
AHU Unit On Discharge Fan Off Finds periods when discharge fan is off and anything is on; hot water valve is more than a threshold, any heating stage is on, chilled water valve is more than a threshold, or any cooling stage is on for over a duration.
Bad Energy Data Finds periods when data contains values outside of low and high limits or the data is NaN for at least a duration
Heat Running During Warm Weather Finds periods when heat is are running and the outside air temperature is above a threshold.
Building Running Too Late Finds periods when the demand of the building does not drop off by at least a percentage or threshold for a duration after occupancy is over.
Building Starting Too Early Finds periods when the demand increases by a percentage or threshold for a duration before building occupancy.
Boiler Cycling Generates a fault when the boiler stays on or off for less than a duration.
Boilers Running During Warm Weather Generates a fault when boilers are running and the outside air temperature is above a threshold.
Cabinet/Door Heater Zone Temperature Out of Range Finds periods for longer than a duration when the space temperature is less than or greater than, the heating temperature setpoint by a threshold.
Chiller Cycling Generates a fault when the chiller stays on or off for less than a pre-specified duration.
Chilled Water Plant Demand Peak Finds chilled water demand peaks throughout the day, as measured against a facility benchmark.
Chilled Water Pressure set point Unreachable Finds periods when any pump is on and the differential pressure cannot get within a threshold of differential pressure set point for over a duration(~15 minutes).
Chilled Water Pressure Unstable Finds periods when any pump is on and the differential pressure cannot stay within a threshold of differential pressure set point for over a duration (~15 minutes).
Chilled Water Plant Temperature Setpoint Unreachable Finds periods when any chiller is on and the leaving CHW temperature is unable to reach a pre-specified threshold of the CHW supply setpoint for over a duration.
Chilled Water Plant Leaving Temperature Unstable Generates a fault when the leaving CHW temperature bounces above and below the supply temperature set point by a dead band.
Chilled Water Low/High Temperature Finds periods when the chiller provides water outside of the set point (+/- 2o F) over a duration (~15 minutes).
Chilled Water Mixing Finds periods when the chilled water return temperature is not more than 4o F above the chilled water supply temperature over a duration (~15 minutes).
Chilled Water System Failure Finds periods when any chiller is on within the chiller plant and the chilled water leaving temperature is not within a specified range for over a duration (~15 minutes).
Chiller Running During Unoccupied Periods Generates a Fault if the chiller plant is operating outside the normal occupancy schedule.
Cooling Set point Out of Range Finds periods when the cooling set point is below a threshold for over a duration.
Cooling Tower Temperature Set point Unreachable Finds periods when cooling tower leaving water temperature cannot get within a threshold of the leaving water temperature set point for over a duration.
Cooling Tower Temperature Unstable Finds periods when cooling tower leaving water temperature bounces above and below the water temperature set point by a dead band.
Double Dipping Data This searches the database and finds data which is duplicated (point readings being stored in separate areas) and notifies administrator to reduce duplicated points, trends or data. Finds periods when a point’s history contains two or more data points within a leeway of an interval for at least a duration.
EF Not Running When Emergency Generator is Engaged Generates a fault when any exhaust fan serving an emergency generator is not operating when the generator has been engaged
EF Not Running Under Thermostatic Control Finds periods when any exhaust fan controlled via thermostat is not operating when space temperature.
EF Running During Unoccupied Periods Finds periods when any exhaust fan is operating outside the normal schedule.
Floor VAV Unstable Airflow Generates a fault when the floor VAV is active and the supply airflow bounces above and below the supply airflow set point by a dead band.
Heat Exchanger Temp Set Point Unreachable Finds periods when the secondary leaving water temperature cannot get within a threshold of secondary leaving water temperature set point, while either a heat exchanger pump is on or a hot water system pump is on, for over a duration.
Heat Exchanger Temp Unstable Finds periods when the secondary leaving water temperature bounces above and below the secondary leaving water temperature set point by a dead band.
Heating Set Point Out of Range Finds periods when the heating set point is above a threshold for over a duration.
Hot Water Circ Pump Running Generates a fault when hot water heating coil pumps are running and no secondary hot water pumps are running in the system.
Hot Water Plant Demand Peak Finds hot water demand peaks throughout the day, as measured against a facility benchmark.
Hot Water Pressure Setpoint Unreachable Finds periods when any pump is on and the differential pressure cannot get within a threshold of differential pressure set point for over a duration.
Hot Water Pressure Unstable Finds periods when any pump is on and the differential pressure cannot stay within a threshold of differential pressure set point for over a duration.
Hot Water Plant Temperature Setpoint Unreachable Finds periods when any boiler is on and the leaving HW temperature is unable to reach a pre-specified threshold of the HW supply setpoint for over a duration.
Hot Water Plant Leaving Temperature Unstable Generates a fault when the leaving HW temperature bounces above and below the supply temperature set point by a dead band.
Missing Data Finds periods when a record’s history contains zero data points within a leeway of an interval for at least a duration.
Occupied Cooling Setpoint Out of Range Finds periods over a duration when the occupied cooling set point is below a threshold.
Occupied Heating Setpoint Out of Range Finds periods over a duration when the occupied heating set point is above a threshold.
Power Peak Finds when power is 5% higher or 5% lower than the previous period or year (similar for day, week, month, year).
Pump Cycling Generates a fault when the pump stays on or off for less than a specified duration.
Sensor Failure Finds periods when a sensor does not change by a threshold for a 24-hour period.
Short Demand Peak Finds short demand peaks throughout the day.
Split System A/C Unit Cooling Setpoint Out of Range Finds periods over a duration when the room or zone temperature is unable to maintain a threshold above or below the cooling setpoint.
Terminal Unit Airflow Setpoint Unreachable Finds periods over a duration when the discharge airflow cannot get within a threshold of discharge airflow set point (while the FCU fan is on).
Terminal Unit Airflow Unstable Generates a fault when the discharge airflow bounces above and below the discharge airflow set point by a dead band.
Terminal Unit Heating Failure Generates a fault when the FCU fan is on (if applicable), heating is on, and discharge temperature sensor is not greater than the discharge air sensor plus a threshold.
Terminal Unit Heating Valve Leaking Generates a fault when FCU fan is on (if applicable), heating valve is closed, airflow is above a threshold, and the discharge temperature sensor is above discharge temperature by a threshold.
Terminal Unit Zone Temperature Out of Range Finds periods when the zone air temperature is less than or greater than the zone set point(s) by a threshold for longer than a duration.
Underfloor Heating Space Temperature Out of Range Finds periods when the underfloor heating space temperature is less than or greater than the setpoint(s) by a threshold for longer than a duration.
Unoccupied Cooling Setpoint Out of Range Finds periods over a duration when the unoccupied cooling set point is below a threshold.
Unoccupied Heating Setpoint Out of Range Finds periods over a duration when the unoccupied heating set point is above a threshold.
Zone Cooling Damper Malfunction Finds periods when the cooling damper is open above a threshold and the zone damper discharge air temperature is not within a threshold of the cold deck discharge air temperature for over a duration.
Zone Heating Damper Malfunction Finds periods when the heating damper is open above a threshold and the zone damper discharge air temperature is not within a threshold of the hot deck discharge air temperature for over a duration.
Zone Temperature Out of Range (Cooling) Finds periods when the zone air temperature is less than the zone set point(s) by a threshold for longer than a duration.
Zone Temperature Out of Range (Heating) Finds periods when the zone air temperature is greater than the zone set point(s) by a threshold for longer than a duration.
Underfloor Heating Space Temperature Out of Range Finds periods when the underfloor heating space temperature is less than or greater than the setpoint(s) by a threshold for longer than a duration.

Leave a Comment

error: Content is Protected.