Measurement and calculation the position of control valve

 This article is about Calculation the position of control valve focusing to the engineers, technicians and supervisors. You will find lot of documents related to this article. Just navigate our website www.paktechpoint.com  and find more articles. Please! Do not forget to subscribe our Youtube channel also. Thanks

PAKTECHPOINT YOUTUBE CHANNEL SUBSCRIBE BY CLICKING

Calculation the position of control valve

A loop controller gives the loop signal of 7.8 mA of the control valve. How much valve will be open or position of Control valve?
Calculation the position of control valve
Because this relation is linear so we will use standard 4-20 mA formula.
              Y= (16/100)X+4
Y= output current signal
X= Process variable in percentage
 Solution:
             7.8= (16/100) X+4
             3.8= 0.16 X
              X= 23.75 %
Hence if we are receiving 7.8 mA current it means valve is 23.75 % open.