NEC IEC Based Low Voltage Cables Selection Criteria

Main keywords for this article are NEC IEC Based Low Voltage Cables Selection Criteria, IEC Low Voltage Cable, Low Voltage Cable Ampacity, Low Voltage Cable Testing and Inspection.

NEC IEC Based Low Voltage Cables Selection Criteria

Low Voltage Cables Selection References

American Society for Testing and Materials (ASTM)
B 3 Specification for Soft or Annealed Copper Wire B 8 Specification for Concentric-Lay-Stranded Copper Conductors, Hard, Medium-Hard, or Soft
Institute of Electrical and Electronic Engineers (IEEE)
383 Type Test of Class 1E Electric Cables
1202 Flame Testing of Cables for Use In Cable Trays
Insulated Cable Engineers Association / National Electric Manufacturers Association (ICEA/NEMA)
ICEA S-95-658/NEMA WC-70 Power Cables Rated 2000 Volts Or Less For The Distribution Of Electrical Energy
International Electrotechnical Commission (IEC)
60038 IEC Standard Voltages
60228 Conductors of Insulated Cables
60332-3 (series)Tests on Electric and optical fibre Cables under Fire Conditions: Test for vertical flame spread of vertically-mounted bunched wires or cables.
60502 Extruded Solid Dielectric Insulated Power Cables for Rated Voltages from 1 kV up to 30 kV.

IEC 60227 : Polyvinyl chloride insulated cables of rated voltages up to and including 450/750 V
National Fire Protection Association (NFPA)
70 National Electrical Code (NEC),
Underwriters Laboratories, Inc. (UL)
44 Rubber-Insulated Wires and Cable
1569 Metal Clad Cables

NEC IEC Based Low Voltage Cables Selection Criteria

This article is about the general requirements for low voltage power cables.

  • Low voltage power cable shall be manufactured and tested in accordance with IEC 60502 or ICEA S-95-658/NEMA WC-70.
  • Cable manufactured to IEC 60502 shall conform to section 5.
  • Cable manufactured to ICEA S-95-658/NEMA WC-70shall conform to section 6.

IEC Low Voltage Cable

  • Cable shall be manufactured and tested in accordance with IEC 60038, 60228, 603323, 60502.
  • The conductors shall be plain annealed circular stranded copper conforming to IEC 60228 Class 2.
  • Low voltage single conductor cables shall be insulated with cross-linked polyethylene (XLPE) insulation extruded directly over the copper conductors or ethylene propylene rubber (EPR). The cable construction shall be in accordance with IEC 60502. Table I lists the minimum acceptable insulation thickness of the cables.

Matching Wire Size to Circuit Amperage

https://youtu.be/clZ1c05ngbg

 

NEC IEC Based Low Voltage Cables Selection Criteria

IEC Low Voltage Cable

Low Voltage Cable Ampacity

  • Multiconductor cables shall have a flame retardant and termite resistant PVC jacket. The material for the cable jacket shall be extruded directly onto the surface to be covered. Table II lists the minimum acceptable jacket thickness for armored and nonarmored multiconductor cables. The cable jacket shall be continuous, homogeneous, voidless, seamless, and free of foreign material.

    Low Voltage Cable Testing and Inspection

  • Cable shall conform to flame retardance test in accordance with IEC 60332-3.

ICEA Low Voltage Cable 

  • Cable shall be manufactured and tested in accordance with all applicable American standards listed in section 2, with the additional requirements of this section.
  • Conductor material shall be plain annealed copper in accordance with ASTM B 3. Conductors shall be concentric lay Class B stranded in accordance with ASTM B 8.
  • Low voltage single conductor cable shall be insulated with cross-linked polyethylene (XLPE) insulation extruded directly over the copper conductors or ethylene propylene rubber (EPR). Table III lists the minimum acceptable insulation thickness of the cables. The cable construction shall be in accordance with UL 44.

    NEC IEC Based Low Voltage Cables Selection Criteria

  • Multiconductor cables shall have an overall PVC jacket consisting of an extruded layer of black PVC suitable for the operating temperature of the cable. Tables IV and V list the minimum acceptable jacket thickness. The cable jacket shall be continuous, homogeneous, voidless, seamless, and free of foreign material. The PVC jacket shall be flame retardant and termite resistant.IEC Low Voltage Cable

    Low Voltage Cable Ampacity

Number and Size of Cables

Low Voltage Cable Power Cables

Insulated conductors shall be supplied in the following standard sizes: 12, 10, 8, 6, 4, 2, 1/0, 2/0, and 4/0 AWG; 250, 350, 500 and 750 MCM or the standard metric equivalent. Multiconductor power cable shall contain 2 or more power circuit conductors plus ground wire(s) and may also contain insulated control wires in sizes 14 or 12 AWG. Table VI defines the acceptable US to Metric cross reference.

Low Voltage Cable Testing and Inspection

Control Cables

Conductors shall be 14, 12 or 10 AWG or the standard metric equivalent. The number of conductors should in general be 5, 12, 19 or 37.

Ground Conductors

Ground conductors shall conform to NFPA 70. See Table VII for minimum acceptable grounding conductor sizes.

NEC IEC Based Low Voltage Cables Selection Criteria

Low Voltage Cable Ampacity

The base current carrying capacity of cables shall be in accordance with NFPA 70, Tables 310-16 to 310-20.

Single Conductor Cables – Building wires

  • Insulated conductor of single conductor cable shall have PVC jacket unless otherwise specified in below data sheet.
    9.2 THHN / THWN type single core wire installed in conduit for wiring of lighting fixture circuits,
    receptacles and building services equipment shall comply with requirements of NEC – Article 310,
    UL Standards 83 and 1063
    9.3 PVC type single core building wire shall be compliant with IEC 60227-1

Multiconductor Cables

Non-armored Cables

  • Insulated conductors of the multiconductor cable shall be assembled with grounding conductors and non-hygroscopic filler material in the interstices. Assembly shall be bound with a binder tape or other suitable material, where necessary. PVC outer jacket shall be extruded over the bound assembly.

Armored Cables

  • Armored cable shall conform to UL 1569. Armor material may be galvanized steel or aluminum. Armor may be interlocking metal tapes; a continuous
    corrugated sheath; or a single layer of round wires.
  • Insulated conductors shall be assembled with grounding conductors and nonhygroscopic filler material in the interstices. The assembly shall be bound with a binder tape or other suitable material, where necessary. An extruded layer of flame retardant PVC compound shall be applied over the core assembly to form a circular cable and to serve as bedding for the armor. The armor shall then be applied using additional bedding material if required. If a layer of round wire armor is used, a galvanized steel tape may be applied over the wire armor as binder in open helix.
  • Cables shall have an overall PVC jacket applied over the armor, consisting of an extruded layer of black PVC suitable for the operating temperature of the
    cable. PVC jacket shall be flame retardant and termite resistant.

Low Voltage Cable Testing and Inspection

The following routine tests shall be performed:
a. DC conductor resistance test
b. Insulation resistance test
c. High voltage test (Hi Pot)

Low Voltage Cable Identification and Tagging

  • The individual wires in multiconductor control cables shall be color coded in accordance with ICEA S-95-658/NEMA WC-70,
  • Power cable shall have the following core (color) designations:
    a. Single core: Black
    b. 2 cores: Black, White
    c. 3 cores: Yellow, Red, Blue
    d. 4 cores: Black, Red, Blue, Yellow
    e. Ground Conductor: Insulated Green, with insulation
  • Finished cable shall be identified by embossing the following identifications on cable external surface at less than 1 m intervals longitudinally:
    Manufacturer’s name or trademark
    Year of manufacture
    Number of cores and size
    Rated voltage and cable description
    UL or other accredited testing laboratory label Conductor material
    Size of ground conductor
    Conductor temperature rating
    Insulation type and thickness
    Oil resistance I or oil resistance II
  • A weatherproof tag suitable for 2 years of outdoor storage shall be affixed to each reel, visible without removal of packing material, with the following information:
    a. Name and kind of cable
    b. Number of cores and size
    c. Length
    d. Net weight and gross weight
    e. Direction of winding of cable
    f. Indicator of cable end position
    g. Manufacturer’s name or trademark
    h. Year and month of manufacture
    i. Drum number and color identification, if specified in purchase order
    j. Purchase order number
    k. Manufacturer’s item code number
    l. Manufacturer’s reel number
  • Data sheet of low voltage cable     

NEC IEC Based Low Voltage Cables Selection Criteria

NEC Low Voltage Switchgear Design Requirement

Main keywords for this article are NEC IEC Based Low Voltage Cables Selection Criteria, IEC Low Voltage Cable, Low Voltage Cable Ampacity, Low Voltage Cable Testing and Inspection.

Leave a Comment

error: Content is Protected.