  • Instrument verified per specification sheet.
  • Direction of action correct.
  • Specific gravity setting correct.
  • Installation as piping hookup.
  • Installation as pneumatic hookup.
  • Vent provided.
  • Drain provided and piped to safe location, if required.
  • Head accessible and correct orientation.
  • Air supply:
    • Provided
    • Air set blown down
    • Set at correct pressure
    • Shutoff provided
  • Output passed through full range. Valve and/or receiver responds.
  • Pneumatic transmission lines leak checked.
  • Instrument traced. Tracing checked to standard.
  • Instrument purged. Purge checked to standard.
  • Controller checked for offset/operation.