ELECTRICAL FIELD TEST OF METERS
VISUAL AND MECHANICAL
Yes
|
No
|
|
1. Examine all devices for broken parts, indication of shipping damage and wire connection tightness.
|
||
2. Verify meter connections in accordance with single line meter and relay diagram.
|
||
3. Verify meter scale is compatible with Current Transformer, Voltage Transformer and/or transducer ratings.
|
ELECTRICAL TESTS
Yes
|
No
|
|
1. Calibrate all meters and transducers in accordance with manufacturer’s instructions.
Verify meter deflection and accuracy at 0, 1/4, 1/2, 3/4, and 100% full scale values. Provide calibration data. |
||
2. Verify all meter multipliers.
|
||
3. Verify instrument transformer secondary wiring terminal to terminal.
|