Safety Precautions for Insulation Resistance Testing [PDF]

Insulation resistance testing is a vital procedure in electrical maintenance, but it must be conducted with utmost safety in mind. Here are key safety precautions to observe when performing insulation resistance tests:

Safety Precautions for Insulation Resistance Testing

1. Safety Rules During Equipment Shutdown:

  • When taking equipment out of service, follow all safety rules and protocols.
  • Securely lock out and tag out disconnect switches to prevent accidental re-energization.
  • Test for foreign or induced voltages that might be present in the equipment.
  • Apply workmen’s grounds to ensure a safe working environment.

2. Beware of Induced Voltages:

  • When working around high-voltage equipment, be aware of the possibility of induced voltages in nearby apparatus or connected lines.
  • Instead of removing workmen’s grounds to perform a test, it’s safer to disconnect the equipment from the exposed bus or line while keeping the latter grounded.
  • Use rubber gloves when connecting test leads to equipment and operating the Megger instrument.

3. Apparatus Must Not Be Live:

  • Emphasize that the equipment under test must never be live during insulation resistance testing.
  • Refer to the preparation steps for ensuring that equipment is properly de-energized before testing.

4. Disconnect Grounds Safely:

  • When disconnecting neutral or other ground connections, ensure they are not carrying current at that moment.
  • Verify that disconnecting these connections won’t leave other equipment unprotected.

5. Attention to Connected Conductors:

  • Pay close attention to conductors leading away from the circuit being tested.
  • Ensure these conductors are properly disconnected from any voltage source to avoid unexpected energization.

6. Shock Hazard from Test Voltage:

  • Be cautious about the voltage rating of the Megger instrument and handle it accordingly.
  • Large electrical equipment and cables can store significant energy from the test current due to their capacitance.
  • Safely discharge this capacitance after testing and before handling test leads (see “Discharge of Capacitance“).

7. Explosion and Fire Hazard:

  • While using the Megger insulation tester itself does not pose a fire hazard, be aware of potential risks when testing equipment in flammable or explosive environments.
  • Slight sparking may occur during different phases of testing, such as attaching test leads, testing faulty insulation, or discharging capacitance.
  • CAUTION: Never use the instrument in an explosive atmosphere.

Safety Suggestions:

  • For minimizing risks during test lead connections and discharge:
    • Establish permanent grounding facilities and safe connection points.
    • Utilize low-voltage testing instruments or incorporate series resistances.
    • After testing, allow at least 30 to 60 seconds before disconnecting test leads to ensure proper capacitance discharge.

Adherence to these safety precautions is essential to protect personnel, equipment, and facilities during insulation resistance testing. Always prioritize safety when working with electrical systems.

Related Articles:

What is Good insulation?
What Makes Insulation Go Bad?
How Insulation Resistance is Measured.
How to Interpret Resistance Readings.
Factors Affecting Insulation Resistance Readings.
Types of Insulation Resistance Tests.
Test Voltage vs. Equipment Rating.
AC Testing vs. DC.
Use of DC Dielectric Test Set.
Tests During Drying out of Equipment.
Effect of Temperature on insulation Resistance.
Effects of humidity.
Preparation of Apparatus to test.
Connections for testing insulation resistance of electrical equipment.
Additional Notes About using A Megger Insulation Tester.
Interpretation-Minimum Values.
Minimum Values for Insulation Resistance.
Tests Using Multi-Voltage Megger Insulation Testers.
Step-Voltage Method.
Use of a Guard Terminal.
Outdoor Oil Circuit Breaker.

Leave a Comment