GENERAL METHODS OF PROTECTION OF INSTRUMENTS

GENERAL METHODS OF PROTECTION OF INSTRUMENTS

GENERAL METHODS OF PROTECTION OF INSTRUMENTS


The general methods of protection of instruments shall include but are not limited to:
(1) Insulation of the instrument including tubing and piping to prevent heat loss or gain.
(2) Tracing the instrument including tubing and piping
• All tracing of instruments shall account for Manufacturer recommendations regarding maximum temperature of operation.
• Where tracing is to be used, care shall be taken to ensure that overheating of the process fluid does not occur.
(3) Purging or flushing the instrument including tubing and piping to prevent undesirable liquids, solids or gases from entering the instrument or impacting its performance.
(4) Isolating the instrument from the process fluid through the use of a diaphragm seal.
(5) Isolating the instrument including tubing and piping from the process fluid through the use of a sealing liquid, noting the following:
• Sealing liquids shall be immiscible/ compatible with the process fluid.
• Water may be used as a sealing liquid where the only purpose is to protect against the entry of the process fluid.
• An instrument may be sealed with a liquid having a low freezing point (e.g.: dibutyl phthalate at –35°C or 50%, ethylene
glycol in water at –36 °C).
• Instruments with a low (negligible) displacement may be sealed without the use of seal pots.
Instruments with appreciable displacement require seal pots with special piping arrangements for control of the seal liquid level in order to prevent hydrostatic errors.
• Instruments that have sealed leg installations should only have legs filled by qualified personnel. Warning labels should be attached to vent/drain connections.
(6) Isolating the instrument and piping from entrained fluids by use of vapor/liquid separators.
Special consideration shall be given to protection method(s) used, where hazardous/toxic fluids are handled. Protection philosophy in these cases shall be to contain the process fluid as close to the process (e.g. piping/vessels) as possible, even when the instrument system materials do not necessarily require protection.
(8) Design and installation of systems shall be such that pockets, crevices, etc. are minimised in order to prevent undesirable build up of hazardous/toxic material.
(9) In some cases, a suitable means of flushing or purging may be required (either continuous or intermittent).

(10) Enclosing the instrument in an insulated housing (where possible equipment shall be specified for the appropriate climatic conditions).

(11) Care shall be taken to ensure temperatures at the instrument to be kept within manufacturer’s tolerances.
(12) Where necessary, personnel protection shall be applied to instrument piping.
(13) Sunshades shall be provided where levels of solar radiation could cause excessive heat within an instrument and affect
its operation or accuracy. Other methods of protection may be used.
(14) The use of NACE compliant trims for corrosive services where applicable.

Read more

Junction Box Requirements for Foundation Fieldbus

Junction Box Requirements for Foundation Fieldbus

Junction Box Requirements for Foundation Fieldbus


There are following requirements.
 All trunk and spur connections in the field junction boxes, including pass through trunk pairs without spurs, shall be terminated on wiring-blocks specifically made for FOUNDATION™ Fieldbus networks.
Each FF field junction box shall be sized according to the number of segment trunk cables and devices that are connected through it. The maximum JB size allowable including installed spares shall provide termination blocks for the connection of three segments with 12 spurs on each. There shall be 20% installed spare device capacity in each Junction Box i.e. sufficient free connection points in the termination blocks to meet this requirement.
The ‘wiring block’ shall meet the following requirements:
  • Two (2) dedicated connections for the fieldbus homerun/trunk cable.
  • Trunk connections shall be non-sparking (no arcing) i.e., Ex nA.
  • Integral short circuit protector for spur connections, maximum current to spur shall be no more than 60 mA.
  • Spur connections shall be rated nonincendive (energy limited), i.e., Ex nL and shall have ‘live disconnect’ capability (including junction boxes).
  • Pluggable (removable) ‘trunk’ and ‘spur’ connectors with retaining screws.
  • LED indicator for each spur connection indicating when a spur is shorted and is in overcurrent mode.
  • LED to indicate when bus power is available.
  • Segment wiring block shall be CENELEC (ATEX) Ex nA[L]; Class 1, Zone 2, Gas Group IIC.
  • Wire capacity: 12-24 AWG.
  • Temperature range -45 to 70 deg C.
  • DIN rail mounting.
  • Available in four (4) spur and eight (8) spur configuration.
  • A warning label must be prominently affixed on the junction box door (inside) stating the following: (red lettering with white background) “WARNING: Explosion Hazard – Do not connect or disconnect the ‘trunk connections’ on the wiring-block unless power has been switched off or the area is known to be non-hazardous.”
  • An information label must be prominently affixed on the junction box door (inside) stating the following: (black lettering with white background) “The spur connections may be connected or disconnected while the circuit is live, i.e., you may connect or disconnect the spur on the wiring-block or at the device without sniffing the area for combustible gasses.”
  • The wiring-blocks shall be mounted vertically in the field junction box.
  • The DIN rail(s) in the junction box shall be designed with enough spare length to allow the future addition of one 8-spur or larger wiring-block.
  • Junction Boxes shall contain only FF signal wiring.
  • The junction box shall be a single door IP65 box.

 

Read more

error: Content is Protected.