Electrical Commissioning of Emergency Generators [PDF]

This article is about commissioning procedure and technical specification outline the necessary protocols for the correct commissioning and ongoing maintenance of emergency generators.

This article covers a range of activities, including visual and mechanical inspections, as well as electrical and functional testing, to ensure the reliable performance of these critical backup power sources. It serves as a comprehensive guide to guarantee that emergency generators are in proper working order and ready to fulfill their essential role in times of need.

Electrical Commissioning and Start-up Checklist

Emergency Generators Nameplate Data

Date:__________

Facility:___________________ Equipment Location:______________ Project #: _________

Equipment Designation:______________________     Unit # _______   of   _______ Units

Manufacturer:_____________________     Serial number:__________________________

Model number:______________________    Type:________________________________

Equipment Rating:_____________________ Volts:________________  Amps:______________

Technician:__________________________ Test Set:_______________  Sheet #  ____ of  ____

Visual and Mechanical Inspection

The visual and mechanical inspection procedures outlined in this article are essential steps to ensure the proper installation and functioning of emergency generators:

  1. Inspect for Shipping Damage: Upon receiving the equipment, conduct a thorough inspection to identify any physical damage that may have occurred during shipping. Any such incidents should be promptly reported following the shipper’s instructions to address any potential issues.
  2. Compare Nameplate Information: Verify that the equipment’s nameplate information matches the latest single-line diagram and equipment specifications. This step ensures alignment between the physical equipment and its documented specifications.
  3. Check Fuel and Exhaust Systems: Confirm that the fuel and exhaust systems are correctly installed and positioned. Proper installation is crucial for the safe and efficient operation of the emergency generator.
  4. Torque Field Power Connections: Utilize a calibrated torque wrench method to apply the correct torque to all field power connections. If the manufacturer’s instructions do not provide torque levels, consult the table in document 4AEL-620100 to ensure proper connection tightness.
  5. Inspect Ground Terminations: Physically examine all ground terminations and connections to confirm their integrity. Adequate grounding is essential for safety and proper functioning.
  6. Exhaust System Verification: Ensure that the engine exhaust and load bank air exhaust are directed away from any flammable materials, electrical equipment, or building windows and doors. Exhaust should be directed upward to minimize potential hazards.

These visual and mechanical inspection procedures are critical in the commissioning process, helping to identify and address any issues that could impact the reliability and safety of emergency generators.

Operational and Electrical Testing

The operational and electrical testing procedures outlined in this article are crucial steps to ensure the reliable performance of emergency generators:

  1. Phase Rotation Verification: Before making the final power connection to the transfer switch, confirm the phase rotation. Correct phase rotation is essential to prevent electrical issues and ensure proper synchronization.
  2. Transfer Switch Inspection: Verify the settings and time delay configurations of the transfer switch, ensuring that it operates as intended. Refer to the manufacturer’s instruction literature for guidance on the switch’s operation.
  3. Full Load Test: Run a full load test on the generator system to assess its performance under maximum capacity conditions. Verify that the generator produces the correct frequency and voltage, as specified. This step is particularly important to ensure the generator can handle its intended load effectively.
  4. Start Circuit and Control Verification: During the full load test and in conjunction with other tasks, confirm the proper operation of the start circuit, transfer switch, and all indicating devices. This comprehensive check ensures that the generator system functions seamlessly.
  5. Battery Charger Inspection: Verify the operation of the battery charger system. Proper battery charging is critical to maintain the readiness of the generator’s starting batteries.
  6. Load Bank Connections: Ensure that the load bank connections are correctly established, and the control circuit operates as expected. Additionally, perform an insulation resistance (Megger) test to assess the insulation integrity. Check the resistance of the generator and load bank, where applicable, to validate their performance.

These operational and electrical testing procedures are essential to guarantee that the emergency generator system operates reliably and efficiently when called upon to provide backup power. By conducting thorough tests and inspections, potential issues can be identified and resolved, ensuring the system’s readiness in critical situations.