This article is about Conduits Installation For Home Run Ceiling System for Building Premises Distribution System of Telecommunication.
Conduits Installation For Home Run Ceiling System | Telecommunication
Conduits Installation For Home Run Ceiling System
- In a “Home Run” ceiling conduit system, verify that a continuous run of conduit from the work area oulet boxes to the TR is placed.
- Verify that each home run conduit can serve from one to three oulet boxes, depending on the design and conduit size.
- For conduits that serve one outlet boxes, ensure that an inside diameter of 1.9 cm. (¾ in.) or greater is required.
- For conduits that serve two outlet boxes, ensure that an inside diameter of 2.5 cm (1 in.) or greater is required.
- For conduits that serve three outlet boxes, ensure that an inside diameter of 3.2 cm (1¼ in.) or greater is required.
- If the number of cables placed per conduit is one, ensure that the maximum conduit fills of 53% is not exceeded.
- If the number of cables placed per conduit is two, ensure that the maximum conduit fills of 31% is not exceeded.
- If the number of cables placed per conduit is three or more, ensure that the maximum conduit fills of 40% is not exceeded.
- Verify that conduit runs contain no 90° condulets (also known as LB).
- Ensure that conduit bends is long, sweeping bends and shall have a minimum bending radius of 10 – 15 times the internal conduit diameter.
- Verify if a conduit run requires more than two 90° bends, a pull box between sections with 2 bends or less is provided.
- Verify that conduit runs contain no continuous sections longer than 30 m (100 ft).
- For conduit runs that total more than 30 m (100 ft) in length, ensure that pull points or pull boxes are inserted so that no segment between points/boxes exceeds the 30 m (100 ft) limit.
- Verify that conduit do not runs through areas in which flammable material may be stored or handled (Hazardous Classified Area).
- “Verify that conduit do not runs over or adjacent to:
– Boilers.
– Incinerators.
– Hot water lines.
– Steam lines.” - Bushings shall be placed on the ends of metallic conduit to protect cable sheaths from damage.
- Verify that each conduit that enters a TC is reamed or bushed and terminated as close as possible to the wall where the backboard is mounted (to minimize the cable route inside the room).
- “Ensure that all conduits are:
• Clean, dry, and unobstructed.
• Capped for protection.
• Labeled for identification and sealed to comply with firestop requirements. Equip all conduits (end to end) with a plastic or nylon pull line that has a minimum test rating of 90 kilograms (200 lbs). The end of each pull line shall be secured to avoid loosing the end section. “ - Verify that ceiling conduits and cabling are suspended from or attached to the structural ceiling or walls with hardware or other installation aids specifically designed to support their weight.
- Verify that the ceiling conduit runs have a minimum of 8 cm (3 in.) of clear vertical space from conduits, wires, and cables.
- Verify that the ceiling conduit runs and cables are not resting directly on ceiling panels, framework (T-bars), vertical supports, or other components of the suspended ceiling.
- Verify that the ceiling conduit runs is located 15 cm (6 in.) to 30 cm (12 in.) above the T-bar and have clear vertical space.
Standards Codes and References for Conduits Installation For Home Run Ceiling System
SAES-T-916, Telecommunications Building Cable Systems.
Telecom Closet / Telecom Equipment Room Size And Location
Telecommunications Infrastructure Design Process
J-STD-607-A Commercial Building Grounding (Earthing) and Bonding Requirements For Telecommunications
ANSI/TIA/EIA 568-B Commercial Building Telecommunications Cabling Standard
Telecommunications Outside Plant Systems Design SAES-T-938 Download.