Substation Transformer What it is? Working, Types, Applications, Capacity, Testing

A substation transformer is a vital component of power systems, designed for use in both large and small three-phase transmission and distribution systems. These transformers are strategically placed within substations, whether indoor or outdoor, typically on concrete bases that are carefully planned during the project’s early stages by power engineers.

Substation transformers play a pivotal role in adjusting voltage levels within power systems, ensuring that electricity can be efficiently transmitted and distributed. They are capable of stepping voltage up or down as needed, making them versatile for various applications.

Key characteristics and features of substation transformers include:

  1. Installation Location: Substation transformers are commonly situated indoors or outdoors, with their placement determined by project requirements and power engineering specifications.
  2. Cable Connections: High-voltage and low-voltage cables are connected to the substation transformer through bushings, either at the side end or the top. These connections allow current to flow into other substation equipment, such as control cabinets, for further distribution and control.
  3. Oil-Immersed: Substation transformers are typically oil-immersed and can use various types of insulating oil, including mineral oil, vegetable oil, or siliceous transformer oil. This design ensures efficient cooling and insulation.
  4. Voltage Class: Substation transformers adhere to specific voltage classes, with primary voltages typically ranging from a minimum of 2.4 kV to a maximum of 69 kV. Secondary voltages can vary from a minimum of 0.6 kV to a maximum of 35 kV, following IEEE standards.

Substation transformers serve two primary usage scenarios:

  • Utility Substation Transformers: These transformers are used by industrial power distribution companies and provide output voltage for private individual consumers. They can output both single-phase and three-phase AC current, with common voltage ratings like 120V, 240V, and 400V. Utility substations may be located in urban or rural areas, with urban substations often enclosed within protective walls.
  • Personal Substation Transformers: These transformers are used for personal consumption by end-users, such as schools, hospitals, and restaurants. They are typically connected to medium and low-voltage grids.

In certain cases, where space constraints or environmental considerations are prominent, underground substation transformers are specially designed. These underground transformers address unique requirements, taking into account factors like safety, oil selection, and quality to minimize operational risks and optimize economic benefits.

Substation transformers are crucial components within power systems, ensuring that electricity is distributed safely and efficiently to meet the needs of various consumers and industries.

Substation Transformer What it is? Working, Types, Applications, Capacity, Testing

Substation Transformer What it is?

A substation transformer is a vital component of electrical distribution systems, especially in outdoor substations. These transformers are designed to handle high power ratings, typically ranging from 750 to 5,000 kVA for single-phase devices and 750 to 25,000 kVA for three-phase devices.

One of the key functions of substation transformers is to step down high voltages to lower levels, making electricity suitable for distribution to homes and businesses. For example, they can reduce voltages from 220kV to 10kV, ensuring safe and efficient power distribution.

These large electrical devices are typically located within substations and play a crucial role in the safe and efficient distribution of electrical power to end-users. They are essential for maintaining voltage levels within acceptable ranges for various applications.

Working Principle of Substation Transformer:

A substation transformer operates on the principle of electromagnetic induction and plays a critical role in transforming electrical power from one voltage level to another. Here’s a simplified explanation of how a substation transformer works:

  1. Input AC Voltage: The primary source of power for a substation transformer comes from the alternating current (AC) input in the distribution network. This input voltage is typically at a high level.
  2. Coil Windings: Inside the substation transformer, there are two adjacent coil windings, known as the primary winding and the secondary winding. These windings are typically insulated from each other.
  3. Magnetic Field Generation: When an AC voltage is applied to the primary winding, it generates a magnetic field around it. This magnetic field is created due to the changing voltage, as AC constantly alternates between positive and negative phases.
  4. Induction: The magnetic field generated by the primary winding couples with the adjacent secondary winding. This coupling induces a voltage in the secondary winding. The induced voltage depends on the number of turns in the primary and secondary windings.
  5. Voltage Transformation: The substation transformer’s primary function is to transform the input voltage to a different level. The ratio of the number of turns in the primary winding to the number of turns in the secondary winding determines the voltage transformation ratio.
  6. Output Voltage: The voltage produced in the secondary winding is the transformed voltage that is suitable for distribution to homes, businesses, and industries. The output voltage is typically at a lower level than the input voltage, allowing for safe and efficient power distribution.
  7. Control and Monitoring: Substation transformers are often equipped with control and monitoring equipment, including circuit breakers and safety devices. These components help ensure the safe and reliable operation of the transformer and the entire transmission and distribution network.

A substation transformer works by utilizing the principles of electromagnetic induction to change the voltage level of electricity. It serves as a vital component in power systems, allowing electricity generated at high voltages to be efficiently distributed to consumers at lower, safer voltage levels. Substation transformers are customizable and integral to the reliable and safe supply of electrical power in our daily lives. Their continued development and integration into smart grids and sustainable energy systems are expected to bring new challenges and opportunities in the future.

Substation Transformers Explanation:

Substation transformers play a crucial role in the electrical grid, primarily in voltage transformation. They serve two key purposes: stepping up voltage at power generation stations for efficient long-distance transmission and stepping down voltage at distribution substations for safe delivery to homes and businesses.

There are two main types of substation transformers: oil-immersed and dry-type. Oil-immersed transformers are common and use insulating oil for both electrical insulation and cooling. Dry-type transformers, on the other hand, utilize environmentally friendly materials like epoxy resin and are suitable for indoor or oil-restricted environments.

To manage the heat generated during operation, cooling systems are employed. Oil-immersed transformers rely on the insulating oil to dissipate heat, often aided by cooling fins or radiators. Dry-type transformers use forced air cooling with fans or blowers to maintain optimal temperatures.

Some substation transformers are equipped with tap changers, allowing adjustments to the turns ratio for precise voltage control. Protective relays are also integral, monitoring parameters like current and temperature. When limits are exceeded, these relays can trip circuit breakers to safeguard the transformer.

Voltage regulation is critical in distribution transformers to maintain stable output voltage despite incoming voltage fluctuations. Substation transformers provide electrical isolation between high-voltage and low-voltage sides, enhancing safety for both personnel and equipment.

Environmental considerations come into play, particularly with oil-immersed transformers. Proper handling, maintenance, and disposal of transformer oil are essential to minimize environmental impact. Regulations often govern safe oil disposal practices.

Efficiency is a significant factor in modern substation transformer design, as it reduces energy losses during voltage conversion and distribution, thereby lowering the grid’s environmental footprint.

Regular monitoring and maintenance are essential to ensure reliability and longevity. This includes routine oil testing, insulation checks, and thermal inspections to detect issues over time.

Substation transformers are vital components of the electrical grid, responsible for voltage transformation, protection, and ensuring a stable and efficient electricity supply. Their operation involves safety, efficiency, and environmental considerations, making them crucial elements in modern power distribution and transmission networks.

Types of Substation Transformer:

Substation transformers come in various types and configurations, each designed to serve specific purposes and voltage levels. Let’s categorize them based on different criteria:

1. By Voltage Level:

  • High Voltage Substation Transformer: These transformers typically operate within the voltage range of 11 kV to 69 kV. They are commonly used for stepping down high-voltage electricity for distribution to lower voltage levels.
  • Extra High Voltage (EHV) Substation Transformer: EHV transformers operate at higher voltage levels, ranging from a minimum of 132 kV to a maximum of 440 kV. They are often used in large-scale power transmission networks.
  • Isolation Transformers: These transformers are designed to provide isolation and safety in the event of a power failure. They do not change the voltage level but are crucial for ensuring electrical safety.
  • Variable Frequency Substation Transformer: This type of transformer is less common for individual residents and is primarily used in industrial substations. It is designed to change the frequency of the electrical supply.
  • AC/DC Substation Transformer: These transformers are used to convert between AC (Alternating Current) and DC (Direct Current) power supplies. They find applications in various fields, such as electroplating and traction systems.

2. By Distribution Location:

  • Grid-Type Substations: Grid-type substations are used for transmitting high-voltage, high-capacity electricity. They are typically located outdoors and are essential for long-distance power transmission.
  • Urban and Rural Substation Transformers: These transformers are commonly found in urban and rural areas. They operate at low to medium voltage levels, typically ranging from 10 kV to 33 kV, and play a crucial role in supplying electricity to homes and businesses in these areas.

These categorizations help us understand the diverse range of substation transformers, each serving specific functions within the power distribution network. The choice of transformer type depends on the voltage requirements, distribution location, and intended applications.

Why need to understand Substation Transformers?

Substation transformers play a pivotal role in the electrical power grid by facilitating the adjustment of voltage levels, whether from high to low or vice versa. This crucial function ensures efficient transmission and distribution of electric power across various applications.

Substation transformers come in different formats to meet specific needs. These formats include oil-cooled transformers, liquid-filled transformers, and three-phase dry-type transformers, among others. The selection of a particular transformer type depends on factors such as the application’s requirements, power demands, and location constraints.

For instance, in areas where aesthetics are a priority, pad-mounted transformers are commonly used due to their unobtrusive appearance. In contrast, industrial regions with ample outdoor space may opt for ground-mounted transformers, which offer practical advantages in such environments. The choice of transformer format is guided by the unique needs and circumstances of each installation.

Why Substation Transformer installed at Power Plants?

Substation transformers are integral components of power plants, playing a critical role in the generation and distribution of electricity over extensive distances. These transformers are essential for ensuring the smooth and efficient operation of power plants.

In a power plant, the electricity generated typically starts at a lower voltage level. To enable efficient long-distance transmission, a step-up transformer is employed, which raises the voltage to the required level. This step-up process allows electricity to be transmitted across vast distances with reduced losses.

Upon reaching the receiving substation, the voltage must be stepped down to a level suitable for local distribution. Substation transformers are responsible for this voltage reduction, ensuring that the electricity can be safely and effectively distributed to homes, businesses, and industries in the vicinity. The coordinated operation of step-up and substation transformers is essential for maintaining a reliable and stable power supply from power plants to end-users.

Substation Transformer Applications:

Substation transformers offer a broad spectrum of applications and can be tailored to meet the specific power requirements of various sectors. For instance, they can provide distribution transformer solutions for papermaking enterprises or distribution transformer capacity solutions for processing factories.

Daelim, as a provider of these transformers, is dedicated to ensuring customer education and transparency in operations. They offer comprehensive explanations of 10kV transformers and their specifications, demonstrating their commitment to customer satisfaction.

Whether you are seeking transformers for sale in Canada or require a specific residential pad-mounted transformer, Daelim is your reliable partner. They specialize in delivering dependable solutions that are customized to address your unique needs.

In the upcoming sections of this article, we will explore topics such as mobile transformer substations and high-voltage distribution transformers. Stay tuned to gain insights into these exciting subjects.

Selection of Substation Transformer:

Selecting the appropriate transformer capacity is a critical decision in substation design and operation. The selection process should adhere to several key principles:

  1. Meet the Total Calculated Load: The rated capacity of the transformer should be sufficient to meet the combined electrical load of all connected equipment. This ensures that the transformer can supply power to all loads without the risk of long-term overload operation, which can lead to overheating and reduced transformer lifespan.
  2. Avoid Excessive Capacity: The transformer’s capacity should not be significantly larger than the total load. Oversized transformers can be less efficient and costlier to operate. Additionally, they may lead to higher initial capital costs.
  3. Consider Redundancy: In substations or power distribution stations with multiple transformers, it’s essential to plan for redundancy. If one transformer fails, the remaining transformers should have the capacity to cover the loads of both Class I and Class II equipment. This redundancy ensures continuity of power supply even during transformer maintenance or failure.
  4. Optimize for Flexibility: Select a transformer capacity that allows for flexibility in operation. Avoid choosing a transformer that is excessively large, as it may limit the flexibility to adjust loads as needed. Smaller transformers can provide more versatile operation and maintenance options.
  5. Operate Above 60% Load: To maintain the efficiency and reliability of the transformer, the normal load should be maintained above 60% of the rated capacity. Operating a transformer below this threshold can result in reduced efficiency and may lead to operational issues.

The selection of transformer capacity should be based on a thorough analysis of the electrical load requirements, including peak demand and future growth considerations. It should also take into account factors such as redundancy, cost-effectiveness, and operational flexibility. Collaborating with electrical engineers and experts in substation design can help ensure the optimal selection of transformer capacity for a given substation.

Capacity of Substation Transformer:

Substation transformers come in various capacities, and manufacturers have the flexibility to adjust these capacities according to specific requirements. Typically, a substation transformer is rated between 69-13 kV and has a power capacity of around 20 MVA (megavolt-amperes) or 20,000 kVA (kilovolt-amperes).

In this rating, the primary voltage is usually around 69 kV, while the secondary voltage is approximately 13 kV. The capacity of the substation transformer, which is 20 MVA, represents its ability to handle and transmit electrical power effectively within the specified voltage ranges. These transformers play a crucial role in voltage conversion and distribution within electrical substations, ensuring that power is delivered safely and efficiently to end-users.

Substation Transformer Function:

The function of a substation transformer is fundamentally to facilitate the transfer of electrical power from one voltage level to another within an electrical power system. Power generation typically occurs at high voltage levels, often above 10 kV (kilovolts), to minimize transmission losses over long distances through high-voltage transmission lines. However, these high voltages are not suitable for direct use by consumers or most industrial equipment. Therefore, substations are strategically placed along the power grid to step down the voltage to levels that are safe and appropriate for distribution to end-users.

Substation transformers play a pivotal role in this voltage transformation process. They consist of two main coils of wire, known as the primary winding and the secondary winding. The primary winding is connected to the high-voltage transmission lines, while the secondary winding is linked to the distribution lines that deliver power to homes, businesses, and industries.

The operation of a substation transformer is based on the principle of electromagnetic induction. When an alternating current (AC) flows through the primary winding, it generates a magnetic field. This magnetic field, in turn, induces a voltage in the secondary winding. The key factor that determines the extent of voltage reduction is the ratio of the number of turns in the primary winding to the number of turns in the secondary winding.

Substation transformers come in various sizes and configurations to accommodate different voltage levels and power demands across the grid. They are a critical component of electrical substations, ensuring that power is efficiently and safely distributed from high-voltage transmission lines to the end-users’ low-voltage systems. These transformers are manufactured by specialized companies with expertise in transformer design and production to meet the specific needs and standards of the power industry.

Substation Transformers Sizes:

Substation transformers are available in a wide range of sizes and specifications to cater to various power distribution needs. The specific size and specifications of a substation transformer are determined by several factors, including the required voltage level, load demand, and the type of substation. Here are some key aspects of substation transformer sizes and specifications:

  1. Power Rating (kVA): Substation transformers are categorized based on their power rating, which is measured in kilovolt-amperes (kVA). The power rating of substation transformers can vary significantly, ranging from small units with a few kVA to large transformers with several hundred megavolt-amperes (MVA). The choice of power rating depends on the electrical load that the transformer needs to serve.
  2. Physical Size: The physical dimensions of a substation transformer are influenced by factors such as the required level of insulation, voltage level, and load capacity. Larger transformers generally have larger physical sizes, as they require more insulation to handle higher voltages and loads.
  3. Cooling System: Substation transformers can be designed with different cooling systems, such as forced air cooling or liquid cooling. The choice of cooling system depends on the transformer’s power rating and the environmental conditions of the substation site.
  4. Insulation Type: Transformers can be insulated using various materials, including oil or dry-type insulation. The selection of insulation type is based on factors like safety, environmental regulations, and specific application requirements.
  5. Number of Phases: Substation transformers can be single-phase or three-phase, depending on the application. Three-phase transformers are common in industrial and utility substations due to their ability to handle balanced loads efficiently.
  6. Frequency: The frequency of the electrical system must match that of the transformer. Common frequencies include 50 Hz and 60 Hz, depending on the region and utility standards.
  7. Voltage Class: Substation transformers are available in different voltage classes to accommodate various voltage levels within the power grid. Common voltage classes include 69 kV, 115 kV, 138 kV, 230 kV, and 345 kV.

Selecting the right substation transformer size and specifications is crucial to ensure that it meets the specific requirements of the application and complies with safety and regulatory standards. Consulting with a reputable substation transformer manufacturer or engineering expert can help in making informed decisions about the appropriate transformer for a given substation project.

Testing of Substation Transformer:

Transformer testing is a critical aspect of ensuring the safety, reliability, and performance of substation transformers. Over time, the methods and scope of transformer testing have evolved to provide comprehensive insights into the transformer’s condition and functionality. Here are some common transformer tests conducted under widely accepted standards like IEC and IEEE:

IEC Standard Tests:

  1. Dielectric Test: This test assesses the insulation strength of the transformer by subjecting it to a high-voltage AC or DC voltage for a specified duration. It helps identify any weaknesses or breakdowns in the insulation system.
  2. Pulse Test: Pulse tests are performed to evaluate the transformer’s ability to withstand transient voltage surges and lightning strikes, simulating real-world conditions.
  3. Lightning Impulse Test: This test exposes the transformer to high-voltage lightning impulses to assess its capability to withstand lightning-induced stresses.
  4. Pressure Test: Pressure tests check the structural integrity of the transformer tank and its ability to withstand internal pressure changes, ensuring safety during operation.
  5. Partial Discharge Measurement: Partial discharge tests identify partial discharges within the transformer insulation, which can indicate potential insulation problems or defects.
  6. Induced AC Voltage Test: This test checks the transformer’s ability to withstand induced AC voltage that may occur during switching operations or system faults.
  7. No-Load Loss Test: This test measures the transformer’s core loss (iron loss) when operating with no load to assess its efficiency under light-load conditions.
  8. Load Loss Test: Load loss tests determine the transformer’s copper loss under load conditions, helping evaluate its overall efficiency.
  9. Temperature Rise Test: This test measures the temperature rise of the transformer’s windings and insulation under load to ensure it operates within safe temperature limits.

IEEE Standard Tests:

IEEE standards also include additional tests and guidelines for transformer testing, such as:

  • Impulse Voltage Test: Similar to the lightning impulse test, this test assesses the transformer’s ability to withstand impulse voltages.
  • Short-Circuit Test: This test evaluates the transformer’s performance under short-circuit conditions, including its ability to handle fault currents.
  • Sound Level Measurement: This measures the acoustic noise generated by the transformer during operation, helping assess its noise emissions.
  • Insulation Resistance Test: This test checks the insulation resistance of the transformer windings and insulation materials.
  • Leakage Reactance Test: It determines the leakage reactance of the transformer to assess its impedance characteristics.

Transformer testing can be both mandatory and non-mandatory, depending on industry standards, manufacturer specifications, and customer requirements. These tests are essential for ensuring the safe and reliable operation of substation transformers throughout their operational life.

Leave a Comment

error: Content is Protected.