Switchgear Breaker Function Test Checklist

Switchboard testing checklist, switchgear inspection checklist, mv switchgear testing procedure pdf, switchgear maintenance checklist, switchgear testing and commissioning procedure, electrical panel testing procedure pdf, types of switchgear testing.

Switchgear Breaker Function Test Checklist

Eaton 480V SWR Breaker Function Test Checklist

Electrical Switchgear Concept | Types | Applications | Calculations | Tests

Close breaker from Breaker Control Switch.
Breaker Closed.
Red Light operational & lens in place.
Open breaker from Breaker Control Switch.
Breaker Open.
Green Light operational & lens in place.
Counter Operational.
Breaker Position Indication Operational.
Spring Condition Indication Operational.
Digitrip display operational.
Manual ON/OFF Control Operational (On/Off switches under plastic covers on front of breaker).
Breaker connected indication = Red.
Racking Mechanism Operational – Rack out breaker.
Breaker Test indication = Yellow.
Breaker Disconnected indication = Green.
Pull breaker out of cubicle with handles and slide (do not remove from rails).
Verify label on side of breaker matches label on door of cubicle (feeder breaker no./cubicle no.).
Shutters Closed.
Manually charge spring, close breaker, open breaker.
Visually inspect control wiring plugs in the top center of the cubicle, ensure they are not broken.
Does the door open and close easily (alignment).
Rack breaker back in.
Charging Motor Operational.

Powell 4.16kV SWR Breaker Function Test Checklist

Close breaker from Breaker Control Switch.
Breaker Closed.
Red Light operational & lens in place.
Open breaker from Breaker Control Switch.
Breaker Open.
Green Light operational & lens in place.
Counter Operational.
Breaker Position Indication Operational.
Spring Condition Indication Operational.
Breaker connected indication.
Shutter open indication = Red.
Racking Mechanism Operational – Rack out breaker.
Breaker Test indication.
Breaker Disconnected indication.
Shutter Closed indication – Green.
Disconnect control cable from front of breaker and roll breaker out of cubicle.
Verify label on side of breaker matches label on door of cubicle (feeder breaker no./cubicle no.).
Shutters Closed.
Ensure rear door of cubicle will open.
Visually inspect rear door latch mechanism and ensure it is not bent/broken (lower left rail near rear of cubicle).
Does the door open and close easily (alignment).
Rack breaker back in.
Charging Motor Operational.
Ensure rear door of cubicle will not open.

Eaton 4.16kV MCC Contactor Function Test Checklist

Disconnect operates correctly (open and close) – freely, no excessive force required.
Red arc barriers are in place between the T-lead connections, fuses, & bus on top of contactors.
Shutters are closed when disconnect is open.
Door will not open when disconnect is closed.
Mechanical indicators are operational.
All components are in good condition – no damaged, loose, or missing parts.
Contactor closes properly.
Contactor opens properly.
Multilin trip contact opens contactor (if this can be tested).

METHOD STATEMENT FOR TESTING & COMMISSIONING OF SWITCHGEAR


Discover more from PAKTECHPOINT

Subscribe to get the latest posts to your email.

Leave a Comment

error: Content is Protected.