This article is about Technical specification, equipment drawing, materials, hardware required for Overhead Line Accessories, Transmission & Distribution Circuit Accessories for commercial buildings, plants and refinery projects as per international codes and standards.
Material Selection Guide & Technical Specification
Overhead circuit accessories / equipment shall be new and unused. |
Overhead circuit accessories / equipment shall be in accordance with the Saudi Aramco-approved project-specific design drawings, diagrams, schedules, lists, database, and associated design documents. |
Overhead circuit accessories / equipment shall be free from damage during transportation. |
Guy insulators shall have a rated ultimate strength greater than the rated breaking strength of the guy. |
Guy and messenger attachment hardware shall be preformed type dead end fittings or automatic guy grips. |
Messengers shall be of the stranded steel type. Messengers shall be sized for the ultimate number of cables to be installed. |
Except where specifically noted or the referenced standard drawings, minimum insulator creepage for components shall be 40 mm per KV line-to-line nominal system voltage. |
Post and suspension type insulators shall be used. Pin type insulators shall not be used. Insulator brackets shall be metallic Semi conducting or resistive glaze insulators shall not be used. |
Insulators used on overhead distribution systems shall meet the requirements of the ANSI C29 series of standards. |
Fog type porcelain suspension insulators shall be used to terminate overhead circuits at a substation bay or supporting strain bus. |
Overhead circuit accessories / equipment including terminating devices, shall be rated for application at line-to-line system voltages. |
Supporting structures for accessories shall have a minimum stress safety factor of 4.0. |
Check that Load break switches are supplied for sectionalizing points. |
International Codes & Standards
SAES-P-107 Overhead Distribution Systems
Overhead Transmission & Distribution Surge Arresters Material Selection
Overhead Transmission & Distribution Cable Termination and Splicing
Galvanized Lattice Steel & Material Selection of Overhead T&D Power Structure
Overhead Transmission & Distribution Capacitor Banks Material Selection