Analog Pressure Transmitter Calibration Procedure

1-   Gauge Pressure Transmitter.

2-   Differential Pressure Transmitter. (Including DP type Level & Flow Transmitters)

3-   Vacuum Transmitter.

4-   P/I Converter (Pneumatic to Current Converter)

ProcedureGeneral Procedure for all Power Stations.
Title of JobMaintenance Check & Calibration
ManpowerInstrument Technician Using PPE (Personal Protective Equipment)
Safety DocumentMaintenance Work Permits. & SCC (Safety Clearance Certificate) If Required
Tools/        SpecialI & C Tool Kit + any special tools (if Required)Test Equipment
Tools
Test Equipment:Note: Select test equipment according to the max. Range & Medium. 1– AVO meter / mA meter       
2– Deadweight Tester, Standard Pressure          Gauge (0.5 Bar to 200 Bars)     
3–  Hydraulic  pressure  pump  and  standard  pressure gauge (0 Bar to 250 Bars). 4–  Air  pressure  pump  with  digital  multifunction calibrator used for very low and low pressure (0 to 20000mmH2O or 0to 2 Bar or 0 to 20 Bars). 5– Water manometer or mercury manometer with air pump (0 to 1500 mm H2O or 0 to 1500mmHg). 6- Vacuum pump with digital multifunction tester.(0 to -760 mmHg / 0 to -30 inches of Hg or  0 to -1 Bar)           
Stores                & MaterialsCleaning spray, brush and cloth 
 
Job Description
ProcessStepsDuring  Maintenance
Isolation & Removal1Isolate the transmitter by closing inlet valves of many fold or isolate from the main isolating valves of impulse lines.
2In case of oil or chemical process use secondary container to avoid spill of oil / chemical when isolating. Depressurize the pressure transmitter and draining tapping lines.
3Confirm that power supply is OFF. Remove the wires from the transmitter terminal by the core identification and insulate all wires terminals by insulation tape (Ensure it isn’t in contact with each other, short circuiting or producing any earth).
 4Move away the tapping lines to avoid spill of oil or chemical from transmitter connections. Disconnect the pressure transmitter or differential pressure transmitter from the process carefully.
5Carry out the Pressure transmitter / diff. pressure transmitter external cleaning, using a brush and approved cleaning spray to remove contamination or solid particles.
6Inspect the Pressure or Diff. Pressure Transmitter for external physical damage,  general appearance & fitness. (Check whether cover seals are intact).
Preparation7Write all the details of pressure or diff. pressure transmitter, tag no., range, service and unit no. in the calibration sheet.
8Collect the calibration range from MEW Engineer of each transmitter (millimeter WC till maximum range in bars) and note in the calibration sheet.
9Damping of Transmitter: Damping means a delay between change in the transmitter inputs and detection of change to the output values. Mostly it is a mechanical screw type damping adjustment on the diff. pressure transmitter. It is better to adjust the transmitter damping value at zero before performing  calibration. Note the position of damping pointer. After test re-adjust the original value of damping before installing in field.
10Set up the test equipment as shown in the diagram:

11Ensure that the medium used for calibration is same as that of medium of the process (if possible).
12Carry out purging (if required) to remove the process medium completely from the transmitter internals (pressurize, fill and then drain).
13Carry out the leak test by applying the pressure to the transmitter & check for leakages. (Pressurize at max. range and wait for at least one minute). If there is any leakage in connections, tighten. Note: 1– Always use high pressure port of Diff. pressure transmitter and keep low pressure port free in air for reference. 2- Never apply pressure more than the rated pressure; otherwise pressure sensor of transmitter will be damaged.
14Connect the power supply 24VDC to the transmitter and mA meter to read output 4~20mADC during calibration.
  Note: Multi-function calibrator can be used for both functions. As a power source and to read out 4~20mADC.
15Exercise the pressure element to stretch for full range and back to zero to make sure that element can operate normal.
Calibration16Without  applying  pressure,  check  the  output  of  transmitter  should  be 4mADC.
17Now apply 100% pressure according to range provided by MEW Engineer and note the output of transmitter. It should be 20mADC. Note: This pressure can be applied in increasing and decreasing order i.e. Ascending or descending order (e.g Increasing like: 0%, 25%, 50%, 75% & 100%) and vice versa.
18If output of the above both values are correct then check middle 3 points (at 25% input pressure, output = 8mADC, at 50% input Pressure, output =12mADC and at 75% input pressure, output=16mADC) for rising and falling values.
19In case of Vacuum transmitter.  Without creating vacuum check the output current  should  be  4.00mADC.  Now  create  the vacuum  in  the vacuum transmitter and note the other 4 points input / output values. (At 25% vacuum: output should be 8.00mADC, at 50% vacuum: output current should be 12mADC, at 75% vacuum: output should be 16mADC & at 100% vacuum: output should be 20mADC). Note: If we consider   0% vacuum at 20mADC then at 100% vacuum, current should be 4.0Madc
20Record  these  input/output  values  in  the  calibration  sheet  in  as  found column or before calibration column.
21If all reading are correct and error is in limit & below the design values then go to step 29.
22If there is difference in reading more than error then adjustment is required. Remove covers (if available) to gain access to zero adjustment and span adjustment screw.
23De-pressurize the transmitter completely to check 4.00mADC at the 0% input pressure, adjust transmitter output 4mADC by zero adjustment screw
24Apply 100%  input  pressure  to  the  transmitter  and  view  the  output  of transmitter it should be at 20mADC.  If it is less or more, then adjust the span screw to keep the current at 20mADC.
24Repeat  steps  23  and  24  till  at  0%  input  pressure,  output  should  be 4.00mADC & 100% input pressure, output should be 20mADC.
26If zero and span became correct then check the other 3 points i.e. at 25% input pressure = 8mADC, at 50% input pressure = 12mADC and at 75% input pressure = 16mADC by increasing and decreasing the pressure.
27Check repeatability by increasing and decreasing pressure and confirm all 5 points (0%, 25%, 50%, 75%, & 100%) input / output values match with standard values. Check the error is in limit and under design value.
 28Record these input & output values in calibration sheet in after calibration columns.
29The pressure transmitter or diff. pressure transmitter input / output values should be inspected by MEW Inspector and Quality Inspector for witness and record these values to sign the certificate after completion of job.
30It  is  necessary  to  adjust  head  correction  (If  any)  to  avoid  any  wrong reading.
Completion31Once the test is completed, remove the test equipment and clean the tested device.
32Install the pressure or diff. pressure transmitter back to its position and reconnect the instrument fittings, tubing without bending or damaging and ensure that connector is not cross fitted that can damage threading.
33After test, re-adjust the original value of damping before installing in field.
34Close the drain valve and open the inlet valve slowly to avoid sudden pressure entering in the transmitter sensor.
35In  case  of  water  /  oil  /  chemicals,  purge  the  air  completely from  the transmitters, tub lines / capillary tube and fill the transmitter carefully to avoid showing any wrong readings.
36Check for leakage during commissioning.
37Complete the check and calibration sheet and handover to the concerned MEW I&C Engineer for inspection and signature.

Leave a Comment

error: Content is Protected.