This article is about Electrical Standard Grounding related to topic of Ground Reference Plate Enclosure.
ELECTRICAL STANDARD GROUNDING – GROUND REFERENCE PLATE ENCLOSURE
ENCLOSURE, SCREW COVER, FIBERGLASS,
HOFFMAN # A-1287 JFG WITH
MOUNTING FOOT KIT #A-5ØMFKR
BRACKET ASSEMBLY (2 REQD)
HOFFMAN #A-8JTMA
MOUNTING STRAP (2 REQD)
HOFFMAN # A -12 JS
EQUIMENT GROUNDING CONNECTION
USE 1 HOLE COMPRESSION LUGS.
DRILL AND TAP GROUND BUS AS REQUIRED.
SEE CONTRACT DRAWINGS FOR QUANTITY
AND SIZES.
X (15Ømm) LONG
X 1/4″ (6mm) THICK
COPPER BAR STOCK
MAIN GROUND LEAD IRREVERSIBLE CONNECTION
COMPRESSION LUG BRAZED TO GROUND BAR OR
CADWELD TYPE ‘L J’ CONNECTION.
PVC CONDUIT HUB
(25mm) PVC CONDUIT
#2/Ø (7Ømm2) INSULATED (ORANGE)
GROUND CONDUCTOR TO GROUNDING
ELECTRODE SYSTEM. SEE CONTRACT
NOTES:
- INSTALLATION OF ENCLOSURE SHALL BE MADE WITH NO METAL TO METAL CONTACT WITH BUILDING STEEL OR OTHER GROUNDED SURFACE.
- PROVIDE LAMINATED PLASTIC NAMEPLATE ORANGE WITH WHITE CORE (5Ømm)X (75mm) MOUNT TO DOOR. ENGR: “GROUND REFERENCE PLATE ENCLOSURE”
DWGS.
REV.
12
DATE
7/9/95
9/10/96
9/7/01
APPD.
GR BUDMAN
DRAWN
TW BECK
CHECKED
ENGINEER
TW BECK
APPD.
DATE
9/6/01
9/7/01
9/7/01
DWG NO.
STDG315A