Integrated Automation System Controlling Points List

This article is about general and technical requirements for Controlling Points List used in Integrated Automation System or Building Automation System.

Integrated Automation System Controlling Points List

The points list below are standard ones which can be added to and edited. Edit the following points list in consultation with the client and the project team, as the associated project requirements may dictate a change in number and type of building systems and equipment installed therein. Use this section if the analytics shall be provided by the system integrations contractor or an IAS provider. Use section 230900 if the analytics shall be provided by the building automation contractor under the mechanical contractor division. Edit references to division 25 and check if those sections are provided.

  1. The following table contains building subsystem points which will be exposed in the IAS along with the corresponding point classification and whether the point will participate in fault detection diagnostics or demand response events. The points list shown below represents the minimum threshold point requirements for each building subsystem and is segmented by each respective CSI Divisions as well as associated equipment/systems. Please see Section 250500 – Common Work Results for Integrated Automation for the specific naming convention associated with the IAS.
Point Name Description Actual IAS Point Name (typ.) – SiteName_Building#._BuildingWing_Floor_Equipment BACnet Object Type (typ.) IAS Graphic FDD DR Trend

Access Control System

             
STS System Status XXXX_XXXX_XXXX_ACS#_STS Multi-state Input (13) x     x
MODE System Mode (Multi-state Signal) XXXX_XXXX_XXXX_ACS#_MODE Multi-state Input (13) x     x
ALM Alarm – General Alarm or Fault XXXX_XXXX_XXXX_ACS#_ALM Multi-state Input (13) x x
OVR_SP System Override XXXX_XXXX_XXXX_ACS#_OVR_SP Multi-state Output (14) x x
OPEN Open Individual Access XXXX_XXXX_XXXX_ACS#_OPEN Analog Input (0) x x
CLOSE Close Individual Access XXXX_XXXX_XXXX_ACS#_CLOSE Analog Input (0) x x
DETECT_OCC Pedestrian Detection at Turnstile duing Occupancy XXXX_XXXX_XXXX_PAC#_DETECT_OCC Multi-state Input (13) x x
DETECT_UNOCC Pedestrian Detection at Turnstile duing Unoccupancy XXXX_XXXX_XXXX_PAC#_DETECT_UNOCC Multi-state Input (13) x x

Existing Elevator/Escalator


Controlling Points List

       
STS System Status XXXX_XXXX_XXXX_ELV#_STS Multi-state Input (13) x x
MODE System Mode (Multi-state Signal) XXXX_XXXX_XXXX_ELV#_MODE Multi-state Input (13) x x
ALM Alarm – General Alarm or Fault XXXX_XXXX_XXXX_ELV#_ALM Multi-state Input (13) x x
OVR_SP System Override XXXX_XXXX_XXXX_ELV#_OVR_SP Multi-state Output (14) x x
MODE Mode XXXX_XXXX_XXXX_ELV#_MODE Analog Input (0) x x
AMP Amperage XXXX_XXXX_XXXX_ELV#_AMP Analog Input (0) x x x
KW Kilowatts XXXX_XXXX_XXXX_ELV#_KW Analog Input (0) x x x
KWH Kilowatt Hour XXXX_XXXX_XXXX_ELV#_KWH Analog Input (0) x x x
LOCATION Floor Location XXXX_XXXX_XXXX_ELV#_FLR Analog Input (0) x x
RUNTIME Runtime Hours XXXX_XXXX_XXXX_ELV#_HOURS Analog Input (0) x x
  Booster Pump status Same as HVAC Pump          

AHUs:

Controlling Points List

Air Handling Unit

AMP Amperage XXXX_XXXX_XXXX_AHU#_AMP Analog Input (0) x
CDT Cold Deck Temperature XXXX_XXXX_XXXX_AHU#_CDT Analog Input (0) x x
CLT Cooling (Coil) Leaving Temperature XXXX_XXXX_XXXX_AHU#_CLT Analog Input (0) x x x
CO2 (Space) Carbon-Dioxide XXXX_XXXX_XXXX_AHU#_CO2 Analog Input (0) x x x
DASP Discharge Air Static Pressure XXXX_XXXX_XXXX_AHU#_DASP Analog Input (0) x x x
DAT Discharge Air Temperature XXXX_XXXX_XXXX_AHU#_DAT Analog Input (0) x x x
EAT Exhaust Air Temperature XXXX_XXXX_XXXX_AHU#_EAT Analog Input (0) x x x
KW Kilowatts XXXX_XXXX_XXXX_AHU#_KW Analog Input (0) x
KWH Kilowatt Hour XXXX_XXXX_XXXX_AHU#_KWH Analog Input (0) x
MAT Mixed Air Temperature XXXX_XXXX_XXXX_AHU#_MAT Analog Input (0) x x x
OAF Outside Airflow XXXX_XXXX_XXXX_AHU#_OAF Analog Input (0) x x
OAENTH Outdoor Air Enthalpy XXXX_XXXX_XXXX_AHU#_OAENTH Analog Input (0) x x
OAH Outdoor Air (Relative) Humidity XXXX_XXXX_XXXX_AHU#_OAH Analog Input (0) x x
OAT Outdoor Air Temperature XXXX_XXXX_XXXX_AHU#_OAT Analog Input (0) x x x
PHT Pre-Heat Temperature XXXX_XXXX_XXXX_AHU#_PHT Analog Input (0) x x
PCWDP Process Chilled Water Differential Pressure XXXX_XXXX_XXXX_AHU#_PCWDP Analog Input (0) x x
PCWR Process Chilled Water Return Temperature XXXX_XXXX_XXXX_AHU#_PCWR Analog Input (0) x x x
PCWS Process Chilled Water Supply Temperature XXXX_XXXX_XXXX_AHU#_PCWS Analog Input (0) x x x
RARH Return Air (Relative) Humidity XXXX_XXXX_XXXX_AHU#_RARH Analog Input (0) x x x
RACO2 Return Air Carbon-Dioxide XXXX_XXXX_XXXX_AHU#_RACO2 Analog Input (0) x x x
RAF Return Airflow XXXX_XXXX_XXXX_AHU#_RAF Analog Input (0) x x
RAT Return air Temperature XXXX_XXXX_XXXX_AHU#_RAT Analog Input (0) x x x
RH (Space) Relative Humidity XXXX_XXXX_XXXX_AHU#_RH Analog Input (0) x x
RSP Remote Static Pressure XXXX_XXXX_XXXX_AHU#_RSP Analog Input (0) x x
SAF Supply Airflow XXXX_XXXX_XXXX_AHU#_SAF Analog Input (0) x x
VLT Voltage XXXX_XXXX_XXXX_AHU#_VLT Analog Input (0) x
ZNT Zone or Space Temperature XXXX_XXXX_XXXX_AHU#_ZNT Analog Input (0) x x x x
ALM Alarm – General Alarm or Fault XXXX_XXXX_XXXX_AHU#_ALM Binary Input (3) x x x
FLTR Dirty Filter Alarm (via Differential Pressure Switch) XXXX_XXXX_XXXX_AHU#_FLTR Binary Input (3) x x
FZ Freezestat XXXX_XXXX_XXXX_AHU#_FZ Binary Input (3) x x
RFST Return Fan Status XXXX_XXXX_XXXX_AHU#_RFST Binary Input (3) x x
SFST Supply Fan Status XXXX_XXXX_XXXX_AHU#_SFST Binary Input (3) x x
VIB Vibration Switch Alarm XXXX_XXXX_XXXX_AHU#_VIB Binary Input (3) x x
CLG Cooling Coil Valve (0-100 percent open control signal) XXXX_XXXX_XXXX_AHU#_CLG Analog Output (1) x x
HTG Heating Coil Valve (0-100 percent open control signal) XXXX_XXXX_XXXX_AHU#_HTG Analog Output (1) x x
HUM Humidifier Control Valve (0-100 percent open control signal) XXXX_XXXX_XXXX_AHU#_HUM Analog Output (1) x x
MAD Mixed Air Dampers (0-100 percent open control signal relative to OAD) XXXX_XXXX_XXXX_AHU#_MAD Analog Output (1) x x
OAD Outside Air Damper (0-100 percent open control signal) XXXX_XXXX_XXXX_AHU#_OAD Analog Output (1) x x
RAD Return Air Damper (0-100 percent open control signal) XXXX_XXXX_XXXX_AHU#_RAD Analog Output (1) x x
SPD Speed for Fan or Pump Variable Frequency Drive (0-100 percent control signal) XXXX_XXXX_XXXX_AHU#_SPD Analog Output (1) x x
VLV Modulating Valve (0-100 percent open control signal) XXXX_XXXX_XXXX_AHU#_VLV Analog Output (1) x x
CMD Command for Fan or Pump Start/Stop XXXX_XXXX_XXXX_AHU#_CMD Binary Output (4) x x
ENABLE Enable/Disable Command for System or Equipment Stage XXXX_XXXX_XXXX_AHU#_ENABLE Binary Output (4) x x
DAT_STPT Discharge Air Temperature Set point XXXX_XXXX_XXXX_AHU#_DAT_STPT Analog Value (2) x x x
EFF_CLG Effective Cooling Set point XXXX_XXXX_XXXX_AHU#_EFF_CLG Analog Value (2) x x x
EFF_HTG Effective Heating Set point XXXX_XXXX_XXXX_AHU#_EFF_HTG Analog Value (2) x x x
HLALM High Limit Alarm XXXX_XXXX_XXXX_AHU#_HLALM Analog Value (2) x x
HLSTPT High Limit Set point XXXX_XXXX_XXXX_AHU#_HLSTPT Analog Value (2) x x
HUM_STPT Humidity Set point XXXX_XXXX_XXXX_AHU#_HUM_STPT Analog Value (2) x x
LLALM Low Limit Alarm XXXX_XXXX_XXXX_AHU#_LLALM Analog Value (2) x x
LLSTPT Low Limit Set point XXXX_XXXX_XXXX_AHU#_LLSTPT Analog Value (2) x x
OCC Occupied Mode XXXX_XXXX_XXXX_AHU#_OCC Multi-state Value (19) x x
RAH_STPT Return Air (Relative) Humidity Set point XXXX_XXXX_XXXX_AHU#_RAH_STPT Analog Value (2) x x
STPT Set point (Zone Temperature Set point) XXXX_XXXX_XXXX_AHU#_STPT Analog Value (2) x x x x
UNOCC Unoccupied Mode XXXX_XXXX_XXXX_AHU#_UNOCC Multi-state Value (19) x x

ACs:

Air Conditioners

Controlling Points List

AMP Amperage XXXX_XXXX_XXXX_RTU#_AMP Analog Input (0) x
CDT Cold Deck Temperature XXXX_XXXX_XXXX_RTU#_CDT Analog Input (0) x x
CLT Cooling (Coil) Leaving Temperature XXXX_XXXX_XXXX_RTU#_CLT Analog Input (0) x x x
CO2 (Space) Carbon-Dioxide XXXX_XXXX_XXXX_RTU#_CO2 Analog Input (0) x x x
DASP Discharge Air Static Pressure XXXX_XXXX_XXXX_RTU#_DASP Analog Input (0) x x x
DAT Discharge Air Temperature XXXX_XXXX_XXXX_RTU#_DAT Analog Input (0) x x x
EAT Exhaust Air Temperature XXXX_XXXX_XXXX_RTU#_EAT Analog Input (0) x x x
KW Kilowatts XXXX_XXXX_XXXX_RTU#_KW Analog Input (0) x
KWH Kilowatt Hour XXXX_XXXX_XXXX_RTU#_KWH Analog Input (0) x
MAT Mixed Air Temperature XXXX_XXXX_XXXX_RTU#_MAT Analog Input (0) x x x
OAF Outside Airflow XXXX_XXXX_XXXX_RTU#_OAF Analog Input (0) x x
OAENTH Outdoor Air Enthalpy XXXX_XXXX_XXXX_RTU#_OAENTH Analog Input (0) x x
OAH Outdoor Air (Relative) Humidity XXXX_XXXX_XXXX_RTU#_OAH Analog Input (0) x x
OAT Outdoor Air Temperature XXXX_XXXX_XXXX_RTU#_OAT Analog Input (0) x x x
PHT Pre-Heat Temperature XXXX_XXXX_XXXX_RTU#_PHT Analog Input (0) x x
RARH Return Air (Relative) Humidity XXXX_XXXX_XXXX_RTU#_RARH Analog Input (0) x x
RACO2 Return Air Carbon-Dioxide XXXX_XXXX_XXXX_RTU#_RACO2 Analog Input (0) x x x
RAF Return Airflow XXXX_XXXX_XXXX_RTU#_RAF Analog Input (0) x x x
RAT Return air Temperature XXXX_XXXX_XXXX_RTU#_RAT Analog Input (0) x x x
RH (Space) Relative Humidity XXXX_XXXX_XXXX_RTU#_RH Analog Input (0) x x x
RSP Remote Static Pressure XXXX_XXXX_XXXX_RTU#_RSP Analog Input (0) x x
SAF Supply Airflow XXXX_XXXX_XXXX_RTU#_SAF Analog Input (0) x x x
VLT Voltage XXXX_XXXX_XXXX_RTU#_VLT Analog Input (0) x
ZNT Zone or Space Temperature XXXX_XXXX_XXXX_RTU#_ZNT Analog Input (0) x x x
ALM Alarm – General Alarm or Fault XXXX_XXXX_XXXX_RTU#_ALM Binary Input (3) x x
FLTR Dirty Filter Alarm (via Differential Pressure Switch) XXXX_XXXX_XXXX_RTU#_FLTR Binary Input (3) x
FZ Freezestat XXXX_XXXX_XXXX_RTU#_FZ Binary Input (3) X x
RFST Return Fan Status XXXX_XXXX_XXXX_RTU#_RFST Binary Input (3) x X x
SFST Supply Fan Status XXXX_XXXX_XXXX_RTU#_SFST Binary Input (3) x X x
VIB Vibration Switch Alarm XXXX_XXXX_XXXX_RTU#_VIB Binary Input (3) X x
CLG Cooling Coil Valve (0-100 percent open control signal) XXXX_XXXX_XXXX_RTU#_CLG Analog Output (1) x x
HTG Heating Coil Valve (0-100 percent open control signal) XXXX_XXXX_XXXX_RTU#_HTG Analog Output (1) x x
MAD Mixed Air Dampers (0-100 percent open control signal relative to OAD) XXXX_XXXX_XXXX_RTU#_MAD Analog Output (1) x x x
OAD Outside Air Damper (0-100 percent open control signal) XXXX_XXXX_XXXX_RTU#_OAD Analog Output (1) x x
RAD Return Air Damper (0-100 percent open control signal) XXXX_XXXX_XXXX_RTU#_RAD Analog Output (1) x x
SPD Speed for Fan or Pump Variable Frequency Drive (0-100 percent control signal) XXXX_XXXX_XXXX_RTU#_SPD Analog Output (1) x x
VLV Modulating Valve (0-100 percent open control signal) XXXX_XXXX_XXXX_RTU#_VLV Analog Output (1) x x
CMD Command for Fan or Pump Start/Stop XXXX_XXXX_XXXX_RTU#_CMD Binary Output (4) x x
ENABLE Enable/Disable Command for System or Equipment Stage XXXX_XXXX_XXXX_RTU#_ENABLE Binary Output (4) x x
DAT_STPT Discharge Air Temperature Set point XXXX_XXXX_XXXX_RTU#_DAT_STPT Analog Value (2) x x x
EFF_CLG Effective Cooling Set point XXXX_XXXX_XXXX_RTU#_EFF_CLG Analog Value (2) x x x
EFF_HTG Effective Heating Set point XXXX_XXXX_XXXX_RTU#_EFF_HTG Analog Value (2) x x x
HLALM High Limit Alarm XXXX_XXXX_XXXX_RTU#_HLALM Analog Value (2) x
HLSTPT High Limit Set point XXXX_XXXX_XXXX_RTU#_HLSTPT Analog Value (2) x x
HUM_STPT Humidity Set point XXXX_XXXX_XXXX_RTU#_HUM_STPT Analog Value (2) x x
LLALM Low Limit Alarm XXXX_XXXX_XXXX_RTU#_LLALM Analog Value (2) x
LLSTPT Low Limit Set point XXXX_XXXX_XXXX_RTU#_LLSTPT Analog Value (2) x x x
OCC Occupied Mode XXXX_XXXX_XXXX_RTU#_OCC Multi-state Value (19) x x
RAH_STPT Return Air (Relative) Humidity Set point XXXX_XXXX_XXXX_RTU#_RAH_STPT Analog Value (2) x x
STPT Set point (Zone Temperature Set point) XXXX_XXXX_XXXX_RTU#_STPT Analog Value (2) x X x x
UNOCC Unoccupied Mode XXXX_XXXX_XXXX_RTU#_UNOCC Multi-state Value (19) x x

FCUs:

Fan Coil Units

Controlling Points List

AMP Amperage XXXX_XXXX_XXXX_FCU#_AMP Analog Input (0) x
CLT Cooling (Coil) Leaving Temperature XXXX_XXXX_XXXX_FCU#_CLT Analog Input (0) x x
CO2 (Space) Carbon-Dioxide XXXX_XXXX_XXXX_FCU#_CO2 Analog Input (0) x x
DAT Discharge Air Temperature XXXX_XXXX_XXXX_FCU#_DAT Analog Input (0) x x x
KW Kilowatts XXXX_XXXX_XXXX_FCU#_KW Analog Input (0) x
KWH Kilowatt Hour XXXX_XXXX_XXXX_FCU#_KWH Analog Input (0) x
RH (Space) Relative Humidity XXXX_XXXX_XXXX_FCU#_RH Analog Input (0) x X x
VLT Voltage XXXX_XXXX_XXXX_FCU#_VLT Analog Input (0) x
ZNT Zone or Space Temperature XXXX_XXXX_XXXX_FCU#_ZNT Analog Input (0) x X x x
ALM Alarm – General Alarm or Fault XXXX_XXXX_XXXX_FCU#_ALM Binary Input (3) x X x
FLTR Dirty Filter Alarm (via Differential Pressure Switch) XXXX_XXXX_XXXX_FCU#_FLTR Binary Input (3) X x
SFST Supply Fan Status XXXX_XXXX_XXXX_FCU#_SFST Binary Input (3) x x
VIB Vibration Switch Alarm XXXX_XXXX_XXXX_FCU#_VIB Binary Input (3) X x
CLG Cooling Coil Valve (0-100 percent open control signal) XXXX_XXXX_XXXX_FCU#_CLG Analog Output (1) x x
HTG Heating Coil Valve (0-100 percent open control signal) XXXX_XXXX_XXXX_FCU#_HTG Analog Output (1) x x
SPD Speed for Fan or Pump Variable Frequency Drive (0-100 percent control signal) XXXX_XXXX_XXXX_FCU#_SPD Analog Output (1) x x
CMD Command for Fan or Pump Start/Stop XXXX_XXXX_XXXX_FCU#_CMD Binary Output (4) x x
ENABLE Enable/Disable Command for System or Equipment Stage XXXX_XXXX_XXXX_FCU#_ENABLE Binary Output (4) x x
DAT_STPT Discharge Air Temperature Set point XXXX_XXXX_XXXX_FCU#_DAT_STPT Analog Value (2) x x x
EFF_CLG Effective Cooling Set point XXXX_XXXX_XXXX_FCU#_EFF_CLG Analog Value (2) x x x
EFF_HTG Effective Heating Set point XXXX_XXXX_XXXX_FCU#_EFF_HTG Analog Value (2) x x x
OCC Occupied Mode XXXX_XXXX_XXXX_FCU#_OCC Multi-state Value (19) x x
STPT Set point (Zone Temperature Set point) XXXX_XXXX_XXXX_FCU#_STPT Analog Value (2) x x x
UNOCC Unoccupied Mode XXXX_XXXX_XXXX_FCU#_UNOCC Multi-state Value (19) x x

VAVs:

Controlling Points List

AMP Amperage XXXX_XXXX_XXXX_VAV#_AMP Analog Input (0) x
CO2 (Space) Carbon-Dioxide XXXX_XXXX_XXXX_VAV#_CO2 Analog Input (0) x x
KW Kilowatts XXXX_XXXX_XXXX_VAV#_KW Analog Input (0) x
KWH Kilowatt Hour XXXX_XXXX_XXXX_VAV#_KWH Analog Input (0) x
RH (Space) Relative Humidity XXXX_XXXX_XXXX_VAV#_RH Analog Input (0) x x
RSP Remote Static Pressure XXXX_XXXX_XXXX_VAV#_RSP Analog Input (0) x x
SAF Supply Airflow XXXX_XXXX_XXXX_VAV#_SAF Analog Input (0) x x
VLT Voltage XXXX_XXXX_XXXX_VAV#_VLT Analog Input (0) x
ZNT Zone or Space Temperature XXXX_XXXX_XXXX_VAV#_ZNT Analog Input (0) x X x x
ALM Alarm – General Alarm or Fault XXXX_XXXX_XXXX_VAV#_ALM Binary Input (3) x X x
HTG Heating Coil Valve (0-100 percent open control signal) XXXX_XXXX_XXXX_VAV#_HTG Analog Output (1) x X x
MAD Mixed Air Dampers (0-100 percent open control signal relative to OAD) XXXX_XXXX_XXXX_VAV#_MAD Analog Output (1) x x
OCC Occupied Mode XXXX_XXXX_XXXX_VAV#_OCC Multi-state Value (19) x x
STPT Set point (Zone Temperature Set point) XXXX_XXXX_XXXX_VAV#_STPT Analog Value (2) x X x x
UNOCC Unoccupied Mode XXXX_XXXX_XXXX_VAV#_UNOCC Multi-state Value (19) x x

FPVAVs:

Controlling Points List

AMP Amperage XXXX_XXXX_XXXX_FPVAV#_AMP Analog Input (0) x
CO2 (Space) Carbon-Dioxide XXXX_XXXX_XXXX_FPVAV#_CO2 Analog Input (0) x x
KW Kilowatts XXXX_XXXX_XXXX_FPVAV#_KW Analog Input (0) x
KWH Kilowatt Hour XXXX_XXXX_XXXX_FPVAV#_KWH Analog Input (0) x
RARH Return Air (Relative) Humidity XXXX_XXXX_XXXX_FPVAV#_RARH Analog Input (0) x x
RACO2 Return Air Carbon-Dioxide XXXX_XXXX_XXXX_FPVAV#_RACO2 Analog Input (0) x x
RAF Return Airflow XXXX_XXXX_XXXX_FPVAV#_RAF Analog Input (0) x x
RAT Return air Temperature XXXX_XXXX_XXXX_FPVAV#_RAT Analog Input (0) x x
RH (Space) Relative Humidity XXXX_XXXX_XXXX_FPVAV#_RH Analog Input (0) x x
RSP Remote Static Pressure XXXX_XXXX_XXXX_FPVAV#_RSP Analog Input (0) x x
SAF Supply Airflow XXXX_XXXX_XXXX_FPVAV#_SAF Analog Input (0) x x
VLT Voltage XXXX_XXXX_XXXX_FPVAV#_VLT Analog Input (0) x x
ZNT Zone or Space Temperature XXXX_XXXX_XXXX_FPVAV#_ZNT Analog Input (0) x X x x
ALM Alarm – General Alarm or Fault XXXX_XXXX_XXXX_FPVAV#_ALM Binary Input (3) X x
ST Status for Pump or Fan (when only fan for system) XXXX_XXXX_XXXX_FPVAV#_ST Binary Input (3) x x
HTG Heating Coil Valve (0-100 percent open control signal) XXXX_XXXX_XXXX_FPVAV#_HTG Analog Output (1) x x
MAD Mixed Air Dampers (0-100 percent open control signal relative to OAD) XXXX_XXXX_XXXX_FPVAV#_MAD Analog Output (1) x x
CMD Command for Fan or Pump Start/Stop XXXX_XXXX_XXXX_FPVAV#_CMD Binary Output (4) x x
OCC Occupied Mode XXXX_XXXX_XXXX_FPVAV#_OCC Multi-state Value (19) x x
STPT Set point (Zone Temperature Set point) XXXX_XXXX_XXXX_FPVAV#_STPT Analog Value (2) x X x x
UNOCC Unoccupied Mode XXXX_XXXX_XXXX_FPVAV#_UNOCC Multi-state Value (19) x x

DX Unit:

Controlling Points List

AMP Amperage XXXX_XXXX_XXXX_AC#_AMP Analog Input (0) x
CLT Cooling (Coil) Leaving Temperature XXXX_XXXX_XXXX_AC#_CLT Analog Input (0) x x
CO2 (Space) Carbon-Dioxide XXXX_XXXX_XXXX_AC#_CO2 Analog Input (0) x x
DAT Discharge Air Temperature XXXX_XXXX_XXXX_AC#_DAT Analog Input (0) x x
KW Kilowatts XXXX_XXXX_XXXX_AC#_KW Analog Input (0) x
KWH Kilowatt Hour XXXX_XXXX_XXXX_AC#_KWH Analog Input (0) x
MAT Mixed Air Temperature XXXX_XXXX_XXXX_AC#_MAT Analog Input (0) x x
OAF Outside Airflow XXXX_XXXX_XXXX_AC#_OAF Analog Input (0) x
OAENTH Outdoor Air Enthalpy XXXX_XXXX_XXXX_AC#_OAENTH Analog Input (0) x x
OAH Outdoor Air (Relative) Humidity XXXX_XXXX_XXXX_AC#_OAH Analog Input (0) x x
OAT Outdoor Air Temperature XXXX_XXXX_XXXX_AC#_OAT Analog Input (0) x x
RARH Return Air (Relative) Humidity XXXX_XXXX_XXXX_AC#_RARH Analog Input (0) x x
RACO2 Return Air Carbon-Dioxide XXXX_XXXX_XXXX_AC#_RACO2 Analog Input (0) x x
RAF Return Airflow XXXX_XXXX_XXXX_AC#_RAF Analog Input (0) x x
RAT Return air Temperature XXXX_XXXX_XXXX_AC#_RAT Analog Input (0) x x
RH (Space) Relative Humidity XXXX_XXXX_XXXX_AC#_RH Analog Input (0) x x
VLT Voltage XXXX_XXXX_XXXX_AC#_VLT Analog Input (0) x
ZNT Zone or Space Temperature XXXX_XXXX_XXXX_AC#_ZNT Analog Input (0) x X x x
ALM Alarm – General Alarm or Fault XXXX_XXXX_XXXX_AC#_ALM Binary Input (3) x x
FLTR Dirty Filter Alarm (via Differential Pressure Switch) XXXX_XXXX_XXXX_AC#_FLTR Binary Input (3) x
ST Status for Pump or Fan (when only fan for system) XXXX_XXXX_XXXX_AC#_ST Binary Input (3) x
CLG Cooling Coil Valve (0-100 percent open control signal) XXXX_XXXX_XXXX_AC#_CLG Analog Output (1) x x
OAD Outside Air Damper (0-100 percent open control signal) XXXX_XXXX_XXXX_AC#_OAD Analog Output (1) x x
RAD Return Air Damper (0-100 percent open control signal) XXXX_XXXX_XXXX_AC#_RAD Analog Output (1) x x
CMD Command for Fan or Pump Start/Stop XXXX_XXXX_XXXX_AC#_CMD Binary Output (4) x x
ENABLE Enable/Disable Command for System or Equipment Stage XXXX_XXXX_XXXX_AC#_ENABLE Binary Output (4) x x
EFF_CLG Effective Cooling Set point XXXX_XXXX_XXXX_AC#_EFF_CLG Analog Value (2) x x x
HLALM High Limit Alarm XXXX_XXXX_XXXX_AC#_HLALM Analog Value (2) x
HLSTPT High Limit Set point XXXX_XXXX_XXXX_AC#_HLSTPT Analog Value (2) x x
HUM_STPT Humidity Set point XXXX_XXXX_XXXX_AC#_HUM_STPT Analog Value (2) x x
LLALM Low Limit Alarm XXXX_XXXX_XXXX_AC#_LLALM Analog Value (2) x
LLSTPT Low Limit Set point XXXX_XXXX_XXXX_AC#_LLSTPT Analog Value (2) x x
OCC Occupied Mode XXXX_XXXX_XXXX_AC#_OCC Multi-state Value (19) x x
RAH_STPT Return Air (Relative) Humidity Set point XXXX_XXXX_XXXX_AC#_RAH_STPT Analog Value (2) x x
STPT Set point (Zone Temperature Set point) XXXX_XXXX_XXXX_AC#_STPT Analog Value (2) x x x
UNOCC Unoccupied Mode XXXX_XXXX_XXXX_AC#_UNOCC Multi-state Value (19) x x

Heat Pump:

Controlling Points List

AMP Amperage XXXX_XXXX_XXXX_HP#_AMP Analog Input (0) x
CLT Cooling (Coil) Leaving Temperature XXXX_XXXX_XXXX_HP#_CLT Analog Input (0) x x
CO2 (Space) Carbon-Dioxide XXXX_XXXX_XXXX_HP#_CO2 Analog Input (0) x x
DAT Discharge Air Temperature XXXX_XXXX_XXXX_HP#_DAT Analog Input (0) x x
KW Kilowatts XXXX_XXXX_XXXX_HP#_KW Analog Input (0) x
KWH Kilowatt Hour XXXX_XXXX_XXXX_HP#_KWH Analog Input (0) x
MAT Mixed Air Temperature XXXX_XXXX_XXXX_HP#_MAT Analog Input (0) x x
OAF Outside Airflow XXXX_XXXX_XXXX_HP#_OAF Analog Input (0) x
OAENTH Outdoor Air Enthalpy XXXX_XXXX_XXXX_HP#_OAENTH Analog Input (0) x x
OAH Outdoor Air (Relative) Humidity XXXX_XXXX_XXXX_HP#_OAH Analog Input (0) x x
OAT Outdoor Air Temperature XXXX_XXXX_XXXX_HP#_OAT Analog Input (0) x x
RARH Return Air (Relative) Humidity XXXX_XXXX_XXXX_HP#_RARH Analog Input (0) x x
RACO2 Return Air Carbon-Dioxide XXXX_XXXX_XXXX_HP#_RACO2 Analog Input (0) x x
RAF Return Airflow XXXX_XXXX_XXXX_HP#_RAF Analog Input (0) x x
RAT Return air Temperature XXXX_XXXX_XXXX_HP#_RAT Analog Input (0) x x
RH (Space) Relative Humidity XXXX_XXXX_XXXX_HP#_RH Analog Input (0) x x
VLT Voltage XXXX_XXXX_XXXX_HP#_VLT Analog Input (0) x
ZNT Zone or Space Temperature XXXX_XXXX_XXXX_HP#_ZNT Analog Input (0) x X x x
ALM Alarm – General Alarm or Fault XXXX_XXXX_XXXX_HP#_ALM Binary Input (3) x x
FLTR Dirty Filter Alarm (via Differential Pressure Switch) XXXX_XXXX_XXXX_HP#_FLTR Binary Input (3) x x
ST Status for Pump or Fan (when only fan for system) XXXX_XXXX_XXXX_HP#_ST Binary Input (3) x x
CLG Cooling Coil Valve (0-100 percent open control signal) XXXX_XXXX_XXXX_HP#_CLG Analog Output (1) x x
HTG Heating Coil Valve (0-100 percent open control signal) XXXX_XXXX_XXXX_HP#_HTG Analog Output (1) x x
OAD Outside Air Damper (0-100 percent open control signal) XXXX_XXXX_XXXX_HP#_OAD Analog Output (1) x x
RAD Return Air Damper (0-100 percent open control signal) XXXX_XXXX_XXXX_HP#_RAD Analog Output (1) x x
CMD Command for Fan or Pump Start/Stop XXXX_XXXX_XXXX_HP#_CMD Binary Output (4) x x
ENABLE Enable/Disable Command for System or Equipment Stage XXXX_XXXX_XXXX_HP#_ENABLE Binary Output (4) x x
EFF_CLG Effective Cooling Set point XXXX_XXXX_XXXX_HP#_EFF_CLG Analog Value (2) x x
EFF_HTG Effective Heating Set point XXXX_XXXX_XXXX_HP#_EFF_HTG Analog Value (2) x x x
HLALM High Limit Alarm XXXX_XXXX_XXXX_HP#_HLALM Analog Value (2) x
HLSTPT High Limit Set point XXXX_XXXX_XXXX_HP#_HLSTPT Analog Value (2) x x
HUM_STPT Humidity Set point XXXX_XXXX_XXXX_HP#_HUM_STPT Analog Value (2) x x
LLALM Low Limit Alarm XXXX_XXXX_XXXX_HP#_LLALM Analog Value (2) x
LLSTPT Low Limit Set point XXXX_XXXX_XXXX_HP#_LLSTPT Analog Value (2) x x
OCC Occupied Mode XXXX_XXXX_XXXX_HP#_OCC Multi-state Value (19) x x
RAH_STPT Return Air (Relative) Humidity Set point XXXX_XXXX_XXXX_HP#_RAH_STPT Analog Value (2) x x
STPT Set point (Zone Temperature Set point) XXXX_XXXX_XXXX_HP#_STPT Analog Value (2) x x x
UNOCC Unoccupied Mode XXXX_XXXX_XXXX_HP#_UNOCC Multi-state Value (19) x x

Unit Heaters:

Controlling Points List

AMP Amperage XXXX_XXXX_XXXX_UH#_AMP Analog Input (0) x
CO2 (Space) Carbon-Dioxide XXXX_XXXX_XXXX_UH#_CO2 Analog Input (0) x x
DAT Discharge Air Temperature XXXX_XXXX_XXXX_UH#_DAT Analog Input (0) x x
KW Kilowatts XXXX_XXXX_XXXX_UH#_KW Analog Input (0) x
KWH Kilowatt Hour XXXX_XXXX_XXXX_UH#_KWH Analog Input (0) x
RH (Space) Relative Humidity XXXX_XXXX_XXXX_UH#_RH Analog Input (0) x x
VLT Voltage XXXX_XXXX_XXXX_UH#_VLT Analog Input (0) x
ZNT Zone or Space Temperature XXXX_XXXX_XXXX_UH#_ZNT Analog Input (0) x X x x
ALM Alarm – General Alarm or Fault XXXX_XXXX_XXXX_UH#_ALM Binary Input (3) x x
ST Status for Pump or Fan (when only fan for system) XXXX_XXXX_XXXX_UH#_ST Binary Input (3) x x
HTG Heating Coil Valve (0-100 percent open control signal) XXXX_XXXX_XXXX_UH#_HTG Analog Output (1) x x
CMD Command for Fan or Pump Start/Stop XXXX_XXXX_XXXX_UH#_CMD Binary Output (4) x x
EFF_HTG Effective Heating Set point XXXX_XXXX_XXXX_UH#_EFF_HTG Analog Value (2) x x
HLALM High Limit Alarm XXXX_XXXX_XXXX_UH#_HLALM Analog Value (2) x
HLSTPT High Limit Set point XXXX_XXXX_XXXX_UH#_HLSTPT Analog Value (2) x x
LLALM Low Limit Alarm XXXX_XXXX_XXXX_UH#_LLALM Analog Value (2) x
LLSTPT Low Limit Set point XXXX_XXXX_XXXX_UH#_LLSTPT Analog Value (2) x x
OCC Occupied Mode XXXX_XXXX_XXXX_UH#_OCC Multi-state Value (19) x x
STPT Set point (Zone Temperature Set point) XXXX_XXXX_XXXX_UH#_STPT Analog Value (2) x X x x
UNOCC Unoccupied Mode XXXX_XXXX_XXXX_UH#_UNOCC Multi-state Value (19) x x

Exhaust Fans:

Controlling Points List

AMP Amperage XXXX_XXXX_XXXX_EF#_AMP Analog Input (0) x
CO2 (Space) Carbon-Dioxide XXXX_XXXX_XXXX_EF#_CO2 Analog Input (0) x x
EAT Exhaust Air Temperature XXXX_XXXX_XXXX_EF#_EAT Analog Input (0) x X x
KW Kilowatts XXXX_XXXX_XXXX_EF#_KW Analog Input (0) x
KWH Kilowatt Hour XXXX_XXXX_XXXX_EF#_KWH Analog Input (0) x
RH (Space) Relative Humidity XXXX_XXXX_XXXX_EF#_RH Analog Input (0) x x
VLT Voltage XXXX_XXXX_XXXX_EF#_VLT Analog Input (0) x
ZNT Zone or Space Temperature XXXX_XXXX_XXXX_EF#_ZNT Analog Input (0) x X x
ALM Alarm – General Alarm or Fault XXXX_XXXX_XXXX_EF#_ALM Binary Input (3) x x
EFST Exhaust (Relief) Fan Status XXXX_XXXX_XXXX_EF#_EFST Binary Input (3) x x
EAD Exhaust (or Relief) Air Damper (0-100 percent open control signal) XXXX_XXXX_XXXX_EF#_EAD Analog Output (1) x x
CMD Command for Fan or Pump Start/Stop XXXX_XXXX_XXXX_EF#_CMD Binary Output (4) x x
HSPD High Speed XXXX_XXXX_XXXX_EF#_HSPD Binary Output (4) x x
LSPD Low Speed XXXX_XXXX_XXXX_EF#_LSPD Binary Output (4) x x
MSPD Medium Speed XXXX_XXXX_XXXX_EF#_MSPD Binary Output (4) x x
HLALM High Limit Alarm XXXX_XXXX_XXXX_EF#_HLALM Analog Value (2) x
HLSTPT High Limit Set point XXXX_XXXX_XXXX_EF#_HLSTPT Analog Value (2) x x
LLALM Low Limit Alarm XXXX_XXXX_XXXX_EF#_LLALM Analog Value (2) x
LLSTPT Low Limit Set point XXXX_XXXX_XXXX_EF#_LLSTPT Analog Value (2) x x
STPT Set point (Zone Temperature Set point) XXXX_XXXX_XXXX_EF#_STPT Analog Value (2) x X x x

Kitchen Exhaust Fans:

Controlling Points List

AMP Amperage XXXX_XXXX_XXXX_KEF#_AMP Analog Input (0) x
CO2 (Space) Carbon-Dioxide XXXX_XXXX_XXXX_KEF#_CO2 Analog Input (0) x x
EAT Exhaust Air Temperature XXXX_XXXX_XXXX_KEF#_EAT Analog Input (0) x X x
KW Kilowatts XXXX_XXXX_XXXX_KEF#_KW Analog Input (0) x
KWH Kilowatt Hour XXXX_XXXX_XXXX_KEF#_KWH Analog Input (0) x
RH (Space) Relative Humidity XXXX_XXXX_XXXX_KEF#_RH Analog Input (0) x x
VLT Voltage XXXX_XXXX_XXXX_KEF#_VLT Analog Input (0) x
ZNT Zone or Space Temperature XXXX_XXXX_XXXX_KEF#_ZNT Analog Input (0) x X x
ALM Alarm – General Alarm or Fault XXXX_XXXX_XXXX_KEF#_ALM Binary Input (3) x x
EFST Exhaust (Relief) Fan Status XXXX_XXXX_XXXX_KEF#_EFST Binary Input (3) x x
EAD Exhaust (or Relief) Air Damper (0-100 percent open control signal) XXXX_XXXX_XXXX_KEF#_EAD Analog Output (1) x x
CMD Command for Fan or Pump Start/Stop XXXX_XXXX_XXXX_KEF#_CMD Binary Output (4) x x
HSPD High Speed XXXX_XXXX_XXXX_KEF#_HSPD Binary Output (4) x x
LSPD Low Speed XXXX_XXXX_XXXX_KEF#_LSPD Binary Output (4) x x
MSPD Medium Speed XXXX_XXXX_XXXX_KEF#_MSPD Binary Output (4) x x
HLALM High Limit Alarm XXXX_XXXX_XXXX_KEF#_HLALM Analog Value (2) x
HLSTPT High Limit Set point XXXX_XXXX_XXXX_KEF#_HLSTPT Analog Value (2) x x
LLALM Low Limit Alarm XXXX_XXXX_XXXX_KEF#_LLALM Analog Value (2) x
LLSTPT Low Limit Set point XXXX_XXXX_XXXX_KEF#_LLSTPT Analog Value (2) x x
STPT Set point (Zone Temperature Set point) XXXX_XXXX_XXXX_KEF#_STPT Analog Value (2) x X x
DMPR_POS Hood Damper Position XXXX_XXXX_XXXX_KEF#_DMPR_POS Analog Input (0) x X x
SUP_PRESS Suppression System Pressure XXXX_XXXX_XXXX_KEF#_SUP_PRESS Analog Input (0) x X x

Make-up Air Units:

Controlling Points List

AMP Amperage XXXX_XXXX_XXXX_MAU#_AMP Analog Input (0) x
EAT Exhaust Air Temperature XXXX_XXXX_XXXX_MAU#_EAT Analog Input (0) x x
KW Kilowatts XXXX_XXXX_XXXX_MAU#_KW Analog Input (0) x
KWH Kilowatt Hour XXXX_XXXX_XXXX_MAU#_KWH Analog Input (0) x
MAT Mixed Air Temperature XXXX_XXXX_XXXX_MAU#_MAT Analog Input (0) x X x
OAF Outside Airflow XXXX_XXXX_XXXX_MAU#_OAF Analog Input (0) x
OAENTH Outdoor Air Enthalpy XXXX_XXXX_XXXX_MAU#_OAENTH Analog Input (0) x x
OAH Outdoor Air (Relative) Humidity XXXX_XXXX_XXXX_MAU#_OAH Analog Input (0) x x
OAT Outdoor Air Temperature XXXX_XXXX_XXXX_MAU#_OAT Analog Input (0) x x
PHT Pre-Heat Temperature XXXX_XXXX_XXXX_MAU#_PHT Analog Input (0) x x
RARH Return Air (Relative) Humidity XXXX_XXXX_XXXX_MAU#_RARH Analog Input (0) x x
RACO2 Return Air Carbon-Dioxide XXXX_XXXX_XXXX_MAU#_RACO2 Analog Input (0) x x
RAT Return air Temperature XXXX_XXXX_XXXX_MAU#_RAT Analog Input (0) x x
RH (Space) Relative Humidity XXXX_XXXX_XXXX_MAU#_RH Analog Input (0) x x
VLT Voltage XXXX_XXXX_XXXX_MAU#_VLT Analog Input (0) x
ZNT Zone or Space Temperature XXXX_XXXX_XXXX_MAU#_ZNT Analog Input (0) x x
ALM Alarm – General Alarm or Fault XXXX_XXXX_XXXX_MAU#_ALM Binary Input (3) x X x
FLTR Dirty Filter Alarm (via Differential Pressure Switch) XXXX_XXXX_XXXX_MAU#_FLTR Binary Input (3) X x
FZ Freezestat XXXX_XXXX_XXXX_MAU#_FZ Binary Input (3) X x
ST Status for Pump or Fan (when only fan for system) XXXX_XXXX_XXXX_MAU#_ST Binary Input (3) x x
VIB Vibration Switch Alarm XXXX_XXXX_XXXX_MAU#_VIB Binary Input (3) X x
HTG Heating Coil Valve (0-100 percent open control signal) XXXX_XXXX_XXXX_MAU#_HTG Analog Output (1) x x
MAD Mixed Air Dampers (0-100 percent open control signal relative to OAD) XXXX_XXXX_XXXX_MAU#_MAD Analog Output (1) x x
OAD Outside Air Damper (0-100 percent open control signal) XXXX_XXXX_XXXX_MAU#_OAD Analog Output (1) x x
RAD Return Air Damper (0-100 percent open control signal) XXXX_XXXX_XXXX_MAU#_RAD Analog Output (1) x x
SPD Speed for Fan or Pump Variable Frequency Drive (0-100 percent control signal) XXXX_XXXX_XXXX_MAU#_SPD Analog Output (1) x x
VLV Modulating Valve (0-100 percent open control signal) XXXX_XXXX_XXXX_MAU#_VLV Analog Output (1) x x
CMD Command for Fan or Pump Start/Stop XXXX_XXXX_XXXX_MAU#_CMD Binary Output (4) x x
ENABLE Enable/Disable Command for System or Equipment Stage XXXX_XXXX_XXXX_MAU#_ENABLE Binary Output (4) x x
HLALM High Limit Alarm XXXX_XXXX_XXXX_MAU#_HLALM Analog Value (2) X x
HLSTPT High Limit Set point XXXX_XXXX_XXXX_MAU#_HLSTPT Analog Value (2) x x
HUM_STPT Humidity Set point XXXX_XXXX_XXXX_MAU#_HUM_STPT Analog Value (2) x x
LLALM Low Limit Alarm XXXX_XXXX_XXXX_MAU#_LLALM Analog Value (2) X x
LLSTPT Low Limit Set point XXXX_XXXX_XXXX_MAU#_LLSTPT Analog Value (2) x x
RAH_STPT Return Air (Relative) Humidity Set point XXXX_XXXX_XXXX_MAU#_RAH_STPT Analog Value (2) x x x

Chillers:

Controlling Points List

AMP Amperage XXXX_XXXX_XXXX_CH#_AMP Analog Input (0) x
CHWDP Chilled Water Differential Pressure XXXX_XXXX_XXXX_CH#_CHWDP Analog Input (0) x X x
CHWR Chilled Water Return Temperature XXXX_XXXX_XXXX_CH#_CHWR Analog Input (0) x X x
CHWS Chilled Water Supply Temperature XXXX_XXXX_XXXX_CH#_CHWS Analog Input (0) x X x
CWR Condenser Water Return XXXX_XXXX_XXXX_CH#_CWR Analog Input (0) x X x
CWS Condenser Water Supply XXXX_XXXX_XXXX_CH#_CWS Analog Input (0) x X x
KW Kilowatts XXXX_XXXX_XXXX_CH#_KW Analog Input (0) x
KWH Kilowatt Hour XXXX_XXXX_XXXX_CH#_KWH Analog Input (0) x
OAENTH Outdoor Air Enthalpy XXXX_XXXX_XXXX_CH#_OAENTH Analog Input (0) x x
OAH Outdoor Air (Relative) Humidity XXXX_XXXX_XXXX_CH#_OAH Analog Input (0) x x
OAT Outdoor Air Temperature XXXX_XXXX_XXXX_CH#_OAT Analog Input (0) x x
PRESS Pressure XXXX_XXXX_XXXX_CH#_PRESS Analog Input (0) x x
PCWDP Process Chilled Water Differential Pressure XXXX_XXXX_XXXX_CH#_PCWDP Analog Input (0) x X x
PCWR Process Chilled Water Return Temperature XXXX_XXXX_XXXX_CH#_PCWR Analog Input (0) x X x
PCWS Process Chilled Water Supply Temperature XXXX_XXXX_XXXX_CH#_PCWS Analog Input (0) x X x
VLT Voltage XXXX_XXXX_XXXX_CH#_VLT Analog Input (0) x
ALM Alarm – General Alarm or Fault XXXX_XXXX_XXXX_CH#_ALM Binary Input (3) x x
CWR Condenser Water Return XXXX_XXXX_XXXX_CH#_CWR Binary Input (3) x X x
VIB Vibration Switch Alarm XXXX_XXXX_XXXX_CH#_VIB Binary Input (3) x
SPD Speed for Fan or Pump Variable Frequency Drive (0-100 percent control signal) XXXX_XXXX_XXXX_CH#_SPD Analog Output (1) x x
VLV Modulating Valve (0-100 percent open control signal) XXXX_XXXX_XXXX_CH#_VLV Analog Output (1) x x
CMD Command for Fan or Pump Start/Stop XXXX_XXXX_XXXX_CH#_CMD Binary Output (4) x x
ENABLE Enable/Disable Command for System or Equipment Stage XXXX_XXXX_XXXX_CH#_ENABLE Binary Output (4) x X x
ISOL Isolation Valve(s) for entire system XXXX_XXXX_XXXX_CH#_ISOL Binary Output (4) x X x
HISOL Humidifier Isolation Valve XXXX_XXXX_XXXX_CH#_HISOL Binary Output (4) x X x
RISOL Return Isolation Valve XXXX_XXXX_XXXX_CH#_RISOL Binary Output (4) x X x
SISOL Supply Isolation Valve XXXX_XXXX_XXXX_CH#_SISOL Binary Output (4) x X x
CHWS_STPT Chilled Water Supply Temperature Set point XXXX_XXXX_XXXX_CH#_CHWS_STPT Analog Value (2) x X x x
HLALM High Limit Alarm XXXX_XXXX_XXXX_CH#_HLALM Analog Value (2) x
HLSTPT High Limit Set point XXXX_XXXX_XXXX_CH#_HLSTPT Analog Value (2) x x
LLALM Low Limit Alarm XXXX_XXXX_XXXX_CH#_LLALM Analog Value (2) x
LLSTPT Low Limit Set point XXXX_XXXX_XXXX_CH#_LLSTPT Analog Value (2) x x

Cooling Towers:

Controlling Points List

AMP Amperage XXXX_XXXX_XXXX_CT#_AMP Analog Input (0) x
CWR Condenser Water Return XXXX_XXXX_XXXX_CT#_CWR Analog Input (0) x X x
CWS Condenser Water Supply XXXX_XXXX_XXXX_CT#_CWS Analog Input (0) x X x
KW Kilowatts XXXX_XXXX_XXXX_CT#_KW Analog Input (0) x
KWH Kilowatt Hour XXXX_XXXX_XXXX_CT#_KWH Analog Input (0) x
OAENTH Outdoor Air Enthalpy XXXX_XXXX_XXXX_CT#_OAENTH Analog Input (0) x x
OAH Outdoor Air (Relative) Humidity XXXX_XXXX_XXXX_CT#_OAH Analog Input (0) x x
OAT Outdoor Air Temperature XXXX_XXXX_XXXX_CT#_OAT Analog Input (0) x x
PRESS Pressure XXXX_XXXX_XXXX_CT#_PRESS Analog Input (0) x x
VLT Voltage XXXX_XXXX_XXXX_CT#_VLT Analog Input (0) x
ALM Alarm – General Alarm or Fault XXXX_XXXX_XXXX_CT#_ALM Binary Input (3) x x
CWS_SP Condenser Water Supply Set point XXXX_XXXX_XXXX_CT#_CWS_SP Analog Output (1) x X x x
VIB Vibration Switch Alarm XXXX_XXXX_XXXX_CT#_VIB Binary Input (3) x
SPD Speed for Fan or Pump Variable Frequency Drive (0-100 percent control signal) XXXX_XXXX_XXXX_CT#_SPD Analog Output (1) x X x
VLV Modulating Valve (0-100 percent open control signal) XXXX_XXXX_XXXX_CT#_VLV Analog Output (1) x x
CMD Command for Fan or Pump Start/Stop XXXX_XXXX_XXXX_CT#_CMD Binary Output (4) x X x
ENABLE Enable/Disable Command for System or Equipment Stage XXXX_XXXX_XXXX_CT#_ENABLE Binary Output (4) x x
ISOL Isolation Valve(s) for entire system XXXX_XXXX_XXXX_CT#_ISOL Binary Output (4) x x
HISOL Humidifier Isolation Valve XXXX_XXXX_XXXX_CT#_HISOL Binary Output (4) x x
RISOL Return Isolation Valve XXXX_XXXX_XXXX_CT#_RISOL Binary Output (4) x X x
SISOL Supply Isolation Valve XXXX_XXXX_XXXX_CT#_SISOL Binary Output (4) x x x
HLALM High Limit Alarm XXXX_XXXX_XXXX_CT#_HLALM Analog Value (2) x
HLSTPT High Limit Set point XXXX_XXXX_XXXX_CT#_HLSTPT Analog Value (2) x x
LLALM Low Limit Alarm XXXX_XXXX_XXXX_CT#_LLALM Analog Value (2) x
LLSTPT Low Limit Set point XXXX_XXXX_XXXX_CT#_LLSTPT Analog Value (2) x x

Heat Exchangers:

Controlling Points List

AMP Amperage XXXX_XXXX_XXXX_HX#_AMP Analog Input (0) x
CHWR Chilled Water Return Temperature XXXX_XXXX_XXXX_HX#_CHWR Analog Input (0) x X x
CHWS Chilled Water Supply Temperature XXXX_XXXX_XXXX_HX#_CHWS Analog Input (0) x X x
CWR Condenser Water Return XXXX_XXXX_XXXX_HX#_CWR Analog Input (0) x X x
CWS Condenser Water Supply XXXX_XXXX_XXXX_HX#_CWS Analog Input (0) x X x
KW Kilowatts XXXX_XXXX_XXXX_HX#_KW Analog Input (0) x
KWH Kilowatt Hour XXXX_XXXX_XXXX_HX#_KWH Analog Input (0) x
OAENTH Outdoor Air Enthalpy XXXX_XXXX_XXXX_HX#_OAENTH Analog Input (0) x x
OAH Outdoor Air (Relative) Humidity XXXX_XXXX_XXXX_HX#_OAH Analog Input (0) x x
OAT Outdoor Air Temperature XXXX_XXXX_XXXX_HX#_OAT Analog Input (0) x x
PRESS Pressure XXXX_XXXX_XXXX_HX#_PRESS Analog Input (0) x x
PCWR Process Chilled Water Return Temperature XXXX_XXXX_XXXX_HX#_PCWR Analog Input (0) x X x
PCWS Process Chilled Water Supply Temperature XXXX_XXXX_XXXX_HX#_PCWS Analog Input (0) x X x
VLT Voltage XXXX_XXXX_XXXX_HX#_VLT Analog Input (0) x
ALM Alarm – General Alarm or Fault XXXX_XXXX_XXXX_HX#_ALM Binary Input (3) x x
VIB Vibration Switch Alarm XXXX_XXXX_XXXX_HX#_VIB Binary Input (3) x
SPD Speed for Fan or Pump Variable Frequency Drive (0-100 percent control signal) XXXX_XXXX_XXXX_HX#_SPD Analog Output (1) x X x
VLV Modulating Valve (0-100 percent open control signal) XXXX_XXXX_XXXX_HX#_VLV Analog Output (1) x X x x
CMD Command for Fan or Pump Start/Stop XXXX_XXXX_XXXX_HX#_CMD Binary Output (4) x x
ENABLE Enable/Disable Command for System or Equipment Stage XXXX_XXXX_XXXX_HX#_ENABLE Binary Output (4) x x
ISOL Isolation Valve(s) for entire system XXXX_XXXX_XXXX_HX#_ISOL Binary Output (4) x X x
RISOL Return Isolation Valve XXXX_XXXX_XXXX_HX#_RISOL Binary Output (4) x X x
SISOL Supply Isolation Valve XXXX_XXXX_XXXX_HX#_SISOL Binary Output (4) x X x
HLALM High Limit Alarm XXXX_XXXX_XXXX_HX#_HLALM Analog Value (2) x
HLSTPT High Limit Set point XXXX_XXXX_XXXX_HX#_HLSTPT Analog Value (2) x x
LLALM Low Limit Alarm XXXX_XXXX_XXXX_HX#_LLALM Analog Value (2) x
LLSTPT Low Limit Set point XXXX_XXXX_XXXX_HX#_LLSTPT Analog Value (2) x x

Pumps:

Controlling Points List

AMP Amperage XXXX_XXXX_XXXX_P#_AMP Analog Input (0) x
CHWDP Chilled Water Differential Pressure XXXX_XXXX_XXXX_P#_CHWDP Analog Input (0) x X x
CHWR Chilled Water Return Temperature XXXX_XXXX_XXXX_P#_CHWR Analog Input (0) x X x
CHWS Chilled Water Supply Temperature XXXX_XXXX_XXXX_P#_CHWS Analog Input (0) x X x
CWR Condenser Water Return XXXX_XXXX_XXXX_P#_CWR Analog Input (0) x X x
CWS Condenser Water Supply XXXX_XXXX_XXXX_P#_CWS Analog Input (0) x X x
HWHDP Hot Water Heating Differential Pressure XXXX_XXXX_XXXX_P#_HWHDP Analog Input (0) x x
HWHR Hot Water Heating Return Temperature XXXX_XXXX_XXXX_P#_HWHR Analog Input (0) x x
HWHS Hot Water Heating Supply Temperature XXXX_XXXX_XXXX_P#_HWHS Analog Input (0) x x
KW Kilowatts XXXX_XXXX_XXXX_P#_KW Analog Input (0) x
KWH Kilowatt Hour XXXX_XXXX_XXXX_P#_KWH Analog Input (0) x
PRESS Pressure XXXX_XXXX_XXXX_P#_PRESS Analog Input (0) x x
PCWDP Process Chilled Water Differential Pressure XXXX_XXXX_XXXX_P#_PCWDP Analog Input (0) x X x
PCWR Process Chilled Water Return Temperature XXXX_XXXX_XXXX_P#_PCWR Analog Input (0) x X x
PCWS Process Chilled Water Supply Temperature XXXX_XXXX_XXXX_P#_PCWS Analog Input (0) x X x
VLT Voltage XXXX_XXXX_XXXX_P#_VLT Analog Input (0) x x
ALM Alarm – General Alarm or Fault XXXX_XXXX_XXXX_P#_ALM Binary Input (3) x x
ST Status for Pump or Fan (when only fan for system) XXXX_XXXX_XXXX_P#_ST Binary Input (3) x X x
SPD Speed for Fan or Pump Variable Frequency Drive (0-100 percent control signal) XXXX_XXXX_XXXX_P#_SPD Analog Output (1) x X x x
CMD Command for Fan or Pump Start/Stop XXXX_XXXX_XXXX_P#_CMD Binary Output (4) x X x x
ENABLE Enable/Disable Command for System or Equipment Stage XXXX_XXXX_XXXX_P#_ENABLE Binary Output (4) x x

Meters:

Controlling Points List

AMP Amperage XXXX_XXXX_XXXX_M#_AMP Analog Input (0) x X x
KW Kilowatts XXXX_XXXX_XXXX_M#_KW Analog Input (0) x X x
KWH Kilowatt Hour XXXX_XXXX_XXXX_M#_KWH Analog Input (0) x x x
ALM Alarm – General Alarm or Fault XXXX_XXXX_XXXX_M#_ALM Binary Input (3) x X x
VLT Voltage XXXX_XXXX_XXXX_M#_VLT Analog Input (0) x X x
HTZ Hertz (Frequency) XXXX_XXXX_XXXX_M#_HTZ Analog Input (0) x x
PF Power Factor XXXX_XXXX_XXXX_M#_PF Analog Input (0) x x x

Lighting Control System:

Controlling Points List

KW Kilowatts XXXX_XXXX_XXXX_LCS#_KW Analog Input (0) x
KWH Kilowatt Hour XXXX_XXXX_XXXX_LCS#_KWH Analog Input (0) x
ALM Alarm – General Alarm or Fault XXXX_XXXX_XXXX_LCS#_ALM Multi-state Input (13) x x x
ENABLE Enable/Disable Command for System or Equipment Stage XXXX_XXXX_XXXX_LCS#_ENABLE Binary Output (4) x x
STS_LAMP Lamp Status XXXX_XXXX_XXXX_LCS#_STS_LAMP Analog Input (0) x x x
STS_BAL Ballast Status XXXX_XXXX_XXXX_LCS#_STS_BAL Analog Input (0) x x x
STS_LIGHT Status of Lighting Level XXXX_XXXX_XXXX_LCS#_STS_LIGHT Analog Input (0) x x x
STS_GROUP Status of Lighting Groups XXXX_XXXX_XXXX_LCS#_STS_GROUP Binary Input (3) x x x
STS_GROUP_LAMP Status of Lighting Groups Lamps XXXX_XXXX_XXXX_LCS#_STS_GROUP_LAMP Analog Input (0) x x
STS_GROUP_BAL Status of Lighting Groups Ballasts XXXX_XXXX_XXXX_LCS#_STS_GROUP_BAL Analog Input (0) x x
STS_OCC_SEN Status of Occupancy Sensor XXXX_XXXX_XXXX_LCS#_STS_OCC_SEN Binary Input (3) x x
STS_DAY_SEN Status of Daylight Sensor XXXX_XXXX_XXXX_LCS#_STS_DAY_SEN Analog Input (0) x x
SP_LIGHT Light Level Set point XXXX_XXXX_XXXX_LCS#_SP_LIGHT Analog Output (1) x x x
SP_GROUP_LIGHT Group Light Level Set point XXXX_XXXX_XXXX_LCS#_SP_GROUP_LIGHT Analog Output (1) x x x
SP_LIGHT_TIME Lighting Level Duration Set point XXXX_XXXX_XXXX_LCS#_SP_LIGHT_TIME Analog Output (1) x x x
SP_SCENE Lighting Scene Set point XXXX_XXXX_XXXX_LCS#_SP_SCENE Multi-state Output (14) x x x
STS_SCENE Lighting Scene Status XXXX_XXXX_XXXX_LCS#_STS_SCENE Multi-state Input (13) x x
SP_SCENE_LIGHT Lighting Level Scene Set point XXXX_XXXX_XXXX_LCS#_SP_SCENE_LIGHT Analog Output (1) x x x
SP_SCENE_LIGHT_TIME Lighting Level Scene Duration Set point XXXX_XXXX_XXXX_LCS#_SP_SCENE_LIGHT_TIME Analog Output (1) x x x
OVR_SP_GROUP_LIGHT Override Group Light Level Set point XXXX_XXXX_XXXX_LCS#_OVR_SP_GROUP_LIGHT Analog Output (1) x x
OVR_LIGHT Override Light Level Set point XXXX_XXXX_XXXX_LCS#_OVR_LIGHT Analog Output (1) x x
PRIOR_OVR_GROUP Set point of Priority Override Command for Group of Lights XXXX_XXXX_XXXX_LCS#_PRIOR_OVR_GROUP Analog Output (1) x x

Emergency Generator:

Controlling Points List

AMP Amperage XXXX_XXXX_XXXX_GEN#_AMP Analog Input (0) x x
KW Kilowatts XXXX_XXXX_XXXX_GEN#_KW Analog Input (0) x x
KWH Kilowatt Hour XXXX_XXXX_XXXX_GEN#_KWH Analog Input (0) x x
VLT Voltage XXXX_XXXX_XXXX_GEN#_VLT Analog Input (0) x x
HTZ Hertz (Frequency) XXXX_XXXX_XXXX_GEN#_HTZ Analog Input (0) x x
PF Power Factor XXXX_XXXX_XXXX_GEN#_PF Analog Input (0) x x
LVL Fuel Tank Level XXXX_XXXX_XXXX_GEN#_LVL Analog Input (0) x x x
ALM Alarm – General Alarm or Fault XXXX_XXXX_XXXX_GEN#_ALM Binary Input (3) x x
ENABLE Enable/Disable Command for System or Equipment Stage XXXX_XXXX_XXXX_GEN#_ENABLE Binary Output (4) x x x
STARTS Number of Operational Starts XXXX_XXXX_XXXX_GEN#_STARTS Analog Input (0) x x
RUNTIME Number of Total Operating Hours XXXX_XXXX_XXXX_GEN#_RUNTIME Analog Input (0) x x x
TEMP_OIL Temperature of Oil XXXX_XXXX_XXXX_GEN#_TEMP_OIL Analog Input (0) x x
TEMP_RAD Temperature of Radiator XXXX_XXXX_XXXX_GEN#_TEMP_RAD Analog Input (0) x x
STS_LOAD Percent of Full Load Power Production XXXX_XXXX_XXXX_GEN#_STS_LOAD Analog Input (0) x x x

Electric Panels/Plug Load Control

Controlling Points List

AMP Amperage XXXX_XXXX_XXXX_EP#_AMP Analog Input (0) x x
KW Kilowatts XXXX_XXXX_XXXX_EP#_KW Analog Input (0) x x
KWH Kilowatt Hour XXXX_XXXX_XXXX_EP#_KWH Analog Input (0) x x
ALM Alarm – General Alarm or Fault XXXX_XXXX_XXXX_EP#_ALM Binary Input (3) x x
ENABLE Enable/Disable Command for System or Equipment Stage XXXX_XXXX_XXXX_EP#_ENABLE Binary Output (4) x x
VLT Voltage XXXX_XXXX_XXXX_EP#_VLT Analog Input (0) x x
STS_OUTLET Status of Recepticle Outlet XXXX_XXXX_XXXX_EP#_STS_OUTLET Analog Input (0) x x x
SP_OUTLET Set point of Recepticle Outlet XXXX_XXXX_XXXX_EP#_SP_OUTLET Analog Output (1) x x x

Fire Alarm Systems:

Controlling Points List

STS System Status XXXX_XXXX_XXXX_FAS_STS Multi-state Input (13) x x
ZONE_STS Adressable Zone Status XXXX_XXXX_XXXX_ FAS _ZONE_STS Multi-state Input (13) x x
ALM Alarm – General Alarm or Fault XXXX_XXXX_XXXX_ FAS _ALM Multi-state Input (13) x x x
PRESS System Pressure XXXX_XXXX_XXXX_ FAS _PRESS Analog Input (0) x x x


Discover more from PAKTECHPOINT

Subscribe to get the latest posts to your email.

Leave a Comment

error: Content is Protected.