SMART Pressure & Diff. Pressure Transmitter Digital Calibration Procedure

1-   SMART Gauge Pressure Transmitter.

2-   SMART Differential Pressure Transmitter. (Including DP type Level & Flow Transmitters)

3-   SMART Vacuum Transmitter.

ProcedureGeneral Procedure for all Power Stations.
Title of JobMaintenance Check & Calibration
ManpowerInstrument Technician Using PPE (Personal Protective Equipment)
Safety DocumentMaintenance Work Permits. & SCC (Safety Clearance Certificate) If Required
Tools/      SpecialI &C Tool Kit & special tools (if Required)Test Equipment
Tools
Test Equipment:Note:  Select  test  equipment  according  to  the max. Range & Medium. 1– Digital multi-meter / mA meter / SMART HART Calibrator           
2– Deadweight Tester, Standard Pressure        Gauge (0.5 Bar to 200 Bars)     
3– Hydraulic pressure pump and standard pressure gauge (0 Bar to 250 Bars). 4–  Air  pressure  pump  with  digital  multifunction calibrator used for very low and low pressure (0 to 20000mmH2O or 0to 2 Bar or 0 to 20 Bars). 5– Water manometer or mercury manometer with air pump (0 to 1500 mm H2O or 0 to 1500mmHg). 
6-   Vacuum   pump   with   digital   multifunction 
tester.(0 to -760 mmHg / 0 to -30 inches Hg or  0 to -1 Bar) 
Stores                 &Cleaning spray, brush and cloth 
Materials 
Job Description
ProcessStepsDuring  Maintenance
Isolation & Removal1Isolate the transmitter by closing inlet valve of many fold or isolate from the main isolating valves of impulse lines.
2In case of oil or chemical process use secondary container to avoid spill of oil / chemical when isolating. Depressurize the transmitter and draining tapping lines.
 3Confirm that power supply is OFF. Remove the wires from the transmitter terminal  by the core identification  and  insulate all  wires  terminals  by insulation tape (Ensure it isn’t in contact with each other, short circuiting or producing any earth).
4Move away the tapping lines to avoid spill of oil or chemical from transmitter connections. Disconnect the SMART pressure transmitter or differential pressure transmitter form the process carefully.
5Carry out the Pressure transmitter / diff. pressure transmitter external cleaning, using a brush and approved Cleaning spray to remove contamination or solid particles.
6Inspect the Pressure or Diff. Pressure Transmitter for external physical damage, general appearance & fitness. (Check whether cover seals are intact).
Preparation7Write all the details of pressure transmitter: tag no., range, service and unit no. in the calibration sheet.
8Damping of Transmitter: Many hart transmitter supports a function Damping.  Damping  means  a  delay  between  change  in  the  transmitter inputs and detection of change in digital value for transmitter input reading and corresponding to the output values. It is better to adjust the transmitter damping  value  at  zero before performing test.  After test  re-adjust  the original value of damping before installing in field.
9Collect the configurations values & calibration range from Engineer of each transmitter (millimeter WC till maximum range in bars) and note in the calibration sheet.
10Set up the test equipment as shown in the diagram:
11Ensure that the medium used for calibration is same as that of medium of the process (If possible) in witch transmitter is installed.
12Carry out purging (if required) to remove the process medium completely from the transmitter internals (Pressurize, Fill & Drain).
13Carry out the leak test by applying the pressure, to the transmitter & check for leakages. (Pressurize at full scale and wait for at least one minute). If there is any leakage in connections, tighten. Note: 1– Always use High pressure port of Diff. pressure transmitter and keep
  Low pressure port free in air for reference. 2- Never apply pressure more than the rated pressure; otherwise pressure sensor of transmitter will be damaged.
 14Connect multi-function HART communicator as shown in diagram and
 VIPswitch ON and wait for stabilize. Before start calibration, check configuration & confirms all parameters, (If required) which are supplied by Engineer by SMART calibrator. {Like: tag no, service name, process name, (pressure, level or flow), engineering units, in case of flow
  check  square  root  extractor  for  local  indication,  input    minimum  and
  maximum ranges, output current range set on 4~20mADC, Damping values, burn out at LRV & URV, date of calibration, next time schedule for calibration, etc.}
 15Exercise the pressure element to stretch for full range and back to zero to make sure that element can operate normal.
Calibration16A  procedure  of  digital  calibrating  of  a  SMART  transmitter  is  called Digital Trimming. A digital trimming is an exercise that allows you to correct the transmitter digital signal to match with plant standard (input pressure range and output digital mA). Digital trim of smart transmitter can be done in 2 ways. (As shown in step 22)
17Without apply actual pressure, apply 0% input pressure on the SMART communicator & wait to establish the output by the SMART transmitter till it reaches 4.0 mA on the SMART HART communicator & note the digital 4mA in the calibration sheet.
18Without apply actual pressure, Now apply 100% pressure on the SMART communicator according to range provided by Engineer and  wait  to  establish  the  digital  output  20.0mA  by  the  SMART Transmitter  on  the  SMART  HART  communicator  &  note  the  digital 20mA in the calibration sheet.
19If outputs of the above both value are correct then check middle 3 points by applying pressure from the HART Communicator  and wait to establish output on the HART communicator. (At 25% input pressure, digital output = 8mA, at 50% input pressure, digital output =12mA and at 75% input pressure, digital output=16mA) for rising and falling values. Note these values in the calibration sheet.
20Record these input/output values in the calibration sheet as found column or before calibration column.
21If all reading are correct and error is in limit or below of the design values then record these values in as found column or before calibration column and go to step 42.
22If deviation (error) is more or less than designed error and instrument is not passed by HART Communicator then adjustment is required. This adjustment is called trimming. There are 2 types of trimming. (1)  Sensor trimming    &  (2)   4-20mA trimming
 231st  way of trimming is Sensor trimming. Start HART communicator & go to options. Select the proper option.
24Performing a Sensor trimming: For sensor trimming we should follow the SMART communicator manufacturer procedure as mentioned in there manual. Normal guide lines are as follows.
25Apply 0% pressure (“low” range value) by the SMART communicator, stimulus to the transmitter and wait for stabilize.
26Execute 0% sensor (“low” sensor) trim function according to the SMART communicator manufacturer’s procedure.
27Apply 100% Pressure (“high” range value) stimulus to the transmitter and wait for stabilize.
28Execute 100% (“high”) sensor trim function according to the SMART communicator manufacturer’s procedure.
292nd  way of trimming is 4~20mA trimming. Start HART communicator & go to options. Select the proper option.
30Performing 4-20mA Trim. For 4~20mA trimming we should follow the SMART communicator manufacturer procedure as mentioned in there manual. General guide lines performing 4mA & 20mA Trimming.
31Using hand held HART communicator; put transmitter output into fixed current mode. The input value for this test is mA asked to produce by the transmitter. The output value can be measured by precision mA meter. Calculate the error between digital mA (PVAO) and produced by transmitter and analog mA on the precision mA meter. If the test does not pass and deviation is more than the designed error then follows the Manufacturer’s recommended procedure for trimming the output. This procedure requires 2 trim points 4mA and 20 mA.
32Execute 0% (“low “) output “4mA” trim test function on the transmitter.
33After stabilizing 4mA on the HART communicator, measure the output signal 4mADC on the precision or digital Amp. Meters.
34Execute 100% “High “output “20mA” trim test function on the transmitter.
35After stabilizing 20mA on the HART communicator, measure the output signal 20mADC on the precision or digital Amp. Meters.
36Enter / save these measured current values when prompt by transmitter.
37Once the trim procedure is completed, calibrate according the standard values known to be accurate. Set lower and upper ranges. Note: The only reason for trimming a SMART transmitter is to ensure accuracy over the long period of time.
38After completion of both trim tests, next step is the actual calibration by giving actual input pressure 0% to 100% and measure the 4~20mADC of all 5 points on the mA meter.
39Check repeatability by increasing and decreasing pressure and confirm all 5 points (0%, 25%, 50%, 75%, & 100%) proportional to output values and match with standard values. Calculate the error in %, it should be within range of designed error.
 40Record the all values in the calibrations sheet in after calibration column.
41Documented calibration throughout the HART communicator before and after  calibration,  in  such  way  communicator  gives  us  complete  result before and after calibration with the error calculation and can print result for us. These results can be shown like this chart.
42The SMART pressure transmitter or SMART diff. pressure transmitter trimming procures and input / output values should be inspected by Inspector and Quality Inspector for witness and record these values to sign the certificate after completion of job.
43After  test  re-adjust  the  original  value  of  damping  by  the  SMART communicator before installing in field.
44It  is  necessary to  adjust  head  correction  (If  any)  to  avoid  any wrong reading.
Completion45Once the test is completed, remove the test equipment and clean the tested device.
46Install the SMART transmitter back to its position and reconnect the instrument fittings, tubing without bending or damaging and ensure that connector is not cross fitted that can damage threading.
47Close the drain valve and open the inlet valve slowly to avoid sudden pressure entering in the transmitter sensor.
48In case of water / oil / chemicals, purge the air completely from the transmitters, tube lines / capillary tube, fill the transmitter carefully to avoid showing any wrong readings.
49Check for leakage during commissioning.
50Complete the check and calibration sheet and handover to the concerned I&C Engineer for inspection and signature

Leave a Comment

error: Content is Protected.