Analog, Digital Indicator & Recorder Calibration Procedure

1-   Analog Indicator (AI)

2-   Digital Indicator (DI) (Input: 4~20mADC)

3-   Digital single channel / multi-channel Recorders (DR) (input: 1~5VDC) (Pressure, Temperature, level, Flow& Valve position Indicator)

ProcedureGeneral Procedure for all stations.
Title of JobMaintenance Check & Calibration
ManpowerInstrument Technician Using PPE (Personal Protective Equipment)
Safety DocumentMaintenance Work Permits. & SCC (Safety Clearance Certificate) If Required
Tools   /   SpecialI &C Tool KitTest Equipment
Tools
Test Equipment:Note: Select test equipment according to the Indicator / Recorder.4~20 mADC Source 1~5VDC
  1-   DC 4~20mA Source 2-   DC 1~5 volt Source 3-   HART Communicator 4-   Crocodile lead wires.
Stores               & MaterialsCleaning spray, brush and cloth 
Job Description
ProcessStepsDuring  Maintenance
Isolation & Removal1Open the back cover of Indicator or recorder to gain access to the wires. Remove the wires by the core identification  and  insulate all  wires by insulation tape (Ensure it isn’t in   contact with each other, short circuiting or producing any earth).     Note: These types of AI, DI & DR can be calibrated at their own locations. It is not necessary to remove.
2Carry out the external cleaning, using a brush and approved cleaning spray to remove dust, contamination or solid particles.
3Inspect for external physical damage, general appearance & fitness.
Preparation4Write the all detail AI, DI or DR Tag No., Channel No. Service,  and Unit No. in the Calibration sheet
5Collect   the   range   and   data   (pressure,   temperature,   flow,   level   or percentage) & engineering units from the engineer and record in the calibration sheet.
6Set  up  test  equipment  for  AI as  per  the diagram shown: Note:   1- Separate power supply is not required for Analog Indicator. 2- Only 24VDC for input: 4~20mADC Pic. 1
 
7In case of Analog Indicator, connect the mA source to the AI as per core identification and switch ON the mA source, check the needle of indicator be raise from bottom and reaches to Zero point. Note: View reading of analog indicator perpendicularly on the scale.
8Set up test equipment for DI & DR as per the diagrams shown
Note:   1- Mostly all recorders works with 1~5 VDC Input signal.   2- Digital type of Indicators & recorders having universal inputs.   3– This set up can be used with separate AC power supply.   4- Digital indicator and recorder are only required for configuration. These are so accurate that calibration is not required. Even that we can check the output values by injecting inputs.
9If DI / DR are removed from the panel, then connect the separate power supply wires to power terminals and then switch it ON the power.
10Connect  the  Digital  Precession  Multifunction  HART  Calibrator to  the Digital indicator or recorder, requiring channel input terminal with core identification and Switch it ON. Now select the type of output. (1~5VDC / 4~20mADC).
  Note: 1- If input signal: 4~20mADC then signal in % is:  (4mA=0%, 8.0mA=25%, 12mA=50%, 16ma=75% & 20mA=100%)   2-  If  input  signal:  1~5VDC  then  signal  in  %  is:  (1V=0%,  2V=25%, 3V=50%, 4V=75% & 5V=100%)
 11If it is required to confirm and check the configuration of DI / DR.  then open set up option:
        Check the channel No.          Check the input type. (1~5VDC / 4~20mADC))          Check the Service name (like: Pressure, level, Flow etc.)          Check the range. (-10000 ~0~10000)          Check the engineering unit. (mm WC, Bar, Meter, M3/Hr.)
 Note: If any configuration is required to change. Ask engineer for further process.
Calibration12Apply 0 % signal to the AI / DI / DR from the mA / V source. View the reading on the indicator / recorder. It should show (0.00) value. Note: (1) Mostly all Mfg. Companies manufacturing analog indicators with Zero and Span adjustment screws as shown in Pic. 1. (Yamatake Co. provides Zero and Span adjustment screws) installed in Distillation Plants. (2)  Some  Mfg.  companies  only provide  Zero  adjustment  screw.  Span screws are not provided.   In these indicators we can adjust only zero. (YEW & Bailey Co. only provided Zero adjustment screw) Installed in Boiler 1~4 and Turbine 1~4. (3) In case of only zero adjustment screw, If there is error more than designed acceptable error, then divide this error by adjusting zero adjustment screw on all values (0, 25%, 50%, 75% and 100%). If still error is more than designed error, then replace the indicator with new indicator.
13Apply 100 % signal and view the reading, it should show 100% value. Note:  The  input  can  be  applied  in  increasing  and  decreasing  order (ascending and descending order) i.e.: 0%, 25%, 50%, 75% & 100% and vice versa.
14If above both values are correct then apply middle 3 points input signal (25%, 50% & 75%) on the calibrator and see the reading on the indicator / recorder.  It should show all values according to the input signal.
15Check these input / output values in sending / descending orders.
16If all 5 reading are matched with all 5 input signals then record these values in as found column or before calibration column. If error is within limit and acceptable then go to step 23.
 17If  error  is  more  than  the  designed  error  then  instrument  needs  to  be calibrated
18Apply 0% signal to the AI from the mA / V source. View the reading on the indicator / recorder. Adjust the zero from zero adjustment mechanical screw. In case of DI & DR, there should be Potentio meter on the PCB. (If available).
19Apply 100%  signal  from  mA  /  V  source  Adjust  the  span  from  span adjustment  mechanical  screw.    In  case  of  DI &  DR,  there should  be Potentio meter on the PCB. (If available).
20Repeat step 18 & 19 till the 0% and 100% reading should match with input signal.
21Again apply 5 points (0%, 25%, 50%, 75% and 100%) signal on the mA / V calibrator in ascending and descending order and view the readings on the indicator / recorder. It should match according to the input signals and error should be in limit.
22If calibration adjustment is successful, record the after adjustment results on the calibration sheet in after adjustment column.
23The analog indicator / digital indicator / digital recorder calibration should be inspected by Inspector and Quality Inspector for witness and record these values to sign the certificate after completion of job.
Completion24Once the test is completed, remove the test equipment and clean the tested device.
25Reconnect all wires at original positions according to the core identification. (If it was removed then install the analog indicator / digital indicator / digital recorder back to its position).
26Switch ON the power supply and commission the analog indicator / digital indicator / digital recorder. Check the reading. It should be 0% if unit is shut-down or under annual maintenance. If process is temperature then it should show ambient temperature.
27Complete the check and calibration sheet and handover to the concerned I&C Engineer for inspection and signature.

Leave a Comment

error: Content is Protected.