SMART Pressure Transmitter Analog Calibration Procedure

1-   SMART Gauge Pressure Transmitter.

2-   SMART Differential Pressure Transmitter. (Including DP type Level & Flow Transmitters)

ProcedureGeneral Procedure for all Power Stations.
Title of JobMaintenance Check & Calibration
ManpowerInstrument Technician Using PPE (Personal Protective Equipment)
Safety DocumentMaintenance Work Permits. & SCC (Safety Clearance Certificate) If Required
Tools/      SpecialI &C Tool Kit & special tools (if Required)Test Equipment
Tools
Test Equipment:Note: Select test equipment according to the max. Range & Medium. 1–  Digital  multi-meter  /  mA  meter  /  SMART HART Calibrator           
2-    Deadweight    Tester,    Standard    Pressure 
Gauge (0.5 Bar to 200 Bars) 3– Hydraulic pressure pump and standard pressure gauge (0 Bar to 250 Bars). 4– Air pressure pump with digital multifunction calibrator used for very low and low pressure (0 to 20000mmH2O or 0to 2 Bar or 0 to 20 Bars). 5– Water manometer or mercury manometer with air   pump   (0   to   1500   mm   H2O   or   0   to 1500mmHg). 6- Vacuum pump with digital multifunction tester.(0 to -760 mmHg / 0 to -30 inches of Hg or 0 to -1 Bar)          
Stores                  & MaterialsCleaning spray, brush and cloth 
 
Job Description
ProcessStepsDuring  Maintenance
Isolation & Removal1Isolate the transmitter by closing inlet valve of many fold or isolate from the main isolating valves of impulse lines.
2In case of oil or chemical process use secondary container to avoid spill of oil / chemical when isolating. Depressurize the transmitter and draining tapping lines.
3Confirm that power supply is OFF. Remove the wires from the transmitter terminal by the core identification and insulate all wires terminals by insulation tape (Ensure it isn’t in contact with each other, short circuiting or producing any earth).
 4Move away the tapping lines to avoid spill of oil or chemical from transmitter connections.   Disconnect the SMART pressure transmitter or differential pressure transmitter form the process carefully.
 5Carry out the Pressure transmitter / diff. pressure transmitter external cleaning, using a brush and approved cleaning spray to remove contamination or solid particles.
 6Inspect the Pressure or Diff. Pressure Transmitter for external physical damage, general appearance & fitness. (Check whether cover seals are intact).
Preparation7Write all the details of pressure or diff. pressure transmitter: tag no., range, service and unit no. in the calibration sheet.
8Collect the calibration range from Engineer of each transmitter (Millimeter WC till maximum range in bars) and note in the calibration sheet.
9Set up the test equipment as shown in the diagram:
10Ensure that the medium used for calibration is same as that of medium of the process (if possible) where transmitter is installed.
11Carry out purging (if required) to remove the process medium completely from the transmitter internals (Pressurize, Fill & Drain).
12Carry out the leak test by applying the pressure, to the transmitter & check for leakages. (Pressurize at max. range and wait for at least one minute). If there is any leakage in connections, tighten. Note: 1– Always use high pressure port of Diff. pressure transmitter and keep low pressure port free in air for reference. 2- Never apply pressure more than the rated pressure; otherwise pressure sensor of transmitter will be damaged.
13Connect multi-function HART communicator as shown in diagram and
VIPswitch ON and wait for stabilize. Before start calibration, check configuration & confirms all parameters (If required) which are supplied by  Engineer  by  SMART  calibrator.  {Like:  tag  no,  service  name, process name, (pressure, level or flow), engineering units, in case of flow
 check  square  root  extractor  for  local  indication,  input    minimum  and
 maximum  ranges,  output  current  range  set  on  4~20mADC,  Damping
  values, burn out at LRV & URV, date of calibration, next time schedule for calibration, etc.} Note: Make the damping 0% before calibration. After calibration readjust the damping on original values as before.
14Exercise the pressure element to stretch for full range and back to zero to make sure that element can operate normal.
Calibration15Without apply pressure check the output of transmitter should be 4mADC.
16Now apply 100% pressure according to range provided by Engineer and note the output of transmitter. It should be 20mADC.
17If output of the above both values are correct then check middle 3 points (at 25% input pressure, output = 8mADC, at 50% input pressure, output =12mADC and at 75% input pressure, output=16mADC) for rising and fallen values.
18In case of Vacuum transmitter.  Without creating vacuum check the output current  should  be  4.00mADC.  Now create the vacuum  in  the vacuum transmitter and note the other 4 points input / output values. (At 25% vacuum: output should be 8.00mADC, at 50% vacuum: output current should be 12mADC, at 75% vacuum: output should be 16mADC & at 100% vacuum: output should be 20mADC). Note: If we consider   0% vacuum at 20mADC then at 100% vacuum, current should be 4.0mADC
19Record these input/output values in the calibration sheet as found column or before calibration column.
20If all reading are correct and error is in limit & below the design values then record these values in as found column or before calibration column and go to step 29.
21If there is difference in reading more than error and adjustment is required. Then remove covers (If available) to gain access to zero adjustment and span adjustment screw. Note: (1) In case of Mfg.: Yamatake Co. SMART Transmitters following calibration procedure is used. (2) In case of Mfg.: YEW Co. SMART Transmitters there is mechanical Zero adjustment screw is available but span adjustment screw is not available.  So  digital  span  trim  adjustment  is  possible  by the  SMART communicator. (3) In case of any other Mfg. Co. SMART transmitters, Zero and span adjustment according to their procedure.
22Depressurize the transmitter completely to check 4.00mADC. At 0% input pressure, adjust transmitter output 4mADC by touch screen with magnetic stick. Touch the magnetic stick at the bottom of screen, Zero adjustment will appear. Change the position of magnetic stick (Left or Right to Increase or decrease mA) it will change mA on the mA meter. So adjust exact 4.0mADC. (Adjust bye zero screw if available)
 23Apply 100% input pressure to the transmitter sensor and view the output of transmitter, should be 20mADC.  If it is less or more, then adjust the span 20mADC by magnetic stick. Move the stick on the top of screen. Span adjustment  will  appear. Change the position  of magnetic stick  (left  or Right) it will change mA on the mA meter. So adjust exact 20.00 mADC on the mA meter.   (Adjust  by span screw if available)
24Repeat  steps  22  and  23  till  at  0%  input  pressure,  output  should  be 4.00mADC & at 100% input pressure, output should be 20mADC.
25If zero and span is corrected then check the other 3 points (at 25% input pressure = 8mADC, at 50% input pressure = 12mADC and at 75% input pressure=16mADC by increasing and decreasing the pressure.
26Check repeatability by increasing and decreasing pressure and confirm all 5 points (0%, 25%, 50%, 75%, & 100%) input / output values match with standard values. Check the error is in limit and under design value.
27Record these input & output values in calibration sheet in after calibration columns.
28Readjust the damping after calibration on original values as before.
29The pressure transmitter or diff. pressure transmitter input / output values should be inspected by Inspector and Quality Inspector for witness and record these values to sign the certificate after completion of job.
30It  is  necessary  to  adjust  head  correction  (If  any)  to  avoid  any wrong reading.
Completion31Once the test is completed, remove the test equipment and clean the tested device.
32Install the SMART transmitter back to its position and reconnect the instrument fittings, tubing without bending or damaging and ensure that connector is not cross fitted that can damage threading.
33If there is damper or capillary tube used before the transmitter. It should be inspected and cleaned or overhauled. (Replace gaskets or O-rings if necessary in damper).
34Close the drain valve and open the inlet valve slowly to avoid sudden pressure entering in the transmitter sensor.
35In  case  of  water  /  oil  /  chemicals,  purge  the  air  completely from  the transmitters, tub lines / capillary tube and fill the transmitter carefully to avoid showing any wrong readings.
36Check for leakage during commissioning.
37Complete the check and calibration sheet and handover to the concerned Instrument & Control Engineer for inspection and signature.

Leave a Comment

error: Content is Protected.