Sun Control System Fault Detection and Diagnostic

This article is about general and Fault Detection and Diagnostic for Sun Control System used in Integrated Automation System or Building Automation System.

Sun Control System Fault Detection and Diagnostic

  1. Blind/Shade Closure Failure

    1. Description:
      1. Generates a fault when the blinds and/or shades are open and the outside light level is above a threshold as measured by the sun sensor. This indicates that either the associated blind/shade motor or controller is not closing the blind/shades when the outside lighting level exceeds a set point. Fault dependencies and associated scenarios include the following;
        • The fault rule will make sure the exterior lighting level, as measured by the associated sun sensor, is currently utilized and above the set point.
        • The fault rule will make sure the interior lighting level, as measured by the associated daylight or multi sensor, is currently utilized and above the set point.
    2. Requirements:
      • Blind Position Command or Shade Position Command: Blind/Shade position command is required, but status can be used as a primary reference.
      • Exterior Lighting Level: Measured in either lumens of foot candles from the sun sensor.
      • Interior Lighting Level: Measured in either lumens of foot candles from the ceiling mounted daylight or multi sensor.
  2. Blind/Shade Opening Failure

    1. Description:
      1. Generates a fault when the blinds and/or shades are closed and the outside light level is within a threshold as measured by the sun sensor. This indicates that either the associated blind/shade motor or controller is not opening the blind/shades when the outside lighting level is within the setpoint. Fault dependencies and associated scenarios include the following;
        • The fault rule will make sure the exterior lighting level, as measured by the associated sun sensor, is currently utilized and within the setpoint.
        • The fault rule will make sure the interior lighting level, as measured by the associated daylight or multi sensor, is currently utilized and within the set point.
    2. Requirements:
      • Blind Position Command or Shade Position Command: Blind/Shade position command is required, but status can be used as a primary reference.
      • Exterior Lighting Level: Measured in either lumens of foot candles from the sun sensor.
      • Interior Lighting Level: Measured in either lumens of foot candles from the ceiling mounted daylight or multi sensor.
  3. Sensor Failure

    1. Description:
      • Finds periods over a duration when a sensor does not change by a threshold for a 24-hour period and equipment is running.
    2. Requirements:
      • Sensor: Any numerical data point, including statuses and operating mode(s).

Vertical Transportation System Fault Detection and Diagnostic

Plumbing and Life Safety System | Fault Detection and Diagnostic

HVAC Control System Fault Detection and Diagnostic

Lighting Control System Fault Detection and Diagnostic

Electrical Power Metering and Generator Control System

Security Control System Fault Detection and Diagnostic | Automation

HVAC System Functional Specification | Integrated Automation System

Water Booster Pump Control System Functional Specification

Building Automation System Functional and Technical Specification

Leave a Comment

error: Content is Protected.