CALIBRATION OF VALVES WITH ACTUATOR AND ACCESSORIES

CALIBRATION OF VALVES WITH ACTUATOR AND ACCESSORIES

CALIBRATION OF VALVES WITH ACTUATOR AND ACCESSORIES

Note:Valve calibration will be carried out at warehouse up to 2” (inch) without transportation and the 3” (inch) above are carried Site calibration.
·         TSO Valves shall be calibrated after the seat leakage test. Hand wheel test as the part of calibration, manual operation of the hand wheel shall override the automatic operation.

Self-Actuating Valves (i.e., pressure regulator)

Visual checking shall be carried out to ensure that there is no damage on the body.
Tag no., range, & type shall conform to the data sheet.
If required, detailed calibration procedure for self-actuating valves shall adhere to manufacturer’s manual and shall be confirmed.
Final set point adjustment is required during start-up operation in order to make it suitable with process variables.
Note: No such confirmation (final set point) is required for pressure regulator with internal relief  feature (i.e., air filter regulator for CV, I/P, etc.).

Diaphragm Actuator, Spring Adjustment (Bench Set)

The following items shall be checked:
·                  Size and type
·                  Stroke range
·                  Spring range
Hook up testing equipment as illustrated below:

Procedure for Valve calibration With Pneumatic Calibrator:

1. Adjust pneumatic signal so that the valve closes slowly, and stop when the valve fully closed.
2.  Dynamic error band, which is the difference between upscale and downscale plots at any given input signal, shall be less than 3.0% which valve travel. If the desired value cannot be obtained with spring
adjustment, change stem length by adjusting connector assembly.
3.  Adjust pneumatic signal so that the valve opens slowly, and stop when the valve fully opened.
4.  Read the pneumatic signal value and compare it with the actuator’s range. If the difference is greater than 3.0%, change spring and recheck closing and opening.
5.  Adjust position indicator scale so that the indication works correctly.
6.   Inject pneumatic signal 0%, 25%, 50%, 75% and 100% of its range and read valve position with signal rising and falling.
7.  Check air failure action by disconnecting air supply.
8.  Check power failure action by disconnecting power supply.
9.  Speed of stroking time from full open to full close shall be checked, if required. Note down in form and compare with datasheet.
Other Type Actuator
The actuators other than diaphragm type shall be checked for the following items before the stroke check
(positioner calibration).
Piston Type Actuator
·                   Size and type
·                   Stoke range
·                   Leakage
 Electrical Actuator
·                   Electrical insulation of motor and other electrical parts
·                   Limit switches and/or torque switches
·                   Positioner assembly
·                   Power requirement
·                   Local open/close/stop switch
·                   Hand wheel operation

Positioner (Stroke check) Procedure Calibration:

                    I. After checking the valve stroke all valves shall be checked with positioner, positioner shall be
checked.                 Functions of HART Calibrator please click here.
                  II.  Determine signal range and characteristics curve through full stroke of valve. Before calibration curve shall be provided.Select proper travel character cam if provided.
                 III.   Connect Power Supply and and/or air supply to the positioner and actuator.
                 IV.      Connect proper input signal source (4-20mA) to the positioner.
                 V.         Adjust input signal so that the valve closes slowly, and stop when the valve is fully closed.
                VI.       Read the input signal and adjust zero adjustment when error is found. Repeat steps until the valve corresponds with closing signal within error limit.
               VII.       Adjust input signal so that the valve opens slowly, and stop when the valve fully opened.
              VIII.       Read the input signal and adjust zero adjustment when error found. Repeat step until the valve corresponds with closing and opening signal within error limit.
              IX.       Inject signal 0%, 25%, 50%, 75%, and 100% of its range and read valve position with signal rising and falling. Action of the positioner shall be checked (direct or reverse).
               X.       Analyse the stroke characteristic curve and figure out the reproducibility which includes dead band and hysteresis.
              XI.       If the character or the reproducibility is not acceptable, check feedback cam style and/or mechanical condition of all moving parts and correct existing deficiencies.
              XII.       Mechanical stops shall be checked as per data sheet.

Read more

HART Utilities and Functions of HART Calibrator

This article is about HART Utilities and Functions of HART Calibrator and focusing to the engineers, technicians and supervisors. You will find lot of documents related to this article. Just navigate our website  www.paktechpoint.com  and find more articles. Please! Do not forget to subscribe our You tube channel also. Thanks in Advance.

PLEASE SUBSCRIBE OUR PAKTECHPOINT YOUTUBE CHANNEL

HART Utilities and Functions of HART Calibrator

Following functions to be discussed here.

Tagging
Trimming
Configuring
Loop Test
Commissioning
Utilities
•–Ininitial commissioning, the transmitter needs to be:
»Tagged
»PV units Set
»Ranging Set
»Damping adjusted
»Transfer function changed
•Pressure only
•Sq, Root, Linear
HART Utilities and Functions of HART Calibrator
Configuring the temperature sensor on a smart temperature transmitter
•Smart temperature transmitters can be configured for a variety of sensors
–Thermocouples (many types)
–RTD (many types), 2,3 or 4 wire
•Select Sensor from the setup menu to access
–Supported devices
HART Utilities and Functions of HART Calibrator

Read more

HART Pressure Calibration and Zero Calibration of Pressure Transmitter

This article is about HART Pressure Calibration and Zero Calibration of Pressure Transmitter and focusing to the engineers, technicians and supervisors. You will find lot of documents related to this article. Just navigate our website  www.paktechpoint.com  and find more articles. Please! Do not forget to subscribe our You tube channel also. Thanks in Advance.

PLEASE SUBSCRIBE OUR PAKTECHPOINT YOUTUBE CHANNEL

HART Pressure Calibration and Zero Calibration of Pressure Transmitter

HART Pressure Calibration and Zero Calibration of Pressure Transmitter

 

•Almost identical to analog transmitter connections
–HART cable connection required for digital adjustment.
•Configure the Calibrator.
•Acquire the test parameters (HART Query).
•Configure the input/output of the calibrator.
•Define the test parameters.
a)Acquire HART Configuration b) Configure the measure and source function of calibrator  c) Define the performance test

Calibration-As Found Test

•Document the pre-adjustment transmitter condition

Calibration- Digital Adjustment

•Perform HART trim on the transmitter
HART trim on the transmitter
As Left Test
•Verify post adjustment  condition of transmitter
•If still Out Of Tolerance (OOT)
–Repeat adjustment
–Re-run as-left until it  passes within tolerance
•If it cannot be satisfactorily adjusted…
–Were there leaks in the fittings?
HART trim on the transmitter

Read more

BASIC CALIBRATION FUNCTIONS IN FLUKE PROCESS HART CALIBRATOR

This article is about BASIC CALIBRATION FUNCTIONS IN FLUKE PROCESS HART CALIBRATOR and focusing to the engineers, technicians and supervisors. You will find lot of documents related to this article. Just navigate our website  www.paktechpoint.com  and find more articles. Please! Do not forget to subscribe our You tube channel also. Thanks in Advance.

PLEASE SUBSCRIBE OUR PAKTECHPOINT YOUTUBE CHANNEL

BASIC CALIBRATION FUNCTIONS IN FLUKE PROCESS HART CALIBRATOR

HART means Highway addressable remote transducer. It is hybrid (analog plus digital) open protocol for instrumentation industry . This HART is alternative to 4-20 mA signal and superimposed on  4-20 mA signal with additional indformation. This is called HART commmunication protocol.

Read also more about HART::::: HART Communication Protocol & its Application

Following points to be covered in this article.
·Identify and communicate with HART transmitters over the bus
·Read transmitter process variable value (PV)
·Read and change range value (LRV, URV)
·Review and change basic sensor configuration.
·Calibrate most input sensor sections
·Perform output trim (4-20 mA) on all transmitters with universal command implementation.
Command Sets, three types.

Read more

error: Content is Protected.