This article is about general and technical requirements for Transducer used in Integrated Automation System or Building Automation System.

TRANSDUCERS TECHNICAL REQUIREMENTS FOR INTEGRATES AUTOMATION SYSTEM

TRANSDUCERS <Modify as required to match project design>

  1. Standard Capacity Electronic-to-Pneumatic (E-P) Transducers: E-P transducers shall be Voltage-to-Pneumatic (V-P) type, Current-to-Pneumatic (I-P) type:
    • Electrical Power Supply: 24 VAC or 24 VDC
    • Pneumatic Air Supply: 30 psig (2.07 bar) maximum
    • Air Capacity: 1100 scim @ 20 psig (300 cm3/sec @ 1.4 bar)
    • Air Consumption: Zero at steady state
    • Output Span: 0-20 psig (0-1.4 bar)
    • Input: 4-20 mA, 0-5 VDC, 1-5 VDC, 0-10 VDC, 2-10 VDC, 0-15 VDC, or 3-15 VDC input
    • Gauges: Provide with main and branch air gauges
    • Enclosure: Polymer designed for surface or panel mount
    • Air Connections: ¼ inch (6.35 mm) barbed
    • Failure Mode on Power Loss: Non-failsafe transducers shall have no output air loss.  Failsafe transducers shall exhaust output upon power loss.
    • Acceptable Manufacturers: <Confirm list>
      • Honeywell RE Technologies Model UCP-522
      • BEC Controls Corp
      • Approved equal
  2. RE Technologies Model UCP-52 Electronic-to-Pneumatic (E-P) Transducers: E-P transducers shall be Voltage-to-Pneumatic (V-P) type, Current-to-Pneumatic (I-P) type, Phase cut Type:
    • Electrical Power Supply: 24 VAC or 24 VDC, 100 mA
    • Accuracy: +/- 1 percent
    • Feedback: Branch pressure feedback from an on board pressure sensor – VDC Feedback
    • Override: Manual Potentiometer
    • Pneumatic Air Supply: 25-30 psig (2.07 bar) maximum
    • Air Capacity: .5 scim @ 20 psig (300 cm3/sec @ 1.4 bar)
    • Air Consumption: None
    • Output Span: 3-15 psig factory set field adjustable
    • Input: 4-20 mA, 0-5 VDC, 0-10 VDC, 2-10 VDC, 0-18 VDC, 0-20V Phase Cut input
    • Gauges: Provide with main and branch air gauges
    • Enclosure: NEMA 1
    • Air Connections: ¼ inch (6.35 mm) barbed brass
    • Failure Mode on Power Loss: Non-failsafe transducers shall have no output air loss.  Failsafe transducers shall exhaust output upon power loss.
    • Acceptable Manufacturers: <Confirm list>
        • Honeywell
        • TRIATEK CP-3000
        • Approved equal