In this article
This article is about High Voltage Motor and Compressor Grounding System related to topic of Electrical Standard Grounding.
High Voltage Motor and Compressor | Electrical Standard Grounding
GROUND REFERENCE PLATE ENCLOSURE | ELECTRICAL STANDARD GROUNDING
Equipment Grounding Requirements | Importance | Design
MOTOR
TERMINAL
BOX
MOTOR
GEAR
BOX
COMPRESSOR
TO GROUNDING
ELECTRODE SYSTEM
SEE CONTRACT DRAWINGS
POWER CONDUIT(S)
OR CABLE(S)
EQUIPMENT GROUNDING
CONDUCTOR(S)
W/ POWER CONDUCTORS
SEE CONTRACT DRAWINGS
GROUND BUS
TO GROUNDING
ELECTRODE SYSTEM
SEE CONTRACT DRAWINGS
PLATFORM STRUCTURAL
STEEL (TYPICAL)
#2/Ø (7Ømm2) BARE
SOFT- DRAWN
COPPER GROUND
CABLE (TYPICAL)
- CONNECTIONS TO MOTOR, GROUND BUS, GEAR BOX AND COMPRESSOR TO BE MADE WITH COMPRESSION LUGS.
- CONNECTIONS TO PLATFORM OR BUILDING STRUCTURAL STEEL (NOT ASSOCIATEDWITH COMPRESSOR ASSEMBLY) TO BE MADE W/ CADWELD TYPE VF OR VB.
- CABLE TO CABLE CONNECTIONS SHALL BE CADWELD TYPE OR BURNDY TYPE YGHC-C ‘HYTAP’.
- ALL GROUND CONDUCTORS SHALL BE PROPERLY SUPPORTED AROUND EQUIPMENT AND RUN IN A NEAT AND WORKMAN LIKE MANNER. SEE STD-P316D.
Ø 1 2 3 4
DATE 9/26/94 7/31/95 9/1ø/96 8/22/01
AIR
AppD.
AMS
GR BUDMAN
DRAWN
TW BECK
CHECKED
ENGINEER
TW BECK
APPD&
DATE
8/22/øl
8/22/01
8/22/01
ELECTRICAL STANDARD
GROUNDING
HIGH VOLTAGE MOTOR
AND COMPRESSOR
DWG NO.
STDG3Ø7A
SCALE
nowcrs —v