This article is about Electrical Standard Grounding related to topic of Foundation Reinforcing Bar.
Electrical Standard Grounding Foundation Reinforcing Bar
Electrical Standard Grounding Foundation Reinforcing Bar
High Voltage Motor and Compressor | Electrical Standard Grounding
Commissioning: Grounding Systems
GROUND REFERENCE PLATE ENCLOSURE | ELECTRICAL STANDARD GROUNDING
Schematic & Wiring Diagrams | Electrical Standard Symbols
Schematic & Wiring Diagrams | Electrical Standard Symbols
Reinforcing Steel Specification | Reinforcing Bars Procedures
GROUNDING PIGTAIL
SEE CONTRACT DRAWINGS
FOR QUANTITY AND LOCATIONS
TYPICAL
FUTURE STRUCT. STL. COLUMN
OR PIPE SUPPORT
3″ (75MM)
-.<— FUTURE
COLUMN
STRUCT. STL.
OR PIPE SUPPORT
RE-BAR (T Y p)
CADWELD TYPE
OR BURNDY TYPE YGHC-C
CONNECTION (TYP)
EXPANSION JOINT (TYP)
BONDING JUMPER
CONNECT ALL FLOOR
SECTIONS TOGETHER
CADWELD TYPE OR
BURNDY TYPE YGHC-C
CONNECTION (TYPICAL)
BONDING JUMPER (BUILDINGS ONLY)
FURNISH AT EACH PIGTAIL LOCATION
WHERE FLOOR SLAB & FOUNDATION
ARE POURED SEPARATELY
*2/Ø (7Ømm2) BARE SOFT-DRAWN COPPER GROUNDING ELECTRODE CONDUCTOR
SEE CONTRACT DRAWINGS FOR
2/-01 (6ØØmm)
INSTALLATION DETAILS. TYPICAL
SKIRT
TYPE OR
BURNDY TYPE YGHC-C
CONNECTION (TYPICAL)
CADWELD TYPE OR
BURNDY TYPE YGHR-C
CONNECTION (TYPICAL)
GROUND ROD
SEE CONTRACT DRAWINGS
FOR QUANTITY AND LOCATIONS
TYPE
TANK
OR
COLD
BOX
NOTE
ALL REBAR BONDING JUMPERS SHALL BE
#2/Ø BARE SOFT-DRAWN COPPER
REV.
5
DATE
9/26/94
7/31/95
9/1ø/96
10/20/97
9/6/01
03/02/06
AppD.
TWB
TWB
AMS
TYPICAL
GR BUDMAN
DRAWN
TW BECK
CHECKED
ENGINEER
TW BECK
APPD&
DATE
9/5/01
9/6/Øl
9/6/Øl
ELECTRICAL STANDARD
GROUNDING
FOUNDATION
REINFORCING BAR
DWG NO.
STDG313A
SCALE
nowcrs —