Temperature Transmitter Calibration Procedure

1-   Temperature Transmitter (T/C to E.I Converter)

2-   Temperature Transmitter (RTD to E.I Converter)

ProcedureGeneral Procedure for all stations.
Title of JobAnnual Maintenance Check & Calibration
ManpowerInstrument Technician Using PPE (Personal Protective Equipment)
Safety DocumentMaintenance Work Permits & SCC (Safety Clearance Certificate) If Required
Tools/          SpecialI &C Tool Kit + any special tools (if Required)Test Equipment
Tools
Test Equipment:Note: Select test equipment according to the max. Range of Temperature Transmitter. 1– Ice Pot 2- Boiling Water 3– mV generator with Temp. Compensator. 4- Thermocouple temperature calibrator. 5- RTD temperature calibrator. 6- Multifunction temperature calibrator. 7- Digital precession temperature Calibrator. 8– Digital HART Calibrator & Communicator.Temperature Transmitter Calibration Procedure
Digital Multifunction Calibrator     Digital HART. Calibrator
Stores & MaterialsCleaning spray, brush and cloth  
Job Description
ProcessStepsDuring  Maintenance
Isolation & Removal1There   are   two   types   of Temperature Transmitters. Direct    mount    type    TT. Mounted in field.
1)  Thermocouple type TT. 2)  RTD type TT.
temperature transmitter calibration procedure
2Remote mount type TT. Mounted in remote area or in control room.
1)  Thermocouple type TT. 2)  RTD type TT.
temperature transmitter calibration procedure
3Open the cover of temperature transmitter and remove the wires of T/C or RTD with core identification from the transmitter terminals.
4Check the power supply by multi mete and it should be OFF. Remove the wires and insulate all wires by insulation tape (Ensure it isn’t in contact
  with each other, short circuiting or producing any earth). Remove the fittings, brackets, vibration suppressers etc. (If available).
 51) Direct mount Temperature transmitter:  Remove the temperature transmitter from the well by opening upper nut, which is tightened in the well.
 62) Remoter mount type Temperature Transmitter: Remove from the field panel or control room panel for calibration. (There are many types of TT as shown above pictures. These can also be module type) Note: These transmitters can be calibrating at their own locations.
 7Inspect the Temperature transmitter for external physical damage, general appearance & fitness. (Check whether cover seals are intact).
 8Carry out the temperature transmitter external cleaning, using a brush and approved Cleaning spray to remove contamination or solid particles.
Preparation9Write the all details of Temperature Transmitter, Temperature range in degree C, input T/C (Type) or RTD (Type), Tag No., Service and Unit No. in the Calibration sheet.
10Open the cover of the Transmitter and set up the test equipment as per the diagram shown.

M M.F. Temperature                      Dry bath tester    Cold & Hot water tester Calibrator  Remote Mount TT  OR   Direct mount TT
11Select the connections according to the measuring principle (T/C or RTD) for multifunction temperature calibration.
Temperature Transmitter Calibration Procedure
12Switch ON the power supply to the temperature transmitter. Now switch on the multi-function temperature calibrator and select the option input type. If it is thermocouple temperature transmitter then select T/C on the multifunction temperature calibrator, then select type of T/C (“T”, “J”, “K” type or any other type) used in the system. Note: Multifunction temperature calibrator will automatically compensate the ambient temperature according to the type to T/C.
13If it  is  RTD temperature transmitter select RTD on the multifunction temperature calibrator and then select type of RTD (“PT100 ohms”, type or any other type) used in the system.
  
14Select temperature transmitter range in degree C, (0-100C, or 0-300C) on the multifunction temperature calibrator which will be shown on the indicator in control room. (Collect the temperature range from MEW I & C Engineer).
15Select  the  output  4  –  20mADC  on  the  multifunction  temperature calibrator.
Calibration16We have two methods of temperature transmitter calibration. 1-  Calibration by multifunction temperature calibrator (this is called cold calibration procedure) 2-  Calibration by temperature bath or by water. (Cold water and hot water calibration) (This is called hot calibration procedure)
171st method of TT calibration. (Cold Calibration Procedure) Calibration by multifunction temperature calibrator. Apply  0%  input   temperature  “0”degree  C   from   the  multifunction temperature calibrator and see the output of Transmitter, it should be 4.00mADC.
18Apply 100% input temperature (full range temperature) in degree C from the multifunction temperature calibrator and see the output of Transmitter, should be 20.00mADC. Note: The temperature can be applied in increasing and decreasing order (ascending and descending order) i.e.: 0%, 25%, 50%, 75% & 100% and vice versa.
19Now apply input temperatures 25%, 50% 75% from the multifunction temperature calibrator and see the outputs of Temperature Transmitter (TT),  it  should  be  according  to  the  percentage  of  input  temperature. 8mADC, 12mADC, & 16mADC.
202nd method of TT calibration. (Hot Calibration Procedure) Calibration by temperature dry bath or by cold water and hot water test. Set up the test equipment as shown below:
21Insert the temperature transmitter sensor (Bulb) in ice water for “0” degree C as shown in diagram.  Wait  for stabilization  of temperature and  see  the  output  of  Transmitter  reaching 4.00mADC.
22Now heat up the water by burner till it starts boiling (100 degree C) i.e. 100% temperature as shown in diagram. Now wait for temperature to stabilize  and  see the output  of Transmitter, it should reach to 20.00mADC.
Temperature Transmitter Calibration Procedure
 23In the above both procedures if temperature is correct and matching with input temperature at 0%, 25%, 50% 75% & 100% then record the results on  the  check  and  calibration  sheet  in  the as  found column  or before calibration column
24If as  found results  are correct  and  error on  all points are in limit of designed error. Then go to step 32.
25In case of difference in reading, error is more than designed error then adjustment is required go to next step.
26Apply 0% input temperature “0” degree C from the multifunction temperature calibrator or dip the sensor bulb in ice water & wait for stabilizing the output  of Transmitter.  Now adjust  the zero adjustment screw to bring output current exactly at 4.00mADC.
27Apply 100% temperature to the transmitter from the multifunction temperature calibrator or dip the sensor bulb in boiling water wait for stabilizing the output of Transmitter. Now adjust the span adjustment screw to bring current output exactly at 20.00mADC.
28Repeat steps 26 and 27 till 0% & 100%. Values of temperature & output of transmitter (4-20mADC) should match according to the % tag of input temperature.
29If with 0% input temperature matches with output of TT is 4.00mADC and 100% input temperature matches with output of TT is 20.00mADC. Then check the other 3 middle points (25% input temperature = 8mADC, 50% input temperature = 12mADC and 75% input temperature =16mADC.)
30Check repeatability by increasing and decreasing temperature input  and confirm all 5 points (0%, 25%, 50%, 75%, & 100%) output values match with standard values 4-20mADCand within acceptable error.
31Record input and output values according to the percentage in calibration sheet in after calibration columns.
32The temperature transmitter calibration should be inspected by MEW Inspector and Quality Inspector for witness and record these values to sign the certificate after completion of job.
Completion33Once the TT calibration is completed, remove the test equipment. Install the Temperature transmitter back to its position.
34Reconnect the power supply and Thermocouple or RTD wires on its original terminal according to the core identification. Fix the cover properly and clean the tested device.
35In case of direct mount TT, ensure that connection are not cross fitted with thermo well that can damage threading.
36Check the condition of the fittings, brackets, vibration suppressers etc. Repair or replace as found necessary
37Commission the Temperature Transmitter and check the readings. It should be nearly ambient temperature, if unit is under annual maintenance.
38Complete the check and calibration sheet and handover to the concerned MEW I&C Engineer for inspection and signature.

Leave a Comment

error: Content is Protected.