Electrical Standard Bus Duct Support Detail

This article is about Electrical Standard Bus Duct Support Detail for Electrical System.

Electrical Standard Bus Duct Support Detail

Electrical Standard Bus Duct Support Detail

Equipment Grounding Requirements | Importance | Design(Opens in a new browser tab)

High Voltage Motor and Compressor | Electrical Standard Grounding(Opens in a new browser tab)

Schematic & Wiring Diagrams | Electrical Standard Symbols(Opens in a new browser tab)

GROUND REFERENCE PLATE ENCLOSURE | ELECTRICAL STANDARD GROUNDING(Opens in a new browser tab)

NOTE: WHERE BUS DUCT SUPPORT EXCEEDS 12 FOOT (3.7M) REVIEW
SUPPORT DETAIL WITH CIVIL/STRUCTURAL ENGINEERING.
DO NOT USE THIS SUPPORT DETAIL
BUS DUCT
SUPPORT
SECURE BUS DUCT
WITH ANGLE CLIP
BOLTED TO ANGLE
31 (75mm)
X xl/411 CHANNEL
(125mm X 75mm X 6mm)
3 1/411 (9Ømm) ØSTANDARD
WEIGHT PIPE
X xl/211 STEEL PLATE
(25Ømm X 25Ømm X 12mm)
ANCHOR TO FOUNDATION
WITH 3/4″ (2Ømm)
KWIK BOLT II ANCHORS
(OR EQUAL)
(25mm) GROUT
REV.
1
2
APPD.
TYP
3/16 ”
GR BUDMAN
DRAWN
TW BECK
CHECKED
ENGINEER
TW BECK
APPD.
(5mm)
DATE
9/26/94
9/11/96
9/24/01
DATE
9/24/01
9/24/01
9/24/01
ELECTRICAL STANDARD
BUS DUCT
SUPPORT DETAIL
DWG NO.
STDP329A
TOP OF SUPPORT
FOUNDATION

Leave a Comment

error: Content is Protected.