NOTE: WHERE BUS DUCT SUPPORT EXCEEDS 12 FOOT (3.7M) REVIEW
SUPPORT DETAIL WITH CIVIL/STRUCTURAL ENGINEERING.
DO NOT USE THIS SUPPORT DETAIL
BUS DUCT
SUPPORT
SECURE BUS DUCT
WITH ANGLE CLIP
BOLTED TO ANGLE
31 (75mm)
X xl/411 CHANNEL
(125mm X 75mm X 6mm)
3 1/411 (9Ømm) ØSTANDARD
WEIGHT PIPE
X xl/211 STEEL PLATE
(25Ømm X 25Ømm X 12mm)
ANCHOR TO FOUNDATION
WITH 3/4″ (2Ømm)
KWIK BOLT II ANCHORS
(OR EQUAL)
(25mm) GROUT
REV.
1
2
APPD.
TYP
3/16 ”
GR BUDMAN
DRAWN
TW BECK
CHECKED
ENGINEER
TW BECK
APPD.
(5mm)
DATE
9/26/94
9/11/96
9/24/01
DATE
9/24/01
9/24/01
9/24/01
ELECTRICAL STANDARD
BUS DUCT
SUPPORT DETAIL
DWG NO.
STDP329A
TOP OF SUPPORT
FOUNDATION