Integral Orifice Material Selection Criteria Design – Flow Measurement

This article is about Integral Orifice Material Selection Criteria Design – Flow Measurement of Instrumentation and Control Systems as per International Codes and standards for Commercial Buildings, Plants and Refinery Projects.

Integral Orifice Material Selection Criteria Design – Flow Measurement

Material Receiving General Checklist for Instrumentation & Control

General Requirements

  1. Purchase Order and Instrument specification sheet criteria shall be confirmed and compared with instrument stainless steel tags / labels and nameplates, and shipment checked for damage, prior to acceptance of the shipment
  2. Verify that all the instruments are from technically acceptable vendors
  3. Integral orifices shall be sized and installed in accordance with manufacturer’s recommendations. Manufacturer shall provide meter sizing and flow calculations. (PIP PCCFL001 Sec. 3.6.2).
  4. Minimum straight run pipe length requirements shall be in accordance with manufacturer’s recommended lengths. (PIP PCCFL001 Sec. 3.6.3)
  5. Unless otherwise required by process services, wetted metal parts shall be type 316 SS. Other wetted components shall be compatible with the process. (PIP PCCFL001 Sec. 3.6.4)
  6. A strainer shall be specified if needed to avoid plugging of the orifice. (PIP PCCFL001 Sec. 3.6.5)

International Standard and Codes for Instrumentation Accessories

  1. Turbine Meter Material Selection Criteria Design & Flow Measurement
  2. Pitot Tube Design Requirement in Process Industry

3. SAES-J-002 -Technically acceptable instruments, 23 June 2008
4. SAES-J-003 – Instrumentation Basic Design, 16 January 2008
5. SAES-J-100 – Process Flow Metering, 05 April 2008
6. PIP PCCFL 001 – Flow Measurement Criteria , August 2006, Process Industry Practices Process Control