Thermocouple RTD and Well Commissioning Checklist
Followings are commissioning checklist points for Thermocouples and RTDs.
- Verify per specification sheet.
- Make sure all Tagging correct.
- Verify Correct location in vessel or line.
- Correct Thermo/Couples and lead wire material.
- T/C tip checked for grounding.
- Lead wire disconnected at both ends and checked for polarity.
- Make sure, Continuity checked wire/wire and wire/ground.
- Signal injected from field. Correct instrument and point number respond in control room.
- Sufficient immersion depth. Element/well.
- RTD resistance lead connection correct.
Thermometers and Wells Commissioning Checklist
- Verified per specification sheet.
- Correct location and line.
- Can be read from nearest access or control point.
- Accessible for maintenance.
- Sufficient immersion depth. Element/well.
- Cleaned for oxygen service.
Following are more commissioning checklist for Electrical and Instrumentation.
Control Valve Commissioning Checklist
Switch Valves, TSA, and PSA Valves Commissioning Checklist
Pressure Transmitter Commissioning Checklist
Temperature Transmitter (Filled System) Commissioning Checklist
Differential Pressure Transmitter Commissioning Checklist
Displacement Level Instrument Commissioning Checklist
Multipoint Recorder Commissioning Checklist
Orifice Plate/Flow Nozzle Commissioning Checklist
Analyzers Commissioning Checklist
Machine Controls Commissioning Checklist & Instrumentation
Vibration Monitors Proximity/Inertia Commissioning Checklist
Surge Control System Commissioning Checklist
Thermocouple RTD and Well Commissioning Checklist
Alarm Switches Commissioning Checklist
Locally Mounted Controller Commissioning Checklist
Panel Controller Pneumatic/Electronic Commissioning Checklist
Panel Controller Pneumatic/Electronic Commissioning Checklist
Signal Modifiers Electronic and Pneumatic – Commissioning Checklist